Setting Position Limits for Electrical Operation
Quick-Start Guide
E2K-210-05-18 Rev. 3
September 2018
4
Setting Position Limits for Electrical Operation
Setting Position Limits for
Electrical
Operation
STEP 1:
CLOSED Valve Position
2
3
4
YES
LOCAL
CLOSE
Hold until
desired
position is
reached.
1
STOP
Turn the selector knob to the
“LOCAL”
position. Hold the control knob in the
“CLOSE”
position until desired
position is reached. Dis-engage motor drive by setting the declutch lever in
“HAND”
mode.
Using handwheel, move the valve in the open direction for one handwheel turn to allow for motor coasting.
Re-engage motor drive by setting the declutch lever out of
“HAND”
mode.
Return the selector knob to the “
STOP”
position. Select
“YES”
to set new close limit.