background image

 

1598013141 XM664K GB CLABO rev1.2 2012.01.26 

                         

XM664K  

          

1/6 

 

XM664K  

1.

 

GENERAL WARNING____________________________________________________________ 1

 

2.

 

GENERAL DESCRIPTION ________________________________________________________ 1

 

3.

 

CONTROLLING LOADS__________________________________________________________ 1

 

4.

 

FRONT PANEL COMMANDS _____________________________________________________ 1

 

5.

 

SECTIONS MENU ______________________________________________________________ 2

 

6.

 

HOW TO CHANGE THE ACTIVE MAP ______________________________________________ 2

 

7.

 

INSTALLATION AND ASSEMBLY __________________________________________________ 2

 

8.

 

ELECTRICAL CONNECTIONS ____________________________________________________ 2

 

9.

 

TTL SERIAL LINE _______________________________________________________________ 2

 

10.

 

HOW TO USE THE HOT KEY _____________________________________________________ 2

 

11.

 

ALARMS ______________________________________________________________________ 3

 

12.

 

TECHNICAL DATA ______________________________________________________________ 3

 

13.

 

CONNECTIONS ________________________________________________________________ 3

 

14.

 

DEFAULT SETTING VALUES _____________________________________________________ 4

 

 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and should be kept near the instrument for easy and quick reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It cannot be used 
as a safety device. 

 

Check the application limits before proceeding. 

1.2

 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do  not  expose  to  water  or  moisture:  use  the  controller  only  within  the  operating  limits  avoiding  sudden 
temperature changes with high atmospheric humidity to prevent  formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In  case  of  failure  or  faulty  operation  send  the  instrument  back  to  the  distributor  (see  address)  with  a 
detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure  that  the  wires  for  probes,  loads  and  the  power  supply  are  separated  and  far  enough  from  each 
other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our  mod. FT1) in parallel with 
inductive loads could be useful. 

2.

 

 GENERAL DESCRIPTION 

The  XM664K  is  microprocessor  controller  suitable  for  medium  and  low  temperature  multiplexed  cabinet 
applications  composed of as  many as  8 sections. This makes it  possible to create a LAN  (local  area  network) 
made  up  of  the  instruments  which,  depending  on  the  programming,  can  operate  as  single  controllers  or 
managing the controls which  arrive  from  one or more sections. The XM664K is  equipped with 6 relay outputs 
which control the compressor, the  defrost 1 and 2 (which can be either  electric  or with hot gas, the evaporator 
fans, the lights and an ON/OFF output. It is supplied with three NTC probe inputs, one for thermostating, one for 
temperature control at the  end  of defrost on evaporator 1 and one for end of defrost 2 control. There  are  also 
two digital inputs which can be configured by parameters.  
The  two  LAN  outputs  provide  an  easy  connection  between  the  various  controllers  while  the  TTL  connector 
programs the complete parameter list by means of a programming key called “Hot Key”. 

3.

 

CONTROLLING LOADS 

3.1

 

COMPRESSOR 

The  regulation  is  performed  according  to  the  temperature  measured  by  the  thermostat  probe  with  a  positive 
differential from the set point: if the temperature increases and reaches set point plus differential the compressor 
is started and then turned off when the temperature reaches the set point value again. 
In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters Con 
and CoF

3.2

 

DEFROST 

There  are  three  types  of  defrost  available  that  can  be  selected  with  the  parameter  tdF:  defrost  with  electric 
heater  (tdF=EL),  with  hot  gas  (tdF=in)  or  disabled  (tdF=oFF).  When  defrost  is  over,  the  dripping  time  starts, 
which is managed by the parameter Fdt
Management of two defrosts is configured by parameters dModd1dEM and dEn. In particular: 
 
dMo
  Defrost 1-2 management mode: (ind; 2-1; dEL) if dMo=ind defrost 1 e 2 managements are independent; 

