PACSystems™ RX3i DNP3 Outstation User Manual
Section 3
GFK-3103B
June 2020
DNP3 Configuration Parameters
28
Parameters
Description
Valid Values
Select
Timeout
(Sec)
Maximum amount of time that a Select
will remain valid before the
corresponding Operate command is
received from the Master.
Value: 1 to 300 Sec,
Default: 5 Sec
Clock Valid
Period
(Min)
Specifies how long the local clock will
remain valid after receiving a time
synchronization.
Refer Section 5.9
Value: 0 to 1440 Min,
Default: 30 Min
DNP3-TCP
Keep Alive
Specifies how often to send link status
requests if no DNP3 frames have been
received.
Refer Section 5.10
Value: 0 to 300 Sec
Default: 30 Sec
Link
Timeout
Disconnect
Specifies to disconnect/reconnect a
connection when link status request
times out.
Refer Section 5.10
Value: True/False, Default:
False
For CPE115 when
configured using SVC_REQ:
Value: 1 / 0.
Max
Control
Requests
Determines the maximum number of
controls (CROB/AOV) allowed in a
single write request.
Value: 1 to 10
Default: 10
DNP3 Time
–
Sync
Required
Specifies whether the DNP3 Outstation
will set the Need Time IIN bit at startup
and after the clock valid period has
elapsed.
Note: When SNTP is configured in the
CPU this parameter should be set to
False.
Refer Section 5.9
Value: True/False
Default: False
For CPE115 when
configured using SVC_REQ:
Value: 1 / 0.
Outstation
Restart Bit
Specifies if required to set Restart Bit in
IIN when DNP3 Outstation starts.
Value: True/False
Default: False
For CPE115 when
configured using SVC_REQ
:
Value: 1 / 0.
Set Default
Class Mask
None
When set to True, On DNP3 Outstation
startup (or) when CPU transition from
RUN-to-STOP/STOP-to-RUN, all the
DNP3 points Class Mask is set to None,
so that no Event Reports are generated
for change in Online/Offline status in
the point Flags.
Value: True/False
Default: False
For CPE115 when
configured using SVC_REQ:
Value: 1 / 0.
Enable
Point Push
Events Y2K
adder
Specifies whether Point Push Data
Needs a Year 2000 Adder.
If set to True, Point Push Event time
stamp year requires Year 2000 Adder;
Event time stamp year assumes 2-digit
year with an epoch of 1970.
If set to True, Point Push Event time
s
tamp doesn’t require Year 2000 adder;
Event time stamp year assumes 4-digit
year.
Value: True/False
Default: False
For CPE115 when
configured using SVC_REQ:
Value: 1 / 0.