background image

 

XW60K 110918 V14.7 EMERSON092718 V14.7 

XW60K 

6/12 

 

AFH 

Differential for temperature alarm recovery:

 (0.1 to 25.5°C; 1 to 45°F) intervention differential for recovery of temperature alarm. 

ALd 

Temperature alarm delay:

 (0 to 255 min) time interval between the detection of an alarm condition and alarm signaling. 

dAo 

Exclusion of temperature alarm at start-up:

 (0.0 to 24h00min, res. 10min) time interval between the detection of the temperature alarm condition after instrument power on and alarm signaling. 

CONDENSER TEMPERATURE ALARM 

AP2 

Probe selection for temperature alarm of condenser:

 (nP; P1; P2; P3; P4)  

nP

 = no probe; 

P1

 = thermostat probe; 

P2

 = evaporator probe; 

P3

 = discharge air probe; 

P4

 = Configurable probe. 

AL2 

Low temperature alarm of condenser:

 (-55 to 150°C; -67 to 302°F) when this temperature is reached the 

LA2

 alarm is signaled, possibly after the Ad2 delay. 

Au2 

High temperature alarm of condenser:

 (-55 to 150°C; -67 to 302°F) when this temperature is reached the 

HA2

 alarm is signaled, possibly after the 

Ad2

 delay. 

AH2 

Differential for temperature condenser alarm recovery:

 0.1 to 25.5°C; 1 to 45°F. 

Ad2 

Condenser temperature alarm delay:

 (0 to 255 min) time interval between the detection of the condenser alarm condition and alarm signaling. 

dA2 

Condenser temperature alarm exclusion at start up:

 0.0 to 24h00min, res. 10min. 

bLL 

Solenoid off with low temperature alarm of condenser:

 (n; Y) 

n

 = solenoid keeps on working; 

Y

 = solenoid is switched off till the alarm is present, in any case regulation restarts after 

AC

 time at minimum. 

AC2 

Solenoid off with high temperature alarm of condenser:

 (n; Y) 

n

 = solenoid keeps on working; 

Y

 = solenoid is switched off till the alarm is present, in any case regulation restarts after 

AC

 time at minimum. 

RELAY OA3 (22-23) CONFIGURATION  

tbA 

Alarm relay silencing (with oA3 =ALr):

 (n; Y) 

n

 = silencing disabled: alarm relay stays on till alarm condition lasts. 

Y

 = silencing enabled: alarm relay is switched OFF by pressing a key during an alarm. 

oA3 

Third relay configuration (XW60K: terminals 22-23): 

(dEF; FAn; ALr; 

LiG

; AUS; onF; Cp2; db; dEF2; HES) dEF = defrost; FAn = do not select it; ALr = alarm; 

LiG

 = light 

(Default)

; AUS = Auxiliary relay; 

onF = always on with instrument on; db = neutral zone 

(4.6)

; dEF2 = second defrost; HES = night curtain 

AoP 

(oA3=Alr) 

Alarm relay polarity:

 (CL; oP) it set if the alarm relay is open or closed when an alarm occurs. 

CL 

= terminals closed during an alarm; 

oP

 = terminals open during an alarm. 

DIGITAL INPUT  

i1P 

First digital input polarity:

 (oP; CL) 

oP

 = the digital input is activated by opening the contact; 

CL

 = the digital input is activated by closing the contact. 

i1F 

First digital input configuration:

 (EAL; bAL; PAL; dor; dEF; ES; AUS; Htr; FAn; HdF; onF; Sbt) 

EAL 

= external alarm: “

EA

” message is displayed; 

bAL

 

= serious alarm “

CA

” message is displayed; 

PAL

 = 

pressure switch alarm, “

CA

” message is displayed; 

dor = door switch function (use i2b)

dEF

 = activation of a defrost cycle; 

AUS

 = auxiliary relay activation with 

oA3=AUS

Htr

 = type of inverting action (cooling 

or heating); 

FAn

 = fan; 

ES

 = energy saving; 

HdF

 = Holiday defrost (enable only with RTC); 

onF

 = to switch the controller off 

STANDBY

LHt = to activate the light.(Use Keyboard i2b=dor)

 

did 

Digital input 1 alarm delay: 

(0 to 255 min) delay between the detection of the external alarm condition and its signaling. 

When 

i1F= PAL

, it is the interval of time to calculate the number of pressure switch activation. 

i2b 

Second digital input on base (n,y) 

= the second digital input is placed on the VX620 keypad. Use the (2) D.I. and (3) minus terminals.  

 
 

= the second digital input is placed on the XW60K , use terminals 8-9.  

D.I 

i2P 

Second digital input polarity:

 (oP; CL) 

oP

 = the digital input is activated by opening the contact; 

CL

 = the digital input is activated by closing the contact. 

i2F 

Second digital input configuration:

 (EAL; bAL; PAL; 

dor

; dEF; ES; AUS; Htr; FAn; HdF; onF; Sbt) EAL

 

= external alarm: 

“EA”

 message is displayed; bAL = serious alarm 

“CA”

 message is displayed; PAL = 

pressure switch alarm, 

“CA”

 message is displayed; 

dor = door switch function

; dEF = activation of a defrost cycle; AUS = auxiliary relay activation with oA3=AUS; Htr = type of inverting action (cooling or 

heating); FAn = fan; ES = energy saving; HdF = Holiday defrost (enable only with RTC); onF = to switch the controller off;

 LHt = to activate the light (activated through 

i2b=dor

)

 

d2d 

Digital input 2 alarm delay: 

(0 to 255 min) delay between the detection of the external alarm condition and its signalling. 

When 

i2F= PAL

, it is the interval of time to calculate the number of pressure switch activation. 

nPS 

Number of pressure switch activation:

 (0 to 15) Number of activation, during the 

did

 or 

d2d

 interval, before signalling an alarm event (

i1F, i2F=PAL

).  

If the 

nPS

 activation during 

did 

or 

d2d

 time is reached, switch off and on the instrument to restart normal regulation. 

odC 

Controller status when open door:

 (no; FAn; CPr; F_C;)  

no

 = no effect  

FAn

 = FAN off; 

CPr

 = LLS Closed, 

F_C

 = Fan and LLS OFF. 

rrd 

Outputs restart after door open alarm:

 (n; Y) 

n

 = outputs follow the 

odC

 parameter.  

Y

 = outputs restart with a door open alarm.  

LES 

Light off during Energy Saving status: 

n; Y. 

HES 

Delta temperature during an Energy Saving cycle: 

(-30.0 to 30.0°C; -54 to 54°F) it sets the increasing value of the set point 

[SET+HES]

 during the Energy Saving cycle.

 

Est 

Energy Savings Timeout; 

0 to 255 hours

 

9

 

REAL TIME CLOCK PARAMETERS (OPTIONAL) 

CURRENT TIME AND WEEKLY HOLIDAYS (ONLY FOR MODELS WITH RTC) 

Hur 

Current hour: 

0 to 23h.

 

Min 

Current minute:

 0 to 59min.

 

dAY 

Current day:

 Sun to SAt.

 

dYM 

Day of the month: 

1 to 31. 

Mon 

Month: 

1 to 12. 

YAr 

Year: 

00 to 99. 

Hd1 

First weekly holiday: 

(Sun to nu) set the first day of the week which follows the holiday times.

 

Hd2 

Second weekly holiday: 

(Sun to nu) set the second day of the week which follows the holiday times.

 

N.B.: Hd1, Hd2 

can be set also as

 

“nu” 

value (Not Used).

  

ENERGY SAVING TIMES (ONLY FOR MODELS WITH RTC) 

ILE 

Energy Saving cycle start during workdays:

 (0 to 23h50min) during the Energy Saving cycle the set point is increased by the value in HES so that the operation set point is 

SET+HES

.

 

dLE 

Energy Saving cycle length during workdays:

 (0 to 24h00min) sets the duration of the Energy Saving cycle on workdays.

 

ISE 

Energy Saving cycle start on holidays:

 0 to 23h50min.

 

dSE 

Energy Saving cycle length on holidays:

 0 to 24h00min.

 

TO SET DEFROST TIMES (ONLY FOR MODELS WITH RTC) 

Ld1...Ld6 

Workday defrost  start:

 (0 to 23h50min) these parameters set the  beginning  of the 6 programmable defrost cycles  during workdays. Ex:  when 

Ld2=12.4

 the second defrost starts  at  12.40  during 

workdays.

 

Sd1...Sd6 

Weekend defrost start:

 (0 to 23h50min) these parameters set the beginning of the 6 programmable defrost cycles on holidays. Ex: when 

Sd2=3.4

 the second defrost starts at 3.40 on holidays.

 

oA3=HES NIGHT CURTAINS or LIGHTS (ONLY FOR MODELS WITH RTC) 

ILE 

Energy Saving cycle start during workdays:

 (0 to 23h50min) Start of the Energy Saving period the 

oA3

 relay is active.

 

dLE 

Energy Saving cycle length during workdays:

 (0 to 24h00min) sets the duration of the Energy Saving period the 

oA3

 relay is active on workdays.

 

ISE 

Energy Saving cycle start on holidays:

 0 to 23h50min.

 

dSE 

Energy Saving cycle length on holidays:

 0 to 24h00min.

 

Note: rtC parameters, t

o disable a defrost cycle set it to “nu” (not used).

 

 

OTHER 

Adr 

Serial address:

 (1 to 247) identifies the instrument address when connected to a ModBUS compatible monitoring system. 

Summary of Contents for dixell XW60K

Page 1: ...ogress a continuous chill mode can be activated by holding the oUP key pressed for about 3 sec The solenoid operates to maintain the CCS set point for the time set through the CCt parameter The cycle can be terminated before the end of the set time by pressing theo UP key for 3 sec 3 3 DEFROST ON DEMAND OR RTC OPTIONAL MUST BE ORDERED Hot Gas or Electric Defrost can be managed through the tdF para...

Page 2: ...ion for the auxiliary relay Ht heating CL cooling SAA 40 230 F Set point for auxiliary relay SHy 0 25 F Differential for auxiliary output With ACH CL aux relay cut in is SAA SHy cut out SAA With ACH Ht aux relay cut in is SAA SHy cut out SAA ArP nP P1 P2 P3 P4 Probe for auxiliary relay Sdd n Y Auxiliary output working during defrost 4 5 ALARM RELAY OA3 ALR OPTIONAL By setting oA3 ALr the relay wil...

Page 3: ...arameter is also present in Pr1 ON Continuous cycle is running ON Energy saving enabled ON Light on ON Auxiliary relay on C F ON Measurement unit 6 AUTOMATIC KEYBOARD LOCK ONLY FOR T620T To avoid accidental modifications of the controller settings the T620T keyboard will be locked automatically if no key will be touched for 60 seconds The T620T will show LoC flashing for few seconds when it s lock...

Page 4: ...ming mode 2 Select the required parameter with UP or DOWN 3 Press the SET key to display its value and LED starts blinking 4 Use UP or DOWN to change its value 5 Press SET to store the new value and move to the following parameter To exit Press SET UP or wait for 15 sec without pressing any key NOTE the new programming is stored even when the procedure is exited by waiting the time out 7 8 HOW TO ...

Page 5: ...d defrosts to start together dFd Temperature displayed during defrost rt it SEt dEF rt real temperature it temperature at defrost start SEt set point dEF dEF label dAd MAX display delay after defrost 0 to 255min sets the maximum time between the end of defrost and the restarting of the real room temperature display Fdt Drip time 0 to 120min is the interval time between reaching defrost termination...

Page 6: ...ls 8 9 D I i2P Second digital input polarity oP CL oP the digital input is activated by opening the contact CL the digital input is activated by closing the contact i2F Second digital input configuration EAL bAL PAL dor dEF ES AUS Htr FAn HdF onF Sbt EAL external alarm EA message is displayed bAL serious alarm CA message is displayed PAL pressure switch alarm CA message is displayed dor door switc...

Page 7: ...th oA3 AUS and i1F AUX it switches the fourth relay 22 23 10 6 START DEFROST I1F DFR OPTIONAL It starts a defrost if there are the right conditions After the defrost is finished the normal regulation will restart only if the digital input is disabled otherwise the instrument will wait until the MdF safety time is expired 10 7 KIND OF ACTION HEATING OR COOLING I1F HTR OPTIONAL This function allows ...

Page 8: ...ments are provided with an internal check for the data integrity The EE alarm flashes when a failure in the memory data occurs In such cases the alarm output is enabled 13 3 ALARM RECOVERY Probe alarms P1 probe1 faulty P2 P3 and P4 they automatically stop 10 sec after the probe restarts normal operation Check connections before replacing the probe Temperature alarms HA LA HA2 and LA2 automatically...

Page 9: ...n a 71x29mm panel cut out Frontal protection IP65 with frontal gasket Connections Screw terminal block 2 5 mm2 Power supply from XW60K power module Display 3 digits red LED 14 2 mm high Alarm Output buzzer Power module XW60K Case 8 DN 140X176X148 Connections Screw terminal block 2 5 mm2 heat resistant wiring and 6 3mm Faston Power supply 230Vac or 110Vac 10 or 24Vac Power absorption 6VA max Inputs...

Page 10: ...30 Pr1 Start defrost delay 0 to 99 min 0 Pr2 Displaying during defrost rt it SEt dEF dEG DEF Pr2 MAX display delay after defrost 0 to 255 min 30 Pr2 Draining time 0 to 60 min 1 Pr2 First defrost after start up n Y n Pr2 Defrost delay after fast freezing 0 0 to 23h50min res 10 min 0 00 Pr2 FANS Fans operating mode C n C y O n O y O_n Pr1 Fans delay after defrost 0 to 255 min 10 Pr1 Differential of ...

Page 11: ... dEF ES Htr FAN ONF AUS LHT dor Pr1 Digital input alarm delay 0 to 255 min 0 Pr1 Number of activation of pressure switch 0 to 15 15 Pr2 Compress and fan status when open door no FAn CPr F_C F C Pr2 Regulation restart with door open alarm n Y yes Pr2 Light off during energy saving status n Y no Pr2 Differential for Energy Saving 30 to 30 C 54 to 54 F 0 Pr2 Current hour read only after first set up ...

Page 12: ...r1 Evaporator probe display read only Pr1 Third probe display read only Pr1 Fourth probe display read only Pr1 Current set point read only Pr1 Software release read only Pr2 Map code read only Pr2 18 CERTIFICATIONS 19 FOR WARRANTY AND OTHER INFORMATION 1065 Big Shanty Road Suite 100 Kennesaw GA 30144 www emerson com Support Phone 770 425 2724 select option 2 SolutionsTechSup Emerson com Sales solu...

Reviews: