XW60K 110918 V14.7 EMERSON092718 V14.7 

XW60K 

3/12 

 

KEYBOARD ICONS

 

 

To display and modify target set point; in programming mode it selects a 

parameter or confirm an operation. By holding it pressed for 3 sec when 
max or min temperature is displayed it will be erased. 

 

(UP

) To see the max stored temperature; in programming mode it browses 

the parameter codes or increases the displayed value.  
By holding it pressed for 3s the fast freezing cycle is started. 

 

 

(

DOWN

)  To  see  the  min  stored  temperature;  in  programming  mode  it 

browses the parameter codes or decreases the displayed value. 

 

 

 

(

DEF

) By holding it pressed for 3 sec the defrost cycle is initiated. 

 

 

 

(

LIG

) Switch ON and OFF the walk-in light. 

 

 

(

ES

“Energy  Pig”  Press  to  enter  into  Energy  Saving  Mode  (HES 

parameter) 

KEY COMBINATIONS 

  

 

 

To lock and unlock the keyboard.

 

  

 

 

To enter the programming mode. 

 

  

 

 

To exit the programming mode.

 

5.1

 

USE OF LEDS 

Each LED function is described in the following table. 

LED 

MODE 

Function 

 

ON 

The solenoid is running 

FLASHING 

- Programming Phase (flashing with LED 

- Anti-short cycle delay enabled 

 

ON 

The fan is running 

FLASHING 

Programming Phase (flashing with LED 

 

ON 

The defrost is enabled 

FLASHING 

Drip time in progress 

 

ON 

The Fast Freezing cycle is enabled 

 

ON 

- ALARM signal 

In “Pr2” indicates that the parameter is also present in “Pr1”

 

 

ON 

Continuous cycle is running 

 

ON 

Energy saving enabled 

 

ON 

Light on 

 

ON 

Auxiliary relay on  

°C/°F 

ON 

Measurement unit  

6

 

AUTOMATIC KEYBOARD LOCK (ONLY FOR T620T) 

To avoid accidental modifications of the controller settings, 

the T620T keyboard will be locked automatically if no key will be touched for 60 seconds. 

The T620T will show “

LoC

” flashing for few seconds when it’s 

locking. The 

light key

 is operating even if the keyboard is locked. 

6.1

 

TO UNLOCK THE T620T 

1.

 

Touch any key. 

2.

 

The keys will be lighted. 

3.

 

Keep a key pushed for few seconds till the “

on

” message is displayed.

 

7

 

CONTROLLER INTERFACE 

SET THE CURRENT TIME AND DAY (ONLY WITH OPTIONAL RTC) 

When the instrument is switched on, it’s necessary t

o program the time and day. 

1.

 

Enter the Pr1 programming menu, by pushing the 

SET+ DOWN

 

keys for 3 sec. 

2.

 

The 

rtC

 parameter is displayed. Push the 

SET

 key to enter the real time clock menu. 

3.

 

The 

Hur

 (hour) parameter is displayed. 

4.

 

Push the 

SET

 and set current hour by the 

UP

 and 

DOWN

 keys, then push 

SET

 to confirm the value. 

5.

 

Repeat the same operations with 

Min

 (minutes), 

dAy

 (day), 

dYM

 (day of month), 

Mon 

(month) and 

YAr 

(year) parameters. 

To exit: 

Push both 

SET+UP

 keys or wait for 15 sec without pushing any keys. 

7.1

 

HOW TO SEE THE MIN TEMPERATURE 

1.  

Press and release the 

DOWN

 key. 

2.  

The “Lo” message will be displayed followed by the minimum temperature recorded.

 

3. 

By pressing the 

DOWN

 key or waiting for 5 sec the normal display will be restored. 

Summary of Contents for dixell XW60K

Page 1: ...ogress a continuous chill mode can be activated by holding the oUP key pressed for about 3 sec The solenoid operates to maintain the CCS set point for the time set through the CCt parameter The cycle can be terminated before the end of the set time by pressing theo UP key for 3 sec 3 3 DEFROST ON DEMAND OR RTC OPTIONAL MUST BE ORDERED Hot Gas or Electric Defrost can be managed through the tdF para...

Page 2: ...ion for the auxiliary relay Ht heating CL cooling SAA 40 230 F Set point for auxiliary relay SHy 0 25 F Differential for auxiliary output With ACH CL aux relay cut in is SAA SHy cut out SAA With ACH Ht aux relay cut in is SAA SHy cut out SAA ArP nP P1 P2 P3 P4 Probe for auxiliary relay Sdd n Y Auxiliary output working during defrost 4 5 ALARM RELAY OA3 ALR OPTIONAL By setting oA3 ALr the relay wil...

Page 3: ...arameter is also present in Pr1 ON Continuous cycle is running ON Energy saving enabled ON Light on ON Auxiliary relay on C F ON Measurement unit 6 AUTOMATIC KEYBOARD LOCK ONLY FOR T620T To avoid accidental modifications of the controller settings the T620T keyboard will be locked automatically if no key will be touched for 60 seconds The T620T will show LoC flashing for few seconds when it s lock...

Page 4: ...ming mode 2 Select the required parameter with UP or DOWN 3 Press the SET key to display its value and LED starts blinking 4 Use UP or DOWN to change its value 5 Press SET to store the new value and move to the following parameter To exit Press SET UP or wait for 15 sec without pressing any key NOTE the new programming is stored even when the procedure is exited by waiting the time out 7 8 HOW TO ...

Page 5: ...d defrosts to start together dFd Temperature displayed during defrost rt it SEt dEF rt real temperature it temperature at defrost start SEt set point dEF dEF label dAd MAX display delay after defrost 0 to 255min sets the maximum time between the end of defrost and the restarting of the real room temperature display Fdt Drip time 0 to 120min is the interval time between reaching defrost termination...

Page 6: ...ls 8 9 D I i2P Second digital input polarity oP CL oP the digital input is activated by opening the contact CL the digital input is activated by closing the contact i2F Second digital input configuration EAL bAL PAL dor dEF ES AUS Htr FAn HdF onF Sbt EAL external alarm EA message is displayed bAL serious alarm CA message is displayed PAL pressure switch alarm CA message is displayed dor door switc...

Page 7: ...th oA3 AUS and i1F AUX it switches the fourth relay 22 23 10 6 START DEFROST I1F DFR OPTIONAL It starts a defrost if there are the right conditions After the defrost is finished the normal regulation will restart only if the digital input is disabled otherwise the instrument will wait until the MdF safety time is expired 10 7 KIND OF ACTION HEATING OR COOLING I1F HTR OPTIONAL This function allows ...

Page 8: ...ments are provided with an internal check for the data integrity The EE alarm flashes when a failure in the memory data occurs In such cases the alarm output is enabled 13 3 ALARM RECOVERY Probe alarms P1 probe1 faulty P2 P3 and P4 they automatically stop 10 sec after the probe restarts normal operation Check connections before replacing the probe Temperature alarms HA LA HA2 and LA2 automatically...

Page 9: ...n a 71x29mm panel cut out Frontal protection IP65 with frontal gasket Connections Screw terminal block 2 5 mm2 Power supply from XW60K power module Display 3 digits red LED 14 2 mm high Alarm Output buzzer Power module XW60K Case 8 DN 140X176X148 Connections Screw terminal block 2 5 mm2 heat resistant wiring and 6 3mm Faston Power supply 230Vac or 110Vac 10 or 24Vac Power absorption 6VA max Inputs...

Page 10: ...30 Pr1 Start defrost delay 0 to 99 min 0 Pr2 Displaying during defrost rt it SEt dEF dEG DEF Pr2 MAX display delay after defrost 0 to 255 min 30 Pr2 Draining time 0 to 60 min 1 Pr2 First defrost after start up n Y n Pr2 Defrost delay after fast freezing 0 0 to 23h50min res 10 min 0 00 Pr2 FANS Fans operating mode C n C y O n O y O_n Pr1 Fans delay after defrost 0 to 255 min 10 Pr1 Differential of ...

Page 11: ... dEF ES Htr FAN ONF AUS LHT dor Pr1 Digital input alarm delay 0 to 255 min 0 Pr1 Number of activation of pressure switch 0 to 15 15 Pr2 Compress and fan status when open door no FAn CPr F_C F C Pr2 Regulation restart with door open alarm n Y yes Pr2 Light off during energy saving status n Y no Pr2 Differential for Energy Saving 30 to 30 C 54 to 54 F 0 Pr2 Current hour read only after first set up ...

Page 12: ...r1 Evaporator probe display read only Pr1 Third probe display read only Pr1 Fourth probe display read only Pr1 Current set point read only Pr1 Software release read only Pr2 Map code read only Pr2 18 CERTIFICATIONS 19 FOR WARRANTY AND OTHER INFORMATION 1065 Big Shanty Road Suite 100 Kennesaw GA 30144 www emerson com Support Phone 770 425 2724 select option 2 SolutionsTechSup Emerson com Sales solu...