Proprietary and confidential
– Do not copy or distribute without permission from Emerson Climate Technologies GmbH
39/42
Technical Information
9
Alarms
Alarm
No.
Alarm
bit field
Alarm description
Category
System behavior
Buzzer
Display
Relay
1
0x0001
EXV alarm
Hardware
alarm
Cooling stop (only with EXV Plug-in)
✓
E00
✓
2
0x0002
Suction pressure sensor
Hardware
alarm
Cooling stop, only active when sensor required
✓
E01
✓
3
0x0004
Suction gas temperature
sensor
Hardware
alarm
Cooling stop (only with EXV Plug-in)
✓
E02
✓
4
0x0008
Air in sensor
Hardware
alarm
Emergency operation (thermostat cycles)
✓
E03
✓
5
0x0010
Air out sensor
Hardware
alarm
Emergency operation (thermostat cycles) / Electrical
heating stop after defrost cycle finish is detected
✓
E04
✓
6
0x0020
Fin sensor
Hardware
alarm
Electrical heating stop after defrost cycle finish is
detected
✓
E05
✓
7
0x0040
Discharge pressure sensor
Hardware
alarm
Hybrid fan on
✓
E06
✓
8
0x0080
Compressor safety chain
Hardware
alarm
Cooling stop
E07
✓
9
0x0100
Discharge temperature
sensor
Hardware
alarm
Only active when sensor required
✓
E08
✓
10
0x0200
Cabinet temperature sensor
Hardware
alarm
✓
E09
✓
11
0x0400
no function
Hardware
alarm
E10
✓
12
0x0800
Low battery voltage
Hardware
alarm
E11
13
0x1000
Class B software
Hardware
alarm
Cooling stop
✓
E12
✓
14
0x2000
EEPROM
Hardware
alarm
Cooling stop
✓
E13
✓
15
0x4000
Modbus Master Jam
Hardware
alarm
E14
16
0x8000
Door Open
Hardware
alarm
17
0x0001
Low pressure
Software
alarm
Cooling stop, only active when using low pressure
transmitter
✓
E32
✓
18
0x0002
Low superheat
Software
alarm
Cooling stop
✓
E33
✓
19
0x0004
High superheat
Software
alarm
Cooling stop
✓
E34
✓
20
0x0008
High cabinet temperature
Software
alarm
✓
E35
✓
21
0x0010
Low cabinet temperature
Software
alarm
Cooling stop
✓
E36
✓
22
0x0020
Low control temperature
Software
alarm
Cooling stop
✓
E37
✓
23
0x0040
High control temperature
Software
alarm
✓
E38
✓
24
0x0080
Defrost terminated by time
Software
alarm
✓
E39
✓
25
0x0100
N/A
Software
alarm
26
0x0200
High discharge temperature
Software
alarm
Cooling stop
✓
E41
✓
27
0x0400
Timeout 100% valve
opening
Software
alarm
✓
E42
✓
28
0x0800
High condensing pressure
Software
alarm
Cooling stop / Hybrid fan on
Only active when using a high pressure sensor
✓
E43
✓
29
0x1000
Bus/gas alarm
Software
alarm
Hybrid fan on
✓
E44
✓
30
0x2000
Configuration alarm
Software
alarm
Cooling stop
E45
31
0x4000
Envelope alarm
Software
alarm
Cooling stop
E46
32
0x8000
Compressor alarm
Software
alarm
Cooling stop
E47
Table 8: Alarm Codes