PACSystems™ RX3i DNP3 Outstation User Manual
Section 3
GFK-3103B
June 2020
DNP3 Configuration Parameters
33
3.2
DNP3 Object Attributes
This section provides details to configure DNP3 Object Attributes:
■
General Parameters
■
Point Template Configuration
■
DI Attributes
■
DO Attributes
■
AI Attributes
■
AO Attributes
3.2.1
General Parameters
This section describes DNP3 Outstation general parameters:
Table 10: General Parameters
Parameters
Description
Digital Input
Digital Input is defined as a DNP3 Object Binary Inputs
–
Obj01.
Corresponding PLC memory type, memory address, and number of
Points are required to be configured. Set the configuration parameter
values as required by the DNP3 application.
Analog Input
Analog Input is defined as a DNP3 Object Analog Inputs
–
Obj30.
Corresponding PLC memory type, memory address, and number of
Points are required to be configured. Set the configuration parameter
values as required by the DNP3 application.
Counters
Counters is defined as a DNP3 Objects such as Binary Counters - Obj20
and Frozen Counters
–
Obj21. The number of points is same as
configured for Binary Inputs
–
Obj01. Set the configuration parameter
values as required by the DNP3 application.
Digital Output
Status
Digital Output Status is defined as a DNP3 Object Binary Output Status
–
Obj10. Corresponding PLC memory type, memory address, and number
of Points are required to be configured. Set the configuration parameter
values as required by the DNP3 application.
Digital Output
/ CROB
Digital Output is defined as a DNP3 Object Control Relay Output Block
(CROB) - Obj12 . Corresponding PLC memory type, memory address, and
number of Points are required to be configured. Set the configuration
parameter values as required by the DNP3 application.
Analog Output
Status
Analog Output Status is defined as a DNP3 Object Analog Output Status
–
Obj40. Corresponding PLC memory type, memory address, and
number of Points are required to be configured. Set the configuration
parameter values as required by the DNP3 application.
Analog Output
/ AOV
Analog Output is defined as a DNP3 Object Analog Output Value (AOV) -
Obj41. Corresponding PLC memory type, memory address, and number
of Points are required to be configured. Set the configuration parameter
values as required by the DNP3 application.
Event Modes
DNP3 Outstation Objects support following Event Modes: