D103831X012
Instruction Manual
March 2015
8 Series
www.enardo.com
Figure 1.
8 Series High Pressure Deflagration Flame Arrestor
8 Series High Pressure Deflagration
Flame Arrestor
Table of Contents
Introduction ..................................................................1
Specifications ..............................................................2
Principle of Operation ..................................................3
Factors Affecting Flame Arrestor Performance ...........4
Installation ...................................................................5
Maintenance ................................................................7
Recommended Spare Parts ......................................10
Parts Ordering ...........................................................10
Parts List....................................................................10
WARNING
!
Failure to follow these instructions or
to properly install and maintain this
equipment could result in an explosion,
fire and/or chemical contamination
causing property damage and personal
injury or death.
Enardo high pressure deflagration flame
arrestors must be installed, operated
and maintained in accordance with
federal, state and local codes, rules
and regulations and Emerson Process
Management Regulator Technologies
Tulsa, LLC (Emerson™) instructions.
Call a qualified service person to service
the unit. Installation, operation and
maintenance procedures performed
by unqualified person may result
in improper adjustment and unsafe
operation. Either condition may result in
equipment damage or personal injury.
Only a qualified person shall install
or service the 8 Series high pressure
deflagration flame arrestor.
Introduction
Scope of the Manual
This manual provides specifications, installation
and maintenance instructions and parts ordering
information for the 8 Series high pressure
deflagration flame arrestor.
Product Description
8 Series high pressure deflagration flame arrestors is
designed to protect equipment against high velocity
and pressure flame fronts inherent in applications
beyond the performance range of a standard flame
arrestor but not yet to the detonation phase of flame
development and provide an economical alternative
to a detonation arrestor. The 8 Series high pressure
deflagration flame arrestor is designed to surpass
standard flame arrestors for applications that
include extended lengths of pipe with one bend,
elevated operating pressures and extended flame
stabilization on the flame cell element. The arrestors
are bi-directional and can stop low, medium and high