Technical Information
66
Valve scaling
The real maximum opening of the valve can be limited by this parameter. This is necessary if the valve built in
is too big for the application. The superheating controller is working relative to this parameter in the range of
0-100%.
This function is only active if an electronic expansion valve is used.
67
Pressure difference 4-way
The minimum pressure difference to switch the four-way-valve is defined by this parameter.
This function is only available if hot-gas-defrost is configured and a suction and discharge pressure sensor is
available. If one of the pressure sensors is missing the valve is switched by time control.
68
Valve type
A thermostatic expansion valve (TXV) or an electric expansion valve (EXV) can be selected.
69
Manual mode timeout
If the controller is running in manual mode a timeout is forcing the device back into normal mode after the time
configured in this parameter.
70 + 71 Pressure sensor type
Several pressure sensor types can be selected.
72 - 77 Temperature sensor type
Several temperature sensor types can be selected.
78
Defrost mode
Four different ways of doing a defrost are configurable
Value
Defrost mode
Defrost relais in use
Fans
Compressor
0
natural
no
on
off
1
electrical
yes
off
off
2
hot-gas bypass
yes
off
on
3
hot-gas 4-way
yes
off
on
4
natural with demand
detection
no
on
off
5
electrical with demand
detection
yes
off
off
6
hot-gas bypass with demand
detection
yes
off
on
7
hot-gas 4-way with demand
detection
yes
off
on
8
electrical with fans on
yes
on
off
9
electrical with fans on and
demand detection
yes
on
off
Table 5: Defrost Modes
79
Defrost valve opening
The opening of the EXV in case of a hot-gas 4-way defrost are defined by this parameter
This function is only active if an electronic expansion valve is used.
80
Fan restart delay after defrost
An instant restart of the fans after an electrical or hot-gas defrost is delayed by this parameter, so no hot air is
blown into the cabinet.