if dMo=2-1 activation of defrost 2 entails activation of defrost 1; if dMo=dEL activation of defrost 2 entails 
activation of defrost 1 with delay set by parameter dd1; 

dd1  Defrost 1 activation delay compared to defrost 2: (0 to 255 min) as previously mentioned, it describes 

the activation delay of defrost 1 after activation of defrost 2 if dMo=dEL; 

dEM  Defrost synchronisation in LAN: (ind; Sin) if dEM=ind the end of defrosts is independent. If dEM=Sin

the end of defrosts is synchronised; 

dEn  Synchronisation  of  local  defrost  end  (def1  and  def2):  (ind;  Sin)  if  dEM=ind  the  end  of  defrosts  is 

independent. If dEM=Sin, the end of defrosts is synchronised. 

 
The start of  a defrost cycle can  be controlled locally  (manual activation  by the keyboard, digital input  or at  the 
end of the time interval). Otherwise the command can arrive from any controller inserted in the LAN. In this last 
case,  the  controller  will  start  a  defrost  cycle  and  will  bring  it  to  the  end  following  the  indications  present  in  its 
programming parameters. But at the end of the cycle, it will wait for all the controllers present in the LAN to finish 
before returning to normal temperature regulation. 

3.3

 

CONTROL OF EVAPORATOR FANS 

The fan control mode is selected by means of the FnC parameter: 

 

FnC = C_n: fans will switch ON and OFF with the compressor and not run during defrost; 

 

FnC = o_n: fans will run even if the compressor is off, and not run during defrost. 
 

After defrost, there is a timed fan delay allowing for drip time, set by means of the Fnd parameter: 

 

FnC = C_Y: fans will switch ON and OFF with the compressor and run during defrost; 

 

FnC = o_Y: fans will run continuously also during defrost. 

 

An additional parameter FSt provides the setting of temperature, detected by the evaporator probe, above which 
the fans are always OFF. This is used to make sure circulation of air only if his temperature is lower than set in 
FSt.  

4.

 

FRONT PANEL COMMANDS 

 

To display and modify target set point; in programming mode it selects a parameter or confirm 
an operation. 
By holding it pressed for 3 sec when max or min temperature is displayed it will be erased. 
To see the max stored temperature value.  
In programming mode it browses the parameter codes or increases the displayed value. 
By holding it pressed for 3s it gives access to the “Section” menu. 

To see the min stored temperature value.  
In programming mode it browses the parameter codes or decreases the displayed value. 

By holding it pressed for 3 sec the defrost is started. 

Switch ON and OFF the room light. 

Keep it pressed more than 3 sec to switch ON and OFF the instrument. 

 
KEY COMBINATIONS 
 

 

+

 

 

To enter the programming mode. 

  

+

 

 

To exit the programming mode. 

4.1

 

USE OF LEDS 

Each LED function is described in the following table. 

LED 

MODE 

Function 

ON 

Compressor enabled 

 

Flashing 

Programming phase  (flashing with the LED 

Anti-short cycle delay enabled 

ON 

Fans enabled 

 

Flashing 

Programming phase  (flashing with the LED 

ON 

Defrost enabled 

 

Flashing 

Defrost or drip time enabled 

ON 

The controller is working in “ALL” mode 

 

Flashing 

The controller is working in remote virtual display mode 

  

ON 

An alarm is active

  

4.2

 

HOW TO SEE AND MODIFY THE SET POINT 

 

1.

 

Push for about 3 sec the SET key: the display will show the Set point value; 

2. 

The measurement unit starts blinking; 

3. 

To change the SET value push the 

or 

n

 arrows within 10 sec. 

4. 

To store the new set point value push the SET key again or wait 10 sec.

 

4.3

 

HOW TO START A MANUAL DEFROST 

 

 
1.

 

Push the DEF key for more than 3 seconds and a manual defrost will start. 

2.

 

Use the UP and DOWN keys to select the dEF1 or the dEF2. 

4.4

 

TO ENTER IN PARAMETERS LIST “PR1” 

To enter the parameter list “Pr1” (user accessible parameters) operate as follows: 

 

 

 
1.  Enter the Programming mode by pressing the SET+DOWN key for few seconds 

(

 and 

 

start blinking). 

2.  The instrument will show the first parameter present in “Pr1”. 

 

4.5

 

TO ENTER IN PARAMETERS LIST “PR2” 

To access parameters in “Pr2”: 
1.

 

Enter the “Pr1” level. 

2.

 

Select “Pr2” parameter and press the SET key.  

3.

 

The “PAS” flashing message will be displayed shortly, followed by “0 - -” with a flashing zero. 

4.

 

Use 

o

or 

n

  to  input  the  security  code  in  the  flashing  digit;  confirm  the  figure  by  pressing  SET.  The 

security code is “321“. 

5.

 

If the security code is correct the access to “Pr2” is enabled by pressing SET on the last digit. 

 
Another possibility is the following: after switching ON the instrument the user can push SET+DOWN keys within 
30 sec. 
 
NOTE
: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing SET+DOWN. When a 
parameter is present in “Pr1” LED 

 is on. 

4.6

 

HOW TO CHANGE THE PARAMETER VALUE 

1.

 

Enter the Programming mode. 

2.

 

Select the required parameter with 

or 

n

3.

 

Press the SET key to display its value (measurement unit starts blinking). 

Summary of Contents for dixell XM664K

Page 1: ...ls activation of defrost 1 if dMo dEL activation of defrost 2 entails activation of defrost 1 with delay set by parameter dd1 dd1 Defrost 1 activation delay compared to defrost 2 0 to 255 min as previously mentioned it describes the activation delay of defrost 1 after activation of defrost 2 if dMo dEL dEM Defrost synchronisation in LAN ind Sin if dEM ind the end of defrosts is independent If dEM ...

Page 2: ...allowed temperature range for correct functioning is between 0 and 60 C Avoid places subject to heavy vibrations corrosive gas excessive filth or humidity The same instructions hold for the probes as well Leave the area near the cooling louvers ventilated 7 1 CUT OUT The T640 keyboard shall be mounted on vertical panel in a 150x31 mm hole and fixed using two screws 3 x 2mm To obtain an IP65 protec...

Page 3: ...he signal on the display remains until the alarm condition has ceased It is possible to inhibit the alarm relay deactivation by setting the parameter tbA n In this way the alarm relay remains active as long as the alarm condition lasts The signal buzzer is found in the keyboard T640 11 4 EE ALARM The instruments of the Dixell series are equipped with an internal control which checks the integrity ...

Page 4: ...d temperature 55 0 C 50 0 C dtS 8 Probe dPb defrost 2 end temperature 55 0 C 50 0 C idF 8 Defrost 1 interval if EdF in intervals If idF 0 defrost is forced manually only from serial from outside contact from coordinated defrost LAN 0 to 120 hours IdS 0 Defrost 2 interval if EdF in intervals If idS 0 defrost is forced manually only from serial from outside contact from coordinated defrost LAN 0 to ...

Page 5: ...iG OnF ES ATA CbL d2d 0 Alarm delay for configurable digital input DI2 0 to 255 min nPS 10 Number of interventions at status before block 0 to 15 OdC FAn Loads control with door open Fan fans Cpr compressor F C fans and compressor Valid if one of the parameters i1 2F dor no FAn CPr F C rrd 30 Forcing of fan compressor restart after door opening Valid if one of the parameters i1 2F dor 0 to 255 min...

Page 6: ...frost LAN 0 to 120 hours IdS 0 Defrost 2 interval if EdF in intervals If idS 0 defrost is forced manually only from serial from outside contact from coordinated defrost LAN 0 to 120 hours MdF 30 Maximum duration forcing defrost 1 end if it is not cut off before the dTE temperature 0 to 255 min MdS 0 Maximum duration forcing defrost 2 end if it is not cut off before the dTS temperature 0 to 255 min...

Reviews: