EC2-311 Display Case and Coldroom Controller 

Operating Instructions 

GB 

List Of Parameters 

 

/ DISPLAY 

PARAMETERS 

Min Max

 

Unit Def. Custom

/1  Value to show 

0   

  0 = Thermostat control temperature with Temp. alignment °C 

1 = Air-in temperature °C 
2 = Air-out temperature °C 
3 = Alarm temperature °C 
4 = Defrost termination  temperature °C 
5 = Coil-in temperature °C  
6 = Coil-out temperature °C 
7 = Calculated superheat °K 
8 = Valve opening in % 
9 = Displays defrost status 

         

/2  Alarm suppression   0= off, 1 = on 

0   

/5  Temperature Unit  

0 = °C, 1 = °F 

0   

/6  Decimal point  

0 = yes, 1 = no 

0   

/7  Display during defrost 

 

  0 = dF (= defrost mode);   1 = dF + defrost termination temp. 

 

2 = dF + control temperature 

       

 

/C  Temperature alignment  for /1=0 

- 20

20 

0.0   

A ALARM-PARAMETERS 

 

 

 

 

 

A0  Mean factor alarm temperature 

100 

100   

A1  Low temp alarm delay 

180 

min 

5   

A2  High temp alarm delay 

180 

min 

5   

A3  Alarm delay after defrost 

180 

min 

10   

AH 

High temp alarm limit 

AL 

70 

°C / K 

40   

AL  Low temp alarm limit 

-55  AH  °C / K  -50   

At  Alarm limit type 

0   

  0=absolute temperatures °C; 1= relative temperatures K to setpoint          

r THERMOSTAT-PARAMETERS 

r1  Min setpoint 

-50 

r2 

°C 

- 50   

r2 Setpoint max 

r1  + 60  °C 

40   

r3  Day/night control   

0 = off, 1 = on 

1   

r4 Thermostat mode 

1   

  0 =  off, no thermostat function, continues cooling  air in sensor 

monitoring off, no temp. alarms generated  

1 =  cooling, deadband control  

cut in   = set-point + difference   
cut out = set-point 

2 =  cooling, modulating thermostat 

cut in   = set-point   
cut out = set-point – difference /2 

3 =  heating, deadband control  

cut in   = set-point – difference  
cut out = set-point 

4 =  on, external control using nvi Valve via SNMP. Air in and air 

out sensor monitoring off. Temp. alarms will be generated 

   

 

   

r6 Setpoint night 

r1  r2 

°C 

4.0   

r7 Differential night 

0.1  20.0 

2.0   

r8  Mean factor, day operation 

100 

100 

 

r9  Mean factor, night operation 

100 

50 

 

rd Differential day 

0.1  20.0 

2.0   

St Setpoint day 

r1  r2 

°C 

2.0   

d DEFROST 

PARAMETERS 

 

 

 

 

 

d0 Defrost mode 

1   

  0 =  natural defrost, defrost heater not activated 

pulsed defrost not possible 

1 =  forced defrost, defrost heater activated, pulsed 

defrost possible 

2 =  forced defrost, defrost heater activated, pulsed defrost possible, 

defrost termination using nviStartUp via SNMP 

 

 

     

d1  Termination by:  

0   

  0 =  termination by temperature,  

termination by time will generate an alarm 

1 =  termination by time,  

termination by temperature will generate an alarm 

2 =  first, what ever comes first time or temperature, no alarm 
3 =  last, by time and temperature, no alarm 

         

d2  Defrost termination sensor  

 

  0 = Dedicated defrost sensor must be installed 

1 = Air-out sensor used for defrost termination 

         

 

   

Min

 

Max

 

Unit Def. Custom

d3 Pulsed defrost 

0   

  0 =  off, no pulsed defrost, heaters switched off at defrost termin-

ation temperature dt or max. time dP whatever is selected  

1 =  on, pulsed defrost, dd and dH in use, heaters are switched off at 

dH and switched on again at  dH – dd 

         

d4 Defrost at startup  

0 = no, 1 = yes 

0   

d5 Delay power up defrost 

180 

min 

0   

d6 Pump down delay 

180 

sec 

0   

  Compressor will run during pump down delay while valve is closed           

d7 Drain delay 

15 

min 

2   

d8 Injection delay 

180 

sec 

0   

  Valve is open during injection delay while compressor is not running          

d9 Demand defrost mode 

0 = off,  1 = on,  
2 = on together with timed defrost 

0 2  -  0   

dd Pulsed defrost differential 

20 

2   

dH Pulsed defrost setpoint 

-40 

dt 

°C 

5   

dt  Defrost termination temperature 

-40 

90 

°C 

8   

dP Max defrost duration 

180 

min 

30   

dI Defrost interval 

192 

8   

du Start up delay after synch 

180 

min 

30   

F FAN-PARAMETERS 

 

 

 

 

 

F1 Fan startup by:   

0 = on  

0   

  1 = delayed by time Fd, error on temperature 

2 = by temperature Ft, error on time 
3 = first, whatever comes first time or temperature, no alarm 
4= last, time and temperature must come, no alarm 

         

F2 During no cooling  

0   

  0 = on; 1 = off; 2 = delayed by F4; 3 = off, when door open 

         

F3 During defrost  

0 = on, 1 = off 

0   

F4 Stop delay time  

30 

min 

0   

F5 During cleaning   

0 = off, 1 = on 

0   

Fd Fan delay after defrost 

30 

min 

0   

Ft On temp after defrost 

-40 

40 

°C 

0   

C COMPRESSOR-PARAMETERS 

C0 Delay first start after power up 

15 

min 

0   

C1 Cycle time 

15 

min 

0   

C2 Min stop time it 

15 

min 

0   

C3 Min run time 

15 

min 

0   

u SUPERHEAT PARAMETERS 

u0 Refrigerant    0 = R22, 1 = R134a,  

3   

  2 = R507; 3 = R404A; 4 = R407C; 5 = R410A; 6 = R124; 7 = R744           

u1 Correction glide / dp 

Glide               =  positive  values 
Pressure drop  =  negative values 

-20.0 20.0 

0.0   

u2 MOP control 

 

0 = MOP off, 1 = MOP on 

0 1  -  0 

 

u3 MOP temperature 

-40 

40 

°C 

0   

u4 Superheat mode  

0 = off 

1 = fixed superheat 
2 = adaptive superheat 

0 2  -  1 

 

u5 Superheat init setpoint 

u6 

u7 

6   

u6 Superheat setpoint min 

u7 

3   

u7 Superheat setpoint max 

u6 

20 

15   

uu Start 

opening 

25 

75 % 30 

 

H OTHER PARAMETERS 

 

 

 

 

 

H2 Display access 

 

3   

  0 = all disabled (Caution, access to controller only via LON 

network possible) 

1 = Keyboard enabled 
2 = IR remote control enabled 
3 = Keyboard and IR remote control; Temporary data display and 

manual defrost enabled. 

4 = Keyboard and IR remote control; Temporary data display 

disabled. Control setpoint with 

SEL

 key and manual defrost 

enabled. 

       

H3 IR access code 

199 

0   

H5 Password 0 

199 

12

 

 

 

Summary of Contents for EC2-311

Page 1: ...al limits Comply with local electrical regulations when wiring Technical Data EC2 Series Controller Power supply 24VAC 10 50 60 Hz Class II Power consumption 20VA max including EX2 Communication LonWorks Interface FTT10 RJ45 connector Plug in connector size Removable screw terminals wire size 0 14 1 5mm2 Temperature storage operating 20 65 C 0 60 C Humidity 0 80 r h non condensing Protection class...

Page 2: ...ress or to show the code of the parameter that has to be changed Press SEL to display the selected parameter value Press or to increase or decrease the value Press SEL to temporarily confirm the new value and display its code Repeat the procedure from the beginning press or to show To exit and save the new settings Press PRG to confirm the new values and exit the parameters modification procedure ...

Page 3: ... first time or temperature no alarm 3 last by time and temperature no alarm d2 Defrost termination sensor 0 1 1 0 Dedicated defrost sensor must be installed 1 Air out sensor used for defrost termination Min Max Unit Def Custom d3 Pulsed defrost 0 1 0 0 off no pulsed defrost heaters switched off at defrost termin ation temperature dt or max time dP whatever is selected 1 on pulsed defrost dd and dH...

Page 4: ... wink request is received OF Node is offline The node is offline and no application is running This is the result of a network management command and will happen for example during node installation dS Defrost standby dP Pump down dF Defrost cycle dd Defrost drain delay dI Defrost injection delay du Defrost start up delay Cn Cleaning CL Alarms are cleared Visualising Data LON Monitoring Server The...

Reviews: