background image

 

XW60K 110918 V14.7 EMERSON092718 V14.7 

XW60K 

9/12 

 

15

 

ELECTRICAL CONNECTIONS 

XW60K

 is provided with screw terminal blocks to connect cables with a cross section up to 2.5 mm

for the RS485 (optional) and the keyboard. To connect the other inputs, power supply and relays, 

XW60K

 is provided with 

Faston connections (6.3mm). Heat-resistant cables should 

be used. Before connecting cables make sure the power supply complies with the instrument’s requirements. Separate the probe 

cables from the power supply 

cables, and from the outputs and the power connections. Do not exceed the maximum current allowed on each relay, in case of heavier loads use a suitable external relay. 

NOTE:

 

the maximum current allowed for all the loads is 16A.

 

15.1

 

PROBE CONNECTIONS 

The probes shall be mounted with the bulb angled upwards to prevent damage due to casual liquid infiltration. It is recommended to place the return air probe to correctly measure the average room temperature. Place the 
defrost termination probe among the evaporator fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during defrost, to prevent premature defrost termination. Place the Discharge 
Air Probe on the discharge side of the evaporator.  
 

 

 

 

16

 

Technical data 

KeyPads 
Housing: 

self extinguishing ABS

 

Case: T620 and T620T: 

face 38x185 mm; depth 23mm 

 

VX620: 

face 72x56 mm; depth 23mm;  

 

CX620: 

face 75x36 mm; depth 23mm 

Mounting:

 

T620T

 panel mounting in a 150x31 mm panel cut-out with the 2 metal brackets supplied. 

VX620: 

panel mounting in a standard J-Box, can be low voltage 

 

CX620: 

panel mounting in a 71x29mm panel cut-out 

Frontal protection:

 IP65 with frontal gasket 

Connections: 

Screw terminal block 

 2.5 mm

2

  

Power supply: 

from

 XW60K 

power module

 

Display

: 3 digits, red LED, 14.2 mm high 

Alarm Output

: buzzer. 

 
Power module XW60K  
Case: 8 DN:

 140X176X148 

Connections: 

Screw terminal block 

 2.5 mm

2

 heat-resistant wiring and 6.3mm Faston 

Power supply: 

230Vac or. 110Vac 

 10% or 24Vac

 

Power absorption: 

6VA max

 

Inputs

: 4 NTC or PTC probes 

Digital inputs

: 2 free voltage 

Relay outputs: 

Total current on loads MAX. 16A

 

Liquid Line Solonoid:

 relay SPST 8 A, 250Vac 

Fan:

 relay SPST 16 A, 250Vac 

 

Defrost:

 relay SPST 16A, 250Vac  

 

Light (oA3):

 relay SPST 16A, 250Vac 

Serial output:

 TTL standard 

Communication protocol:

 Modbus - RTU

 

Data storing

: on the non-volatile memory (EEPROM) 

Kind of action: 

1B 

Pollution degree: 

normal 

Software class: 

A

 

Operating temperature: 

-10 to 60°C (14 to 140°F) 

Storage temperature: 

-25 to 60°C (-13 to 140°F)  

Relative humidity:

 20 to 85% (no condensing) 

Measuring and regulation range:  

NTC probe: 

-40 to 110°C (-58 to 230°F) 

PTC probe: 

-50 to 150°C (-58 to 302°F) 

Resolution: 

0.1°C or 1°C or 1°F (selectable) 

Accuracy (ambient temp. 25°C):

 ±0.5°C ±1 digit 

17

 

Default setting values 

 

Label 

Name 

Range 

Default 

Level 

REGULATION

 

 

Set point 

LS; US 

- - - 

Real time clock menu 

(OPTIONAL)

 

Pr1 

 

Differential 

[0.1 to 25.5°C] [1 to 45°F] 

Pr1 

 

Minimum set point 

[-55.0°C to SET] [-67°F to SET] 

-58 

Pr2 

 

Maximum set point 

[SET to 150°C] [SET to 302°F] 

230 

Pr2 

 

Thermostat probe calibration 

[-12 to 12°C] [-21 to 21°F] 

Pr1 

 

Evaporator probe presence 

n=not present; Y=pres. 

yes 

Pr1 

 

Evaporator probe calibration 

[-12 to 12°C] [-21 to 21°F] 

Pr2 

 

Discharge Air Probe presence 

n=not present; Y=pres. 

no 

Pr2 

 

Third probe calibration 

[-12 to 12°C] [-21 to 21°F] 

Pr2 

 

Fourth probe presence (opt. cond. probe) 

n=not present; Y=pres. 

no 

Pr2 

 

Fourth probe calibration 

[-12 to 12°C] [-21 to 21°F] 

Pr2 

Summary of Contents for dixell XW60K

Page 1: ...ogress a continuous chill mode can be activated by holding the oUP key pressed for about 3 sec The solenoid operates to maintain the CCS set point for the time set through the CCt parameter The cycle can be terminated before the end of the set time by pressing theo UP key for 3 sec 3 3 DEFROST ON DEMAND OR RTC OPTIONAL MUST BE ORDERED Hot Gas or Electric Defrost can be managed through the tdF para...

Page 2: ...ion for the auxiliary relay Ht heating CL cooling SAA 40 230 F Set point for auxiliary relay SHy 0 25 F Differential for auxiliary output With ACH CL aux relay cut in is SAA SHy cut out SAA With ACH Ht aux relay cut in is SAA SHy cut out SAA ArP nP P1 P2 P3 P4 Probe for auxiliary relay Sdd n Y Auxiliary output working during defrost 4 5 ALARM RELAY OA3 ALR OPTIONAL By setting oA3 ALr the relay wil...

Page 3: ...arameter is also present in Pr1 ON Continuous cycle is running ON Energy saving enabled ON Light on ON Auxiliary relay on C F ON Measurement unit 6 AUTOMATIC KEYBOARD LOCK ONLY FOR T620T To avoid accidental modifications of the controller settings the T620T keyboard will be locked automatically if no key will be touched for 60 seconds The T620T will show LoC flashing for few seconds when it s lock...

Page 4: ...ming mode 2 Select the required parameter with UP or DOWN 3 Press the SET key to display its value and LED starts blinking 4 Use UP or DOWN to change its value 5 Press SET to store the new value and move to the following parameter To exit Press SET UP or wait for 15 sec without pressing any key NOTE the new programming is stored even when the procedure is exited by waiting the time out 7 8 HOW TO ...

Page 5: ...d defrosts to start together dFd Temperature displayed during defrost rt it SEt dEF rt real temperature it temperature at defrost start SEt set point dEF dEF label dAd MAX display delay after defrost 0 to 255min sets the maximum time between the end of defrost and the restarting of the real room temperature display Fdt Drip time 0 to 120min is the interval time between reaching defrost termination...

Page 6: ...ls 8 9 D I i2P Second digital input polarity oP CL oP the digital input is activated by opening the contact CL the digital input is activated by closing the contact i2F Second digital input configuration EAL bAL PAL dor dEF ES AUS Htr FAn HdF onF Sbt EAL external alarm EA message is displayed bAL serious alarm CA message is displayed PAL pressure switch alarm CA message is displayed dor door switc...

Page 7: ...th oA3 AUS and i1F AUX it switches the fourth relay 22 23 10 6 START DEFROST I1F DFR OPTIONAL It starts a defrost if there are the right conditions After the defrost is finished the normal regulation will restart only if the digital input is disabled otherwise the instrument will wait until the MdF safety time is expired 10 7 KIND OF ACTION HEATING OR COOLING I1F HTR OPTIONAL This function allows ...

Page 8: ...ments are provided with an internal check for the data integrity The EE alarm flashes when a failure in the memory data occurs In such cases the alarm output is enabled 13 3 ALARM RECOVERY Probe alarms P1 probe1 faulty P2 P3 and P4 they automatically stop 10 sec after the probe restarts normal operation Check connections before replacing the probe Temperature alarms HA LA HA2 and LA2 automatically...

Page 9: ...n a 71x29mm panel cut out Frontal protection IP65 with frontal gasket Connections Screw terminal block 2 5 mm2 Power supply from XW60K power module Display 3 digits red LED 14 2 mm high Alarm Output buzzer Power module XW60K Case 8 DN 140X176X148 Connections Screw terminal block 2 5 mm2 heat resistant wiring and 6 3mm Faston Power supply 230Vac or 110Vac 10 or 24Vac Power absorption 6VA max Inputs...

Page 10: ...30 Pr1 Start defrost delay 0 to 99 min 0 Pr2 Displaying during defrost rt it SEt dEF dEG DEF Pr2 MAX display delay after defrost 0 to 255 min 30 Pr2 Draining time 0 to 60 min 1 Pr2 First defrost after start up n Y n Pr2 Defrost delay after fast freezing 0 0 to 23h50min res 10 min 0 00 Pr2 FANS Fans operating mode C n C y O n O y O_n Pr1 Fans delay after defrost 0 to 255 min 10 Pr1 Differential of ...

Page 11: ... dEF ES Htr FAN ONF AUS LHT dor Pr1 Digital input alarm delay 0 to 255 min 0 Pr1 Number of activation of pressure switch 0 to 15 15 Pr2 Compress and fan status when open door no FAn CPr F_C F C Pr2 Regulation restart with door open alarm n Y yes Pr2 Light off during energy saving status n Y no Pr2 Differential for Energy Saving 30 to 30 C 54 to 54 F 0 Pr2 Current hour read only after first set up ...

Page 12: ...r1 Evaporator probe display read only Pr1 Third probe display read only Pr1 Fourth probe display read only Pr1 Current set point read only Pr1 Software release read only Pr2 Map code read only Pr2 18 CERTIFICATIONS 19 FOR WARRANTY AND OTHER INFORMATION 1065 Big Shanty Road Suite 100 Kennesaw GA 30144 www emerson com Support Phone 770 425 2724 select option 2 SolutionsTechSup Emerson com Sales solu...

Reviews: