background image

This document may be photocopied for personal use. 

Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.

Join Emerson Retail Solutions Technical Support on Facebook. http://on.fb.me/WUQRnt

The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or 

applicability. Emerson Climate Technologies Retail Solutions, Inc. and/or its affiliates (collectively “Emerson”), reserves the right to modify the designs or specifications of such products at any time without notice. Emerson does 

not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any product remains solely with the purchaser and end-user.

026-4157 19-FEB-2016 Emerson is a trademark of Emerson Electric Co. ©2016 Emerson Climate Technologies Retail Solutions, Inc. All rights reserved.

Document Part # 026-4157 Rev 0 19-FEB-2016

Page 4 of 4

1. In the 

COM2 Connection

 field, if the value displayed is something other than 

IO Net

, set this parame-

ter to 

IO Net

.

2. In the 

COM2 Baud

 field, set the value to 

19.2 Kbaud

.

Figure 2  - E2E Serial Configuration Screen - Baud Rate 

Summary of Contents for E2 Enhanced RX

Page 1: ...RS232 COM C host network to connect all units to a modem for alarm dial out E2Es may use either Echelon or Ethernet for box to box communication The existing host network wiring may not be used for E2E box to box communication you will either have to rewire using approved Echelon network wire or wire CAT 5 cable to an approved network router or switch Refer to the E2E User s Guide for more informa...

Page 2: ...CC BEC BCU I O networks Set the three jumpers to the middle I O terminated position if the port is at the end of a network segment or the hub of a star configuration and down NO unterminated if the port is in the middle of a segment There is one set of RS485 jumpers for each RS485 port COM2A 2B COM6 and COM4A B Jumpers J8 J10 are located directly above the COM2A connector port and jumpers J11 J13 ...

Page 3: ... same baud rate all I O boards connected to the RMCC BEC BCU were also set to communicate at 19200 baud Because the default E2E baud rate for I O networks is 9600 baud you will need to change the COM2 baud rate setting This must be done in the C3 Serial tab of the E2E s General Controller Info screens 1 Log into the E2 with Level 4 password access 2 Press to access the General Controller Info scre...

Page 4: ...collectively Emerson reserves the right to modify the designs or specifications of such products at any time without notice Emerson does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any product remains solely with the purchaser and end user 026 4157 19 FEB 2016 Emerson is a trademark of Emerson Electric Co ...

Reviews: