background image

 

www.easyheat.com

 

TyPICAL MeMBRANe ROOF 

Ice dams may occur on flat roofs typically at the edge of the 

flashing and at drains.  Flat roofs are normally pitched toward 

drains and these paths can become obstructed by snow and ice.  

To maintain a path for melt water to run off, install the heating 

cable as shown below using appropriate attachment methods.   

Additional heating cable may be required for downspouts. 

Note:

 Heating cable attachment methods are not shown in the 

diagram below.  For attachment we recommend using our ZH-C 

roof clip.  Properly securing this clip to different roofing materials 

may require differing methods; consult a roofing professional for 

more information.  If the situation warrants it may also be  

possible to use strips of the roofing membrane to secure the 

heating cable by adhering the cable under the strip to the main 

roofing membrane (see figure below).

Heating cable layout on flat roof:

•   Install heating cable around the perimeter.

•   Install heating cable running from the perimeter to the drain.

•   Heating cable is to be installed into drain so that it extends at 

least 12 inches (30cm) into a heated space.

Heating cable control options and power 

connection 

For 120 Volt cables, the heating cable can be simply plugged 

into a ground fault protected electrical receptacle, when icing 

conditions are present on the roof. The (optional) EasyHeat RS-2 

Roof Sentry (120 Volt) control can be used to automatically 

ensure cables are energized only when icing conditions are 

present on the roof, minimizing energy consumption and 

extending cable life.

For 240 Volt cables, the cable is designed to be directly 

connected into an appropriate electrical connection box. 

Since it will be necessary to remove power from the cable from 

time to time, such as in summer, always connect the cable to 

an appropriate double-pole electrical switch. If the heating 

cable is the only load on the circuit, the branch circuit breaker 

may be used to disconnect power from the cable (switch is 

not necessary). Several automatic controls are available from 

EasyHeat.

        Always connect a pilot light into the circuit of 240V cables to 

indicate when the cables are energized.

Testing the system. Once the installation is complete, apply power 

to the heating cable; the surface of the cable will feel warm after 

about 15 minutes.

Operation

If no automatic controls are installed, energize the cable only 

when icing conditions are present on the roof, and de-energize 

when icing conditions are no longer present. For 120 Volt models 

only, the power cord plug contains a pilot light indicating that 

power is being applied to the cable. Ensure power is removed 

from the cable/control in summer.

 

Maintenance

Check cable annually for any damage, such as nicks or cuts 

possibly caused by animals or other activity on the roof. Check 

any ground fault protection devices for proper operation. 

Remove all debris (leaves, twigs, pine needles, etc.) from roof, 

gutters and downspouts prior to energizing the roof cable. Do not 

attempt to energize the roof cable if any of these problems are 

discovered.

Heating cable should be positioned around the 

perimeter and in the valleys of a flat roof. The 

heating cable must extend into the drain or 

scupper to allow the melt water to exit the roof. 

Heating cable is to be installed into drain  

so that it extends at least 12 inches (30 cm) 

into a heated space. 

Drain

Slope

Junction Box

Cable 

End Seal

Heating cable should be positioned  

around the perimeter of a flat roof. The 

 

heating cable must extend into the drain 

or scupper to allow the melt water to 

exit the roof. 

Drip Loop

Cable  

End Seal

Junction Box

Scupper

Heating cable provides a 

continuous heated path to 

allow melt water to run off the 

roof before it refreezes.

Adhesive

Roof Membrane

Heating Cable

Membrane 

Strip

Summary of Contents for EASYHEAT PSR1006

Page 1: ...fiberglass insulation or equivalent For protection to 40 F 40 C use 1 25 4 mm fiberglass insulation Note Allow an extra foot 30 48 cm of heating cable for each valve Pipe Freeze Protection 120 Volt Cable Selection Chart Model No Length in Ft m Wattage 50 F 10 C PSR1006 6 1 83 30 PSR1012 12 3 76 60 PSR1018 18 5 49 90 PSR1024 24 7 32 120 PSR1050 50 15 24 250 PSR1075 75 22 86 375 PSR1100 100 30 48 50...

Page 2: ... is the same length as the pipe run it straight along the bottom of the pipe If two cables are required position them in the 4 and 8 o clock positions If the cable selected is exactly double the pipe length apply a single trace of cable straight along the pipe all the way to the end and loop back applying cable straight along the pipe all the way back to the starting point If the cable selected is...

Page 3: ...hingle Roof Single cable shown for roof and gutter H loop height overhang Typical metal roof Separate cables shown for roof and gutter DSH Hanger Clamp Mid Circuit Downspout Installation End Seal Must not be submerged nor allowed to be at the bottom end of a down spout End Circuit Downspout Installation Roof Clip ZH C Heater Cable Roof Clips 24 60 96 cm O C H Drip Loop Typ Weatherproof outlet box ...

Page 4: ...the cable to an appropriate double pole electrical switch If the heating cable is the only load on the circuit the branch circuit breaker may be used to disconnect power from the cable switch is not necessary Several automatic controls are available from EasyHeat Always connect a pilot light into the circuit of 240V cables to indicate when the cables are energized Testing the system Once the insta...

Page 5: ...o you the model or sample was used merely to illustrate the general type and quality of the goods and not to represent that the goods would necessarily be of that type or nature No agent employee or representative of ours has authority to bind us to any affirmation representation or warranty concerning the goods sold unless such affirmation representation or warranty is specifically incorporated b...

Reviews: