XR30CX

 

3/4 

did 

Digital input alarm delay when i1F=EAL or i1F=bAL: (0÷255 min) delay between 
the detection of the external alarm condition and its signalling. 

 

With i1F= dor: door open signalling delay.

 

With  i1F=PAL:  time  for  pressure  switch  function.  It  is  the  time 

interval to calculate the number of the pressure switch activation. 

nPS 

Number  of  pressure  switch  activation:  (0

15)  Number  of  activation,  during  the 

did interval, before signalling an alarm event (i2F=PAL).  
If the nPS activation during did time is reached, switch off and on the instrument to 
restart normal regulation. 

odc 

Compressor status when open door: (no; FAn; CPr;F_C;)  no = normal;  
FAn = normal; CPr = compressor OFF, F_C = compressor OFF. 

rrd 

Outputs restart after doA alarm: (n; Y) n = outputs not affected by the doA alarm;  
Y = outputs restart with the doA alarm. 

HES 

Temperature  increase  during  the  Energy  Saving  cycle:  (-30.0

30.0°C;  -54

54°F)  it  sets  the  increasing  value  of  the  set  point  [SET+HES]  during  the  Energy 
Saving cycle. 

OTHER 

Adr 

Serial  address:  (1÷244)  identifies  the  instrument  address  when  connected  to  a 
ModBUS compatible monitoring system. 

PbC 

Type of probe: (ntC, CtC) it allows to set the kind of probe used by the instrument:  
PtC = PTC probe, Pt1 = Pt1000 probe. 

onF 

On/Off key enabling: (nU; oFF; ES) nU = disabled; oFF = enabled; ES = not set it. 

rSE 

Real set point: it shows the set point used during the energy saving cycle or during 
the continuous cycle. 

rEL 

Software release for internal use. 

Ptb 

Parameter table code: readable only. 

8. DIGITAL INPUT

The free voltage digital input is programmable in different configurations by the i1F parameter. 

8.1

 

DOOR SWITCH INPUT  (i1F = dor) 

It signals the door status and the corresponding relay output status through the odC parameter: no, 
Fan = normal (any change); CPr,   F_C = Compressor OFF. 
Since the door is opened, after the delay time set through parameter did, the door alarm is enabled, 
the display shows the message “dA” and the regulation restarts is rtr=Y. The alarm stops as soon 
as  the  external  digital  input  is  disabled  again.  With  the  door  open,  the  high  and  low  temperature 
alarms are disabled. 

8.2

 

GENERIC ALARM (i1F = EAL) 

As soon as the digital input is activated the unit will wait for did time delay before signalling the “EAL” 
alarm message. The outputs status doesn’t change. The alarm stops just after the digital input is de-
activated. 

8.3

 

SERIOUS ALARM MODE (i1F = bAL) 

When  the  digital  input  is  activated,  the  unit  will  wait  for  did  delay  before  signalling  the  “CA”  alarm 
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated. 

8.4

 

PRESSURE SWITCH (i1F = PAL) 

If  during  the  interval  time  set  by  did  parameter  the  pressure  switch  reaches  the  nPS  number  of 
activation, the “CA” pressure alarm message will be displayed and the compressor and the regulation 
will be stopped. When the digital input is ON the compressor is always OFF. 
If  the  nPS  activation  in  the  did  time  is  reached,  switch  off and on the instrument to restart 
normal regulation. 

8.5

 

START DEFROST (i1F = dFr) 

A defrost will start if there are the right conditions. After the defrost is finished, the normal regulation 
will restart only if the digital input is disabled otherwise the instrument will wait for MdF safety time to 
expire. 

8.6

 

INVERSION OF THE KIND OF ACTION: HEATING-COOLING (i1F = Htr) 

This function allows to invert the regulation of the controller: from cooling to heating and viceversa. 

8.7

 

ENERGY SAVING (i1F = ES) 

The  Energy  Saving  function  allows  to  change  the  set  point  value  as  the  result  of  the  [SET+  HES] 
(parameter) sum. This function is enabled until the digital input is activated. 

8.8

 

DIGITAL INPUTS POLARITY  

The digital input polarity depends on the i1P parameter. 

 

i1P=CL: the input is activated by closing the contact.

 

i1P=OP: the input is activated by opening the contact

9. TTL SERIAL LINE – FOR MONITORING SYSTEMS

It is possible to connect the instrument to a ModBUS-RTU compatible monitoring system (e.g.  
X-WEB500/3000/300)  by  using  the  TTL  serial  line  available on the HOTKEY connector. An external 
adapter  has  to  be  used  to  connect  the  device  to  the  network  (e.g. a TTL/RS485 converter XJ485-
CX
).

10. INSTALLATION AND MOUNTING

Instrument XR30CX shall be mounted on vertical panel, in a 29x71 
mm hole, and fixed using the special bracket supplied.  
The temperature range allowed for correct operation is 0

60 °C. 

Avoid places subject to strong vibrations, corrosive gases, 
excessive dirt or humidity. The same recommendations apply to 
probes. Let air circulate by the cooling holes. 

11. ELECTRICAL CONNECTIONS

The  instrument  is  provided  with  screw  terminal  block  to  connect  cables  with  a  cross  section  up  to 
2.5mm

2

.  Before  connecting  cables  make  sure  the  power  supply  complies  with  the  instrument’s 

requirements.  Separate  the  probe  cables  from  the  power  supply  cables,  from  the  outputs  and  the 
power  connections.  Do  not  exceed  the  maximum  current  allowed  on  each  relay,  in  case  of heavier 
loads use a suitable external relay. 

11.1

 

PROBE CONNECTION 

The  probes  shall  be  mounted  with  the  bulb  upwards  to  prevent  damages  due  to  casual  liquid 
infiltration.  It  is  recommended  to  place  the  thermostat  probe  away  from  air  streams  to  correctly 
measure  the  average  room  temperature. Place the defrost termination probe among the evaporator 
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during 
defrost, to prevent premature defrost termination. 

12. HOW TO USE THE HOT KEY

12.1

 

HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1.

Program one controller with the front keypad.

2.

When  the  controller  is  ON,  insert  the  “HOT-KEY”  and  push  UP  button;  the  “uPL  message 
appears followed a by a flashing “End” label.

3.

Push SET button and the “End” will stop flashing.

4.

Turn OFF the instrument, remove the “HOT-KEY” and then turn it ON again.

NOTE: the “Err” message appears in case of a failed programming operation. In this case push again 
button if you want to restart the upload again or remove the “HOT-KEY” to abort the operation. 

12.2

 

HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD) 

1.

Turn OFF the instrument.

2.

Insert  a  pre-programmed  “Hot  Key”  into  the 5-PIN receptacle and then turn the Controller
ON. 

3.

The  parameter  list  of  the  “Hot  Key”  will  be  automatically  downloaded  into  the  Controller
memory. The “doL” message will blink followed a by a flashing “End” label. 

4.

After 10 seconds the instrument will restart working with the new parameters.

5.

Remove the “HOT-KEY”.

NOTE: the message “Err” is displayed for failed programming. In this case turn the unit off and then 
on if you want to restart the download again or remove the “HOT-KEY” to abort the operation. 

13. ALARM SIGNALS

Message 

Cause 

Outputs 

“P1” 

Room probe  failure 

Compressor output acc. to par. Con and CoF

“HA” 

Maximum temperature alarm 

Outputs unchanged. 

“LA” 

Minimum temperature alarm 

Outputs unchanged. 

“dA” 

Door open 

Compressor restart according to rrd

“EA” 

External alarm 

Output unchanged. 

“CA” 

Serious external alarm (i1F=bAL)  All outputs OFF. 

“CA” 

Pressure switch alarm (i1F=PAL)  All outputs OFF 

13.1

 

ALARM RECOVERY  

Probe  alarm  “P1”  starts  some  seconds  after  the  fault  in  the  related  probe;  they  automatically  stop 
some  seconds  after  the  probe  restarts  normal  operation.  Check  connections  before  replacing  the 
probe.  
Temperature alarms “HA” and “LA” automatically stop as soon as the temperature returns to normal 
values. 
Alarms “EA” and “CA (with i1F=bAL) recover as soon as the digital input is disabled. 
Alarm “CA” (with i1F=PAL) recovers only by switching off and on the instrument. 

13.2

 

OTHER MESSAGES 

Pon  Keyboard unlocked. 
PoF  Keyboard locked 
noP  In programming mode: none parameter is present in Pr1 

On the display or in dP2, dP3, dP4: the selected probe is nor enabled 

noA  No alarm recorded. 

14. TECHNICAL DATA

Housing: self extinguishing ABS. 
Case: XR30CX 
frontal 32x74mm; depth 60mm. 
Mounting: XR30CX panel mounting in a 71x29mm panel cut-out. 
Protection: IP20. Frontal protection: XR30CX IP65. 
Connections: Screw terminal block 

 2.5 mm

2

 wiring. 

Model 7020346 and 7020345: fast-on tabs 6,3mm for loads and power supply; Disconnect able 
screw terminal blocks for probe, digital input and  

Power  supply:   according  to  the  model:  100Vac 

10%,  50/60Hz;  or  230Vac 

10%,  50/60Hz,  or 

120Vac 

10%, 50/60Hz, or 

Power absorption: 3VA max. 
Display:
 3 digits red LEDs, 14.2 mm high. 
Digital input:  free voltage contact. 
Analogue Input: a PT1000 or PTC probe, set via parameter. 
Relay outputs:  

Compressor: 20(8)A, 250Vac. 

  

Alarm: SPDT 8(3)A, 250Vac. 

Connectors for external backup battery (only for battery-backup model).

 

Data storing: on the non-volatile memory (EEPROM). 
Kind of action: 1B. Pollution degree: 2. Software class: A. 
Rated impulsive voltage: 2500V. Overvoltage Category: II. 
Operating temperature: 
0÷60°C. 
Storage temperature: -30÷85 °C.  
Relative humidity: 20

85% (no condensing). 

Measuring and regulation range:  

Pt1000 probe: -100÷100°C (-148÷212°F). 

Summary of Contents for Dixel XR30CX Series

Page 1: ... point plus differential the compressor is started and then turned off when the temperature reaches the set point value again Time Temper Compr SET ON In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters Con and CoF 3 2 DEFROST Defrost is performed through a simple stop of the compressor Parameter idF controls the interval between defrost cycle...

Page 2: ...in minimum interval between the compressor stop and the following restart rtr Percentage of the second and first probe for regulation 0 100 100 P1 0 P2 it allows to set the regulation according to the percentage of the first and second probe as for the following formula rtr P1 P2 100 P2 CCt Compressor ON time during continuous cycle 0 0 24h00min res 10min allows to set the length of the continuous...

Page 3: ...The temperature range allowed for correct operation is 0 60 C Avoid places subject to strong vibrations corrosive gases excessive dirt or humidity The same recommendations apply to probes Let air circulate by the cooling holes 11 ELECTRICAL CONNECTIONS The instrument is provided with screw terminal block to connect cables with a cross section up to 2 5mm2 Before connecting cables make sure the pow...

Page 4: ...res 10s 0 0 0 0 Pr2 idF Interval between defrost cycles 1 120 hours 0 0 Pr1 MdF Maximum length for defrost 0 255 min 0 0 Pr1 dFd Displaying during defrost rt it SEt DEF rt rt Pr2 dAd MAX display delay after defrost 0 255 min 0 0 Pr2 ALC Temperature alarms configuration rE related to set Ab absolute rE rE Pr2 ALU MAXIMUM temperature alarm Set 110 C Set 230 F 15 C 59 F 15 C 59 F Pr1 ALL Minimum temp...

Reviews: