DEVICE PROFILE DOCUMENT
Vendor Name: Emerson Automation Solutions
Device Name:
CPE400/CPL410, CPE115 Outstation
, using the Triangle Micro Works, Inc. DNP3 Outstation Source
Code Library, Version 3.22
Highest DNP Level Supported:
For Requests:
Level 3
For Responses:
Level 3
Device Function:
Master
Outstation
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete
list is described in the attached table):
For static (non-change-event) object requests, request qualifier codes 07 and 08 (limited quantity), and 17 and 28
(index) are supported. Static object requests sent with qualifiers 07, or 08, will be responded with qualifiers 00 or 01.
16-bit, 32-bit and Floating-Point Analog Change Events with Time may be requested.
Floating Point Analog Output Status and Output Block Objects 40 and 41 are supported.
Output Event Objects 11, 42 and 43 are supported.
Maximum Data Link Frame Size (octets):
Transmitted:
292
Received
292
Maximum Application Fragment Size (octets):
Transmitted:
2048
Received
2048
Maximum Data Link Re-tries:
Configurable, range 0 to 255
Fixed 65535
Maximum Application Layer Re-tries:
None
Configurable
Requires Data Link Layer Confirmation:
Never
Always
Sometimes
Configurable as:
Never
,
Only for multi-frame messages
, or
Always