EC2-311 Display Case and Coldroom Controller 

Operating Instructions 

GB 

Formula for Mean Factors A0, r8, r9 

Temperature calculation by the following formula: 
     Temperature = Air

in

 * (1 - Mean Factor / 100) + Air

out

 * Mean Factor / 100 

Examples: 

Mean factor = 0    ,   Temperature = Air in 
Mean factor = 100,   Temperature = Air out 
Mean factor = 50   ,   Temperature = Average between Air-in and Air-out 

Alarm Codes 

E0  

Coil in sensor alarm

 

E1  

Coil out sensor alarm

 

E2  

Air-in sensor alarm 

This Alarm Code is inhibited if no air-in sensor used 

(A0, r8 and r9 = 100)

 

E3  

Air-out sensor alarm 

This Alarm Code is inhibited if no air-out sensor used 

(A0, r8 and r9 = 0) and fin sensor installed (d2 = 1)

 

E4  

Fin sensor alarm 

This Alarm Code is inhibited if no fin sensor used (d2 = 0)

 

Explanations for 

E0 … E4 Alarms

: No sensor connected, or the sensor 

and/or the sensor cable is broken or short-circuited. 

Er 

Data error display - out of range 

 

Data send to the display is out of range. 

AH 

High temperature alarm 

AL 

Low temperature alarm 

AE 

Thermostat emergency operation 

 

Air sensor failure, system is in continuous cooling mode

 

AF 

Valve Status 

 

Valve closed due to compressor safety loop active 

Ao 

Superheat, emergency operation 

 Sensor(s) 

failure

 

Ar 

No refrigerant flow detected

 

 

No refrigerant flow was detected 

Au 

Valve open 100% for more than 10 minutes 

dt 

Forced

 

defrost termination (time or temperature) 

Ft 

Forced fan startup (time or temperature) 

Messages 

---  

No data to display 

 

The display will show an “---” at node start up and when no data is send to 
the display.

 

In  

Reset to default values activated 

 

The display will show an “In” when the factory default configuration data set 
is initialized.

 

Id  

Wink request received 

 

The display will show a flashing “Id” when the wink request was received. 
The flashing “Id” will be shown on the display until the service button will 
be pressed, or a 30 min delay timer will expire or a second wink request is 
received.  

OF  

Node is offline 

 

The node is offline and no application is running. This is the result of a 
network management command and will happen for example during node 
installation.

 

dS

 Defrost 

standby 

dP

 Pump 

down 

dF

 Defrost 

cycle 

dd

 

Defrost drain delay 

dI

 Defrost 

injection 

delay 

du

 

Defrost start-up delay 

Cn

 Cleaning 

CL

 

Alarms are cleared 

Visualising Data: LON Monitoring Server 

The 

EC2-311 

has a LON communication interface enabling the controller to be 

directly connected to a Monitoring Server. It can be connected by using the optional 
cable assembly to a LON network (ECC-014, order nr. 804 381, with RJ45 to open, 
cable length 3m). 

Neuron ID / Service PIN: 

The service pin is available on the display. It is used to identify the controller in a 
LON network. Press the    button for app. 1 second to send the Neuron ID. The 
LED in the left upper corner will indicate the transmission of the Neuron ID.  
The default settings may be modified remotely from the Monitoring Server via the 
LON network. Consult the Monitoring Server user manual for more information. 
It is also possible to display live graphical data on the server or to log data 
containing the control temperature at defined intervals. 

 
 
 
 
 
 
 
 
 
 
 
Emerson Electric GmbH & Co OHG is not to be held responsible for erroneous 
literature regarding capacities, dimensions, applications, etc. stated herein. 
Products, specifications and data in this literature are subject to change without 
notice. The information given herein is based on technical data and tests which 
EMERSON believes to be reliable and which are in compliance with technical 

knowledge of today. It is intended only for use by persons having the appropriate 
technical knowledge and skills, at their own discretion and risk. Since conditions of 
use are outside of EMERSON’s control we cannot assume any liability for results 
obtained or damages occurred due to improper application. 
This document replaces all former versions 

 
Emerson Electric GmbH & Co OHG - Postfach 1251 - Heerstraße 111  -  D-71332 Waiblingen  -  Germany  -  Phone .49-(0)7151-509-0  -  Fax .49-(0)7151-509-200 
 

www.emersonclimate.eu

 

Summary of Contents for EC2-311

Page 1: ...al limits Comply with local electrical regulations when wiring Technical Data EC2 Series Controller Power supply 24VAC 10 50 60 Hz Class II Power consumption 20VA max including EX2 Communication LonWorks Interface FTT10 RJ45 connector Plug in connector size Removable screw terminals wire size 0 14 1 5mm2 Temperature storage operating 20 65 C 0 60 C Humidity 0 80 r h non condensing Protection class...

Page 2: ...ress or to show the code of the parameter that has to be changed Press SEL to display the selected parameter value Press or to increase or decrease the value Press SEL to temporarily confirm the new value and display its code Repeat the procedure from the beginning press or to show To exit and save the new settings Press PRG to confirm the new values and exit the parameters modification procedure ...

Page 3: ... first time or temperature no alarm 3 last by time and temperature no alarm d2 Defrost termination sensor 0 1 1 0 Dedicated defrost sensor must be installed 1 Air out sensor used for defrost termination Min Max Unit Def Custom d3 Pulsed defrost 0 1 0 0 off no pulsed defrost heaters switched off at defrost termin ation temperature dt or max time dP whatever is selected 1 on pulsed defrost dd and dH...

Page 4: ... wink request is received OF Node is offline The node is offline and no application is running This is the result of a network management command and will happen for example during node installation dS Defrost standby dP Pump down dF Defrost cycle dd Defrost drain delay dI Defrost injection delay du Defrost start up delay Cn Cleaning CL Alarms are cleared Visualising Data LON Monitoring Server The...