Proprietary and confidential
– Do not copy or distribute without permission from Emerson Climate Technologies GmbH
25/42
Technical Information
52
Demand defrost relative delta threshold
If in configuration parameter
78 Defrost mode
a demand detection is selected, this demand is detected in
three stages. As a first stage the best cooling capability of the evaporator is measured after a defrost. If this
capability drops below a temperature difference configured in this parameter the next defrost is triggered.
Figure 18: Demand Defrost Detection
53
Demand defrost absolute delta threshold
If in configuration parameter
78 Defrost mode
a defrost mode with demand detection is selected, this
demand is detected in three stages. As a second stage a detection is triggered if the absolute temperature
difference between Air Out and Air In drops below the value configured in this parameter. If this fails, the
defrost is triggered by time
26
Defrost interval time
(final criterion).
54
Demand defrost delay
Time in seconds. The detection of the best cooling capability after a defrost termination is delayed by the time
configured in this parameter.
55
Demand defrost Delta lambda
Filter factor to lowpass the temperature difference.
56
Refrigerant
Selection of the used refrigerant.