PACSystems™ RX3i DNP3 Outstation User Manual
Section 3
GFK-3103B
June 2020
DNP3 Configuration Parameters
38
Parameters
Description
Valid Values
Default Static Variation
Object20
Binary Counter
Object20 default
Static Variation
Value:
1
–
“32
-bit with
Flag”
2
–
“16
-
bit with Flag”
5
–
“32
-
bit without Flag”
6
–
“16
-
bit without Flag”
Default: 1
–
“32
-bit with
Flag”
Default Static Variation
Object21
Binary Frozen Counter
Object21 default
Static Variation
Value:
1
–
“32
-
bit with Flag”
2
–
“16
-bit with
Flag”
5
–
“32
-bit with Flag &
Time”
6
–
“16
-bit with Flag &
Time”
9
–
“32
-
bit without Flag”
10
–
“16
-
bit without Flag”
Default: 1
–
“32
-bit with
Flag”
Default Event Variation
Object22
Binary Counter Event
Object22 default
Event Variation
Value:
1
–
“32
-b
it with Flag”
2
–
“16
-
bit with Flag”
5
–
“32
-bit with Flag &
Time”
6
–
“16
-bit with Flag &
Time”
9
–
“32
-
bit without Flag”
10
–
“16
-
bit without Flag”
Default: 1
–
“32
-bit with
Flag”
Default Event Mode
Object22
Object22 Default
Event Mode
Value:
1 - SOE
2 - MOST RECENT
Default: 2 - MOST RECENT
Default Class Mask
Object22
Object22 Event Class
Mask
Value:
0
–
CLASS MASK NONE
1
–
CLASS MASK ONE