background image

 

xxxxxxxxxxxxxxxxxx XR44CH ISA GB r1.6 21.11.2016 

XR44CH 

1/5 

Digital controller with defrost and fan management

 

XR44CH  

1.

 

GENERAL WARNING __________________________________________________________ 1

 

2.

 

GENERAL DESCRIPTION ______________________________________________________ 1

 

3.

 

CONTROLLING LOADS ________________________________________________________ 1

 

4.

 

FRONT PANEL COMMANDS ____________________________________________________ 2

 

5.

 

MAX & MIN TEMPERATURE MEMORIZATION _____________________________________ 2

 

6.

 

DUAL TEMPERATURE FUNCTION _______________________________________________ 2

 

7.

 

MAIN FUNCTIONS ____________________________________________________________ 2

 

8.

 

PARAMETERS _______________________________________________________________ 3

 

9.

 

DIGITAL INPUTS  _____________________________________________________________ 4

 

10.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS  _________________________________ 4

 

11.

 

INSTALLATION AND MOUNTING ________________________________________________ 4

 

12.

 

ELECTRICAL CONNECTIONS___________________________________________________ 4

 

13.

 

USE THE HOT KEY ___________________________________________________________ 4

 

14.

 

ALARM SIGNALS _____________________________________________________________ 4

 

15.

 

TECHNICAL DATA ____________________________________________________________ 5

 

16.

 

CONNECTIONS ______________________________________________________________ 5

 

17.

 

DEFAULT SETTING VALUES ___________________________________________________ 5

 

 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and should be kept near the instrument for easy and quick 
reference. 

 

The  instrument  shall  not  be  used  for  purposes  different  from  those  described  hereunder.  It 
cannot be used as a safety device. 

 

Check the application limits before proceeding. 

 

Dixell  Srl  reserves  the  right  to  change  the  composition  of  its  products,  even  without  notice, 
ensuring the same and unchanged functionality. 

1.2

 

SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not expose to water or moisture: use the controller only within the operating limits avoiding 
sudden  temperature  changes  with  high  atmospheric  humidity  to  prevent    formation  of 
condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.” 
(see address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from 
each other, without crossing or intertwining. 

 

In  case  of  applications  in  industrial  environments,  the  use  of  mains  filters  (our  mod.  FT1)  in 
parallel with inductive loads could be useful. 

2.

 

GENERAL DESCRIPTION 

Model XR44CH, format 32 x 74 mm, is microprocessor based controller, suitable for applications on 
low temperature refrigerating units. It has four relay outputs to control compressor 1 and 2, defrost 1 
and 2, which can be either electrical or reverse cycle (hot gas). It is also provided with up to three NTC 
or PTC probe inputs, the first one for temperature control, the second and third one, to be located onto 
the evaporator, to control the defrost termination temperature on the evaporator 1 and 2.   
It allows to program the controller by means the HOT KEY programming keyboard. 

3.

 

CONTROLLING LOADS 

3.1

 

COMPRESSOR 

The regulation is performed according to 
the  temperature  measured  by  the 
thermostat  probe  with  a  positive 
differential  from  the  set  point:  if  the 
temperature  increases  and  reaches  set 
point  plus  differential  the  compressor  is 
started  and  then  turned  off  when  the 
temperature reaches the set point value 
again. 

Time

Temper.

Compr.

SET

ON

 

In  case  of  fault  in  the  thermostat  probe  the  start  and  stop  of  the  compressor  are  timed  through 
parameters Con and CoF

3.2

 

SECOND COMPRESSOR MANAGEMENT  

The relay of the second compressor is activated according to the settings of the following parameters.  
The 2CC (SEq; HAF), defines how the second compressor is activated. 

3.2.1  Sequence activation 

With  2CC = SEq the second compressor is activated after a delay counter AC1 ( parameter ). Both 
compressor are switched off when the temperature set point is reached. 

 

3.2.2  Dual band activation 

 

With 2CC = HAF the regulation is 
changed as follows. 

 

a. 

Activation of 

compressors

 

The activation threshold of the first 
compressor is (where T is 
temperature): 

T> SET + Hy 

The activation threshold of the 
second compressor is (where T is 
temperature) : 

T>SET+Hy+Hy2 

 

 
The second compressor is activated in any case only if the AC1 timer has already expired, where AC1 
is the  delay between the activation of two compressors 

 

b. 

Deactivation of compressors

 

The second compressor is switched off when the temperature drops below  

T <SET + Hy 

The first compressor is turned off when: 

T<SET 

 

ROTATION 

Once both the compressors are switched off, the activation order of the 2 compressors is reversed in 
order to balance the working hours. 
A cycle is considered as completed even if only one compressor is switched on and off: that is, when 
the temperature exceeds the first activation threshold, (SET + HY) and then latter returns below the 
value of the set point (SET). 
 

STALL PREVENTION 

The Mon parameter defines the maximum time a single compressor can run continuously. When the 
Mon timer expires the other compressor is activated, to increase capacity and therefore to reduce the 
temperature, both the compressors are switched off at the same time when the SET point is reached 
 

3.3

 

DEFROST  

3.3.1  THE PRE-DEFROST CYCLE 

A pre-defrost cycle, to cool deeper the goods before the defrost can be managed. 
If it is enabled the temperature set point (SET) becomes:  SET+Hd1  for Ht1 mins, then the defrost 
starts.  
The pre-defrost cycle cannot be performed if the defrost is started manually by keyboard. 

3.3.2  THE POST- DEFROST CYCLE 

After defrost and dripping time, a post defrost cycle can be managed. 
If it is enabled the temperature set point (SET) becomes:  SET+Hd2  for Ht2 mins, then the standard 
regulation starts..  
If enabled, the post defrost cycle si always done. 

3.3.3  DEFROST MODES 

Two  defrost  modes  are  available  through  the  tdF  parameter:  defrost  through  electrical  heater 
(tdF=EL) and hot gas defrost (tdF=in). In this case by the parameter StC (0÷15min) the compressor 
can be stopped before the defrost. The compressor is stopped after the pre-defrost cycle. 
 
Other parameters are used to control the interval between defrost cycles (idF), its maximum length 
(MdF) and two defrost modes: timed or controlled by the evaporator’s probe (P2P).  
At the end of defrost dripping time is started, its length is set in the Fdt parameter. With Fdt=0 the 
dripping time is disabled. 
 

3.3.4  SECOND  EVAPORATOR  CONTROL  AND  EVAPORATORS  CYCLING 
WITH HOT GAS DEFROST 

With      tdF  =  ALt  a  hot  gas  defrost  with  double  evaporator  is  managed.  The  2  evaporators  are 
alternated according to the following indications:  

a.

 

After IdF the COMP+DEF1 are activated 

b.

 

After IdF the COMP+DEF2 are activated  

c.

 

After IdF the COMP+DEF1 are activated 

 

3.4

 

CONTROL OF EVAPORATOR FANS 

The fan control mode is selected by means of the FnC parameter: 
FnC=C_n, fans will switch ON and OFF with the compressor and not run during defrost. 
FnC=o_n, fans will run even if the compressor is off, and not run during defrost. 
 
After defrost, there is a timed fan delay allowing for drip time, set by means of the Fnd parameter. 
FnC=C_Y, fans will switch ON and OFF with the compressor and run during defrost. 
FnC=o_Y, fans will run continuously also during defrost. 

 

An additional parameter FSt provides the setting of temperature, detected by the evaporator probe, 
above  which  the  fans  are  always  OFF.  This  is  used  to  make  sure  circulation  of  air  only  if  his 
temperature is lower than set in FSt

3.4.1  Forced activation of fans 

This  function  managed  by  the  FCt  parameter  is  designed  to  avoid  short  cycles  of  fans,  that  could 
happen when the controller is switched on or after a defrost, when the room air warms the evaporator. 
How it works: if the temperature difference between evaporator probe and room probe is higher than 
the FCt parameter value, fans will be switched on. With FCt=0 the function is disabled. 

3.4.2  Cyclical activation of the fans with compressor off. 

When FnC=C-n or C-Y (fans working in parallel with the compressor), by means of the Fon and FoF 
parameters the fans can carry out on and off cycles even if the compressor is switched off. When the 
compressor is stopped the fans go on working for the Fon time. With Fon=0 the fans remain always 
off, also when the compressor is off.  

Summary of Contents for Dixell XR44CH

Page 1: ...econd compressor is activated after a delay counter AC1 parameter Both compressor are switched off when the temperature set point is reached 3 2 2 Dual band activation With 2CC HAF the regulation is changed as follows a Activation of compressors The activation threshold of the first compressor is where T is temperature T SET Hy The activation threshold of the second compressor is where T is temper...

Page 2: ... Press and release the UP key 2 The Hi message will be displayed followed by the maximum temperature recorded 3 By pressing the UP key again or by waiting 5 sec the normal display will be restored 5 3 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 1 Keep the SET key pressed more than 3 sec while the max or min temperature is displayed rSt message will be displayed 2 To confirm the operation the...

Page 3: ...nly for model with this option enabled P4 Fourth probe SET set point dtr percentage of visualization rEd X REP display optional P1 P2 P3 P4 SET dtr it selects which probe is displayed by X REP P1 Thermostat probe P2 Evaporator probe P3 Third probe only for model with this option enabled P4 Fourth probe SET set point dtr percentage of visualization dLy Display delay 0 20 0m risul 10s when the tempe...

Page 4: ...d the display shows the message dA and the regulation restarts is rtr YES The alarm stops as soon as the external digital input is disabled again With the door open the high and low temperature alarms are disabled 9 5 START DEFROST I1F DEF It starts a defrost if there are the right conditions After the defrost is finished the normal regulation will restart only if the digital input is disabled oth...

Page 5: ... Defrost type EL 0 in 1 ALt 2 in Pr2 dFP Probe for first defrost nP 0 P1 1 P2 2 P3 3 P4 4 P2 Pr2 dSP Probe for second defrost nP 0 P1 1 P2 2 P3 3 P4 4 nP Pr2 dtE First defrost termination temperature 55 0 C 50 0 C 67 F 122 F 8 0 Pr2 dtS Second defrost termination temperature 55 0 C 50 0 C 67 F 122 F 8 0 Pr2 idF Interval between defrost cycles 0 120 hours 6 Pr2 MdF Maximum length for first defrost ...

Reviews: