background image

 

XW60K 110918 V14.7 EMERSON092718 V14.7 

XW60K 

4/12 

 

7.2

 

HOW TO SEE THE MAX TEMPERATURE 

1.  

Press and release the 

UP

 key. 

2.  

The “Hi” message will be displayed followed by the maximum temperature recorded.

 

3. 

By pressing the 

UP

 key or waiting for 5 sec the normal display will be restored. 

7.3

 

HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 

To reset the stored temperature, when max or min temperature is displayed: 

1.

 

Press 

SET

 

key until “rST” label starts blinking.

 

Note: after the first start-up remember to RESET the temperature stored.

 

7.4

 

HOW TO SEE AND MODIFY THE SET POINT 

1.

 

Push and immediately release the 

SET 

key: the display will show the Set point value; 

2.

 

To change the 

SEt

 value, push the 

UP

 or 

DOWN

 arrows within 10 sec. 

3.

 

To memorise the new set point value push the 

SET

 key again or wait for 10 sec. 

7.5

 

TO START A MANUAL DEFROST  

 

1.

 

Push the 

DEF 

key for more than 2 sec and a manual defrost will start. 

 

7.6

 

TO ENTER IN PARAMETE

RS LIST “PR1” 

 

To enter the parameter list “Pr1” (user accessible parameters) operate as follows:

 

+

 

1.

 

Enter the Programming mode by pressing the Set and DOWN key 
for few seconds (

 and 

 start blinking). 

2.

 

The instrument will show the first parameter present in “Pr1”

 

7.7

 

THE HIDDEN MENU (PR2) 

In the hidden menu there are all the parameters of the instrument. 

7.7.1

 

ENTERING THE HIDDEN MENU 

1.

 

Enter the Programming mode by pressing the 

SET+DOWN

 

keys for 3 sec (the “

°C

” or “

°F

” LED will start blinking).

 

2.

 

Release the keys and then press again the 

SET+DOWN

 keys more than 7 se

c. The “

Pr2

” label will be displayed immediately, followed from the 

HY

 parameter.  

NOW THE HIDDEN MENU IS DISPLAYED

 

3.

 

Select the required parameter. 

4.

 

Press 

SET

 key to display its actual value 

5.

 

Use 

UP 

or 

DOWN 

keys to change its value. 

6.

 

Press 

SET

 to store the new value and move to the following parameter. 

To exit

: Press 

SET+UP 

or wait for 15 sec without pressing any key. 

NOTE1: 

if no parameter is present in the “

Pr1

” level, after the first 3 sec the “

noP

” message will be displayed. Keep 

SET+DOWN

 keys pushed till t

he “

Pr2

” message will be displayed. 

 

NOTE2

: the new set value will be stored even if the procedure is exited by waiting for the time-out to expire. 

7.7.2

 

HOW TO: MOVE A PARAMETER FROM THE HIDDEN MENU TO THE FIRST LEVEL AND VICEVERSA. 

Each parameter present in th

e HIDDEN MENU can be moved or put into “THE FIRST LEVEL” (user level) by pressing 

SET+DOWN

 keys. In HIDDEN MENU, if a parameter is present also in the First Level (Pr1), the decimal 

point will be lit. 

7.7.3

 

HOW TO CHANGE THE PARAMETER VALUE 

1.

 

Enter the Programming mode. 

2.

 

Select the required parameter with 

UP 

or 

DOWN

3.

 

Press the “

SET

” key to display its value (

 and 

 LED starts blinking).  

4.

 

Use 

UP 

or 

DOWN

 to change its value. 

5.

 

Press 

SET

 to store the new value and move to the following parameter. 

To exit

: Press 

SET+UP 

or wait for 15 sec without pressing any key. 

NOTE

: the new programming is stored even when the procedure is exited by waiting the time-out. 

7.8

 

HOW TO LOCK THE KEYBOARD (MANUALLY) 

7.9

 

ON/OFF FUNCTION (STAND BY) OPTIONAL INSTEAD OF ES MODE 

 

By pushing the 

ON/OFF

 

key, the instrument shows “

OFF

” for 5 sec. and the ON/OFF LED 

is switched ON. 
During the OFF status, all the relays are switched OFF and the regulations are stopped; if 
a monitoring system is connected, it does not record the instrument data and alarms. 

When the instrument is in stand by the keyboard displays “

OFF

 

N.B. During the OFF status the Light and AUX buttons are active. 

 

7.10

 

TO SEE THE PROBE VALUES 

1. 

Enter in “

Pr1

” level.

 

2.  Parame

ters “dP1”, “dP2”

“dP3” and “dP4” display the value of probes 1

(Room), 2(Def), 3(Pb3) 

and 4(Pb4).  

8

 

PARAMETER LIST 

rtC 

Real time clock menu (only for controller with RTC): 

to set the time, date and defrost start time.

 

REGULATION 

HY 

Differential:

 (0.1 to 25.5°C; 1 to 45°F) intervention differential for set point. Solenoid Cut IN is Set Point + differential (

HY

). Solenoid Cut OUT is when the temperature reaches the set point. 

LS 

Minimum set point:

 (-55°C to SET; -67°F to SET) sets the minimum value for the set point. 

US 

Maximum set point:

 (SET to 150°C; SET to 302°F) set the maximum value for set point. 

ot 

Thermostat probe calibration:

 (-12.0 to 12.0°C; -21 to 21°F) allows to adjust possible offset of the thermostat probe. 

P2P 

Second probe presence:

 (n; Y) 

n

 = not present, the defrost stops by time;  

Y

 = present, the defrost stops by temperature. P2 should be placed inside the evaporator. 

oE 

Second probe calibration:

 (-12.0 to 12.0°C; -21 to 21°F) allows to adjust possible offset of the evaporator probe. 

P3P 

Third probe presence (P3):

 (n; Y) 

n

 = not present, 

Y

 = present. P3 should be placed in the discharge air. 

o3 

Third probe calibration (P3):

 (-12.0 to 12.0°C; -21 to 21°F) allows to adjust possible offset of the third probe. 

P4P 

Fourth probe presence: 

(n; Y) n = Not present; Y = present. For Condenser alarm. 

o4 

Fourth probe calibration:

 (-12.0 to 12.0°C; -21 to 21°F) allows to adjust possible offset of the fourth probe. 

 

1.  

Keep the 

UP

 and 

DOWN

 keys pressed together for more than 3 sec 

the 

UP

 and 

DOWN

 keys. 

2.  

The “

PoF

” message will be displayed and the keyboard is locked. At 

this point it is only possible the viewing of the set point or the MAX or 
Min temperature stored and to switch ON and OFF the light, the 
auxiliary output and the instrument. 

 

TO UNLOCK THE KEYBOARD 

 
Keep the 

UP

 and 

DOWN

 keys pressed together for more than 3 sec. 

 

Summary of Contents for dixell XW60K

Page 1: ...ogress a continuous chill mode can be activated by holding the oUP key pressed for about 3 sec The solenoid operates to maintain the CCS set point for the time set through the CCt parameter The cycle can be terminated before the end of the set time by pressing theo UP key for 3 sec 3 3 DEFROST ON DEMAND OR RTC OPTIONAL MUST BE ORDERED Hot Gas or Electric Defrost can be managed through the tdF para...

Page 2: ...ion for the auxiliary relay Ht heating CL cooling SAA 40 230 F Set point for auxiliary relay SHy 0 25 F Differential for auxiliary output With ACH CL aux relay cut in is SAA SHy cut out SAA With ACH Ht aux relay cut in is SAA SHy cut out SAA ArP nP P1 P2 P3 P4 Probe for auxiliary relay Sdd n Y Auxiliary output working during defrost 4 5 ALARM RELAY OA3 ALR OPTIONAL By setting oA3 ALr the relay wil...

Page 3: ...arameter is also present in Pr1 ON Continuous cycle is running ON Energy saving enabled ON Light on ON Auxiliary relay on C F ON Measurement unit 6 AUTOMATIC KEYBOARD LOCK ONLY FOR T620T To avoid accidental modifications of the controller settings the T620T keyboard will be locked automatically if no key will be touched for 60 seconds The T620T will show LoC flashing for few seconds when it s lock...

Page 4: ...ming mode 2 Select the required parameter with UP or DOWN 3 Press the SET key to display its value and LED starts blinking 4 Use UP or DOWN to change its value 5 Press SET to store the new value and move to the following parameter To exit Press SET UP or wait for 15 sec without pressing any key NOTE the new programming is stored even when the procedure is exited by waiting the time out 7 8 HOW TO ...

Page 5: ...d defrosts to start together dFd Temperature displayed during defrost rt it SEt dEF rt real temperature it temperature at defrost start SEt set point dEF dEF label dAd MAX display delay after defrost 0 to 255min sets the maximum time between the end of defrost and the restarting of the real room temperature display Fdt Drip time 0 to 120min is the interval time between reaching defrost termination...

Page 6: ...ls 8 9 D I i2P Second digital input polarity oP CL oP the digital input is activated by opening the contact CL the digital input is activated by closing the contact i2F Second digital input configuration EAL bAL PAL dor dEF ES AUS Htr FAn HdF onF Sbt EAL external alarm EA message is displayed bAL serious alarm CA message is displayed PAL pressure switch alarm CA message is displayed dor door switc...

Page 7: ...th oA3 AUS and i1F AUX it switches the fourth relay 22 23 10 6 START DEFROST I1F DFR OPTIONAL It starts a defrost if there are the right conditions After the defrost is finished the normal regulation will restart only if the digital input is disabled otherwise the instrument will wait until the MdF safety time is expired 10 7 KIND OF ACTION HEATING OR COOLING I1F HTR OPTIONAL This function allows ...

Page 8: ...ments are provided with an internal check for the data integrity The EE alarm flashes when a failure in the memory data occurs In such cases the alarm output is enabled 13 3 ALARM RECOVERY Probe alarms P1 probe1 faulty P2 P3 and P4 they automatically stop 10 sec after the probe restarts normal operation Check connections before replacing the probe Temperature alarms HA LA HA2 and LA2 automatically...

Page 9: ...n a 71x29mm panel cut out Frontal protection IP65 with frontal gasket Connections Screw terminal block 2 5 mm2 Power supply from XW60K power module Display 3 digits red LED 14 2 mm high Alarm Output buzzer Power module XW60K Case 8 DN 140X176X148 Connections Screw terminal block 2 5 mm2 heat resistant wiring and 6 3mm Faston Power supply 230Vac or 110Vac 10 or 24Vac Power absorption 6VA max Inputs...

Page 10: ...30 Pr1 Start defrost delay 0 to 99 min 0 Pr2 Displaying during defrost rt it SEt dEF dEG DEF Pr2 MAX display delay after defrost 0 to 255 min 30 Pr2 Draining time 0 to 60 min 1 Pr2 First defrost after start up n Y n Pr2 Defrost delay after fast freezing 0 0 to 23h50min res 10 min 0 00 Pr2 FANS Fans operating mode C n C y O n O y O_n Pr1 Fans delay after defrost 0 to 255 min 10 Pr1 Differential of ...

Page 11: ... dEF ES Htr FAN ONF AUS LHT dor Pr1 Digital input alarm delay 0 to 255 min 0 Pr1 Number of activation of pressure switch 0 to 15 15 Pr2 Compress and fan status when open door no FAn CPr F_C F C Pr2 Regulation restart with door open alarm n Y yes Pr2 Light off during energy saving status n Y no Pr2 Differential for Energy Saving 30 to 30 C 54 to 54 F 0 Pr2 Current hour read only after first set up ...

Page 12: ...r1 Evaporator probe display read only Pr1 Third probe display read only Pr1 Fourth probe display read only Pr1 Current set point read only Pr1 Software release read only Pr2 Map code read only Pr2 18 CERTIFICATIONS 19 FOR WARRANTY AND OTHER INFORMATION 1065 Big Shanty Road Suite 100 Kennesaw GA 30144 www emerson com Support Phone 770 425 2724 select option 2 SolutionsTechSup Emerson com Sales solu...

Reviews: