PACSystems™ RX3i DNP3 Outstation User Manual
Section 3
GFK-3103B
June 2020
DNP3 Configuration Parameters
37
Parameters
Description
Valid Values
Object02 Parameters
Default Event Variation
Object02
Binary Input Event
Object02 default
Event Variation
Value:
1
–
“Event without Time”
2
–
“Event with Time”
3
–
“Event with Relative
Time”
Default: 2
“Event with
Time”
Default Event Mode
Object02
Object02 Default
Event Mode
Value:
1 - SOE
2 - MOST RECENT
Default: 2 - MOST RECENT
Default Class Mask
Object02
Object02 Default
Event Class Mask
Value:
0
–
CLASS MASK NONE
1
–
CLASS MASK ONE
2
–
CLASS MASK TWO
3
–
CLASS MASK THREE
Default: 1
–
CLASS MASK
ONE
Maximum Events
Object02
Maximum Number of
Events for Event
Object02
Value: 0 to 8000
Default: 500
Number of Point
Configurations Object02
Number of Points that
require other than
default Event Mode &
Class Mask.
For CPE115,this
parameter is not
applicable when
configured using
SVC_REQ
Value: 0 to 512
Default: 0
Enable Counter Objects20,
21, 22
Enable / Disable Binary
Counter Objects 20,
21 & 22
Value: True/False
Default: False
For CPE115 when
configured using SVC_REQ:
Value: 1 / 0.
If set to 0 Counter Objects
will be disabled.