EC2-712_65108_EN_R03.doc
Replacement for Rev.:02
2 / 4
16.09.2009
EC2-712 Condenser Controller
Operating Instructions
GB
Parameter Modification: Procedure
•
Press or to show the code of the parameter that has to be changed;
•
Press
SEL
to display the selected parameter value;
•
Press or to increase or decrease the value;
•
Press
SEL
to temporarily confirm the new value and display its code;
•
Repeat the procedure from the beginning "
press
or
to show...
"
To exit and save the new settings:
•
Press
PRG
to confirm the new values and exit the parameters modification
procedure.
To exit without modifying any parameter:
•
Do not press any button for at least 60 seconds (TIME OUT).
•
Press “
ESC
” on IR remote control.
Load Default Parameters:
The default parameter settings can be reloaded into the controller memory by using
the special function described below.
Special Functions:
The Special Functions can be activated by:
•
Press and together for more than 5 seconds, a flashing “0” is displayed.
•
Press or until the password is displayed (default = 12). If password was
changed, select the new password.
•
Press
SEL
to confirm password, a “0” is displayed and the Special Function
mode is activated.
•
Press or to select the function. The number of special functions is dynamic
and controller dependent. See list below.
•
Press
SEL
to activate the function without leaving the special function mode.
•
Press
PRG
to activate the function and leave the special function mode.
Most of the Special Functions work in a toggle mode, the first call activates the
function, and the second call deactivates the function.
The indication of the function can only be displayed after exiting the special
function mode.
•
0: Display test function
•
1: Displays the current TCP/IP address
•
2: Set the controller's TCP/IP address to 192.168.1.101 (default value). This
change is only temporary. A power down will reset the previous address
•
3: Resets all parameters to the factory default setting. The controller will
indicate “oF” during the reset and the valve will close.
Display of Data:
The data to be permanently shown on the display can be selected by the user (parameter
/1). In case of an alarm, the alarm code is displayed alternately with the selected data.
The user can inhibit the alarm code.
It is possible to temporarily display these values. This is a useful feature when
initially setting-up the system without the aid of the WebPages. Press the
SEL
button to scroll through all possible displayable data.. The display will show for one
second the numerical identifier of the data (see /1 parameter) and then the selected data.
After two minutes the display will return to the by parameter /1 selected data. This
action is only valid when parameter H2 = 3.
Ethernet activity LED
(only active when service pin is pressed)
Display indicates condenser controller
Display indicates pressure in bar
Alarm condition
Fan 3 on
IR LED
Fan 4 on
Fan 2 on
Fan 1 on
Indications on The Display:
Condenser fan controller
•
State
•
Alarm in combination with alarm message and alarm LED
•
Condensing pressure or saturation temperature from condensing pressure
•
Parameter
Other display
•
Pressure: Pressure value in bar (g)
•
Alarm: Alarm condition
•
IR: IR communication enabled
Alarm Codes
hP
High pressure alarm
Condensing pressure higher than the maximum limit
lP
Low pressure alarm
Condensing pressure lower than the minimum limit
EP
Error pressure
Condensing pressure sensor failure
Fr
Fast recovery alarm
Fast recovery form low condensing pressure
hr
High discharge pressure alarm
High condensing pressure recovery
E1
Feedback alarm 1
Digital input associated with fan 1 has changed into alarm state (safety chain)
E2
Feedback alarm 2
Digital input associated with fan 2 has changed into alarm state (safety chain)
E3
Feedback alarm 3
Digital input associated with fan 3 has changed into alarm state (safety chain)
E4
Feedback alarm 4
Digital input associated with fan 4 has changed into alarm state (safety chain)
n1
Service alarm 1
Fan 1 operating time higher than run limit
n2
Service alarm 2
Fan 2 operating time higher than run limit
n3
Service alarm 3
Fan 3 operating time higher than run limit
n4
Service alarm 4
Fan 4 operating time higher than run limit
Er
Data error
Data send to the display is out of range
Messages
---
No data to display
The display will show an “---” at node start up and when no data is send to the
display.
In
Reset to default values activated
The display will show an “In” when the factory default configuration data set
is initialized.
Id
Wink request received
The display will show a flashing “Id” when the wink request was received.
The flashing “Id” will be shown on the display until the service button will be
pressed, or a 30 min delay timer will expire or a second wink request is
received. This function is action only when using SNMP protocol
OF
Node is offline
The node is offline and no application is running. This is the result of a
network management command and will happen for example during node
installation.