PACSystems™ RX3i DNP3 Outstation User Manual
Section 1
GFK-3103B
June 2020
Introduction
11
1.9.2
DNP3 Outstation Static and Event Poll Support
Class 0 Poll
Yes, returns all class 0 data and any buffered event data to the
master station, also referred to as static Poll
Class 1, 2, and 3 Event Poll
Yes, returns event data format
1.9.3
Number of Points and Events Support
Table 2: Static Data Objects
Static Object
Group
Maximum Points
Maximum Points
CPE400/CPL410
CPE115
Binary Input
1
3000
1024
Binary Output Status
10
3000
1024
Binary Counters
20
3000
1024
Frozen Counters
21
3000
1024
Analog Input
30
2000
2000
Analog Output Status
40
2000
2000
Analog Deadband
34
2000
2000
Binary Command
–
Control Relay Output
Block (CROB)
12
1024
1024
Analog Output Value
41
1000
1000
Table 3: Event Data Objects
Event Object
Group
Maximum Events
Binary Input Event
2
8000*
Binary Output Event
11
8000*
Counter Event
22
8000*
Analog Input Event
32
8000*
Analog Output Event
42
8000*
Analog Output Command Event
43
8000*
*DNP3 Outstation supports maximum of 8000 events per Event Object across all the configured DNP3 Masters.