background image

8 Series

2

8

/

-

-

Deflagration  Flame 

Arrestor

Housing 

 

Size

Connection 

Size

NEC

Housing 

Material

Element 

Material

Connection 

Type

Options

E8 if eccentric 

configuration

08 = 8 in. 

through 

48 = 48 in.

02 = 2 in. 

through  

24 = 24 in.

Gas 

Group

C = Carbon Steel

4 = 304 SST

6 = 316 SST

H = Hastelloy

®

E = Exotic

4 = 304 SST

6 = 316 SST

H = Hastelloy

®

E = Exotic

F =  Flat face 

flange

R =  Raised 

face 

flange

1 = Drain Plug

2 = Pressure Tap 

3  =   Temperature 

Probe Tap

4 = Miscellaneous

5 = Protective coating

6 = Special feature

B

C

D

Figure 2. 

8 Series High Pressure Deflagration Flame Arrestor Available Constructions and Model Numbering System

Hastelloy

®

 is a mark owned by Haynes International, Inc.

Specifications 

The Specifications table lists the specifications for the 8 Series high pressure deflagration flame arrestors. 

Specification is stamped on the nameplate attached to the flame arrestor.

Available Construction

See Table 1 and Figure 2

Gas Group

B, C and D

Flange Size and Rating

2 to 24 in. / 50 to 600 mm

CL150 FF and RF 

Housing Size

8 to 48 in. / 200 to 1200 mm

1. The pressure/temperature limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded.

Temperature Rating of Gaskets

(1)

 

Fiber Gaskets 

(standard)

:

 

450°F / 232°C or higher

Pipe Length

See Table 4

Housing Material

Carbon steel, 304 Stainless steel, 

 

316 Stainless steel, Hastelloy

®

 and Exotic

Cell Material

304 Stainless steel, 316 Stainless steel 

 

and Hastelloy

®

Summary of Contents for ENARDO 8 Series

Page 1: ...dures performed by unqualified person may result in improper adjustment and unsafe operation Either condition may result in equipment damage or personal injury Only a qualified person shall install or service the 8 Series high pressure deflagration flame arrestor Introduction Scope of the Manual This manual provides specifications installation and maintenance instructions and parts ordering inform...

Page 2: ... mark owned by Haynes International Inc Specifications The Specifications table lists the specifications for the 8 Series high pressure deflagration flame arrestors Specification is stamped on the nameplate attached to the flame arrestor Available Construction See Table 1 and Figure 2 Gas Group B C and D Flange Size and Rating 2 to 24 in 50 to 600 mm CL150 FF and RF Housing Size 8 to 48 in 200 to ...

Page 3: ...signed to stop flames in the low medium and high pressure deflagration states Flame arrestor allows gas to pass though it but stops flame in order to prevent a larger fire of explosion Arrestor prevents flame by absorbing and dissipating the heat from flame as it attempts to travel through the spiral wound crimped ribbon flame cells These cells allow maximum flow with maximum protection See Figure...

Page 4: ...erify that the high pressure deflagration flame arrestor being installed has the appropriate gas group rating for your process This information is shown on the nameplate attached to the element housing Do not remove or alter this nameplate The measurement of the maximum gap between two equatorial flanges on a metal sphere that will prevent a flame from being transmitted from the sphere to the surr...

Page 5: ...e the auto ignition temperature of the process gas stream resulting in flame propagation through the arrestor See Table 3 for the endurance burn time of each gas group Pipe Lengths Extended lengths of pipe allow the flame to advance into more severe states of flame propagation such as high pressure deflagration or detonations High pressure deflagration flame arrestors should be installed in accord...

Page 6: ...Direction The Enardo high pressure deflagration flame arrestor is bi directional and can be installed either vertically or horizontally Consideration should be given to non symmetrical assemblies that include features such as clean out ports temperature monitoring device or other options that might have a preferred installation direction to suit the needs of the customer Piping Expansions and Redu...

Page 7: ... to maximize spray media penetration into the element Alternately spray each side of the element surface until clean 7 The cleaning interval should be governed by the amount and type of particulate in the system to which it is installed and must be determined by the user To determine the maintenance interval the user should check the element in the first few months of operation to find how quickly...

Page 8: ... 50 68 81608 2 1 8 Snug 25 34 50 68 75 102 82010 3 1 1 4 8 Snug 35 47 70 95 120 163 82412 4 1 1 4 8 Snug 35 47 70 95 120 163 82814 5 1 1 4 8 Snug 35 47 70 95 120 163 83016 6 1 1 4 8 Snug 35 47 70 95 120 163 83620 7 1 1 2 8 Snug 50 68 120 163 170 230 1 Using machine oil as lubricant See Bolt Lubrication section on page 9 and torque correction factors for other lubricants in Table 6 2 See Figure 4 P...

Page 9: ...e permanent damage to gaskets and housing Tools Supplies Required Hand operated conventional torque wrench or power assisted torque wrench appropriate for the specified torque Socket wrenches of the proper size to fit the hex nuts being tightened Molydisulfide based lubricating paste Molykote G n or equivalent Brush suitable for applying lubricant to the studs Wiping rags necessary for the clean u...

Page 10: ...mum downtime it is recommended that the user purchase a spare element assembly and several spare element gaskets The spare element assembly can be installed immediately and the dirty assembly can then be cleaned and be stored as a spare for the next maintenance interval Note Element gaskets should be replaced each time the cell assembly is loosened and removed to insure a gas tight seal Parts Orde...

Page 11: ...nless Steel Model Part Number 80802 80803 80804 8000903 8000922 8000901 81206 8000904 8000923 8000905 81608 8000906 8000924 8000907 82010 8000908 8000925 8000909 82412 8000910 8000926 8000911 82814 8000912 8000927 8000913 83016 8000914 8000928 8000915 83620 8000918 8000930 8000919 Table 8 Replacement Element Assemblies Part Numbers Group D Gas ...

Page 12: ... guarantees express or implied regarding the products or services described herein or their use or applicability We reserve the right to modify or improve the designs or specifications of such products at any time without notice Emerson Process Management Regulator Technologies Tulsa LLC does not assume responsibility for the selection use or maintenance of any product Responsibility for proper se...

Reviews: