PACSystems™ RX3i DNP3 Outstation User Manual
Section 3
GFK