Technical Information
Table 1: Connector assignment
J8
RAST2.5 3-pin socket connectors
Evaporator temperature
1 = 3.3V DC
2 = open
3 = GND
Stocko: 008
J6
RAST2.5 3-pin socket connectors
Air out temperature
1 = 3.3V DC
2 = open
3 = GND
Stocko: 009
J3
RAST2.5 3-pin socket connectors
Air in temperature
1 = 24V DC
2 = 4-20 mA
3 = GND
Stocko: 004
J20
RAST2.5 3-pin socket connectors
Display unit ECD-05
1 = +12V DC
2 = open
3 = GND
Stocko: 005
J26
RAST2.5 3-pin socket connectors
24 V/0.5 A power supply
1 = +24V DC
2 = open
3 = GND
Stocko: 007
J30
JST B6B
Electronic expansion valve (EXV)
1 = +24V DC red
2 = +24V DC brown
3 = coil 1 blue
4 = coil 1 orange
5 = coil 2 yellow
6 = coil 2 white
J25
RAST5 2-pin multipoint connector
Synchronized defrost
1 = + 8V DC
2 = GNDIS
Stocko: 050
J27
RAST5 2-pin multipoint connector
RS485 communication, Modbus Master
1 = Modbus A
2 = Modbus B
3 = Modbus GND
Stocko: 008
JP1
JP2
RJ45
RS485 communication, Inter Cabinet BUS
1 = n.c.
2 = n.c.
3 = n.c.
4 = Modbus A
5 = Modbus B
6 = n.c.
7 = n.c.
8 = Modbus GND
J3 / J4
Header rows
Optional communication interface
J7 / J8
Header rows
Optional output interface (EXM, relay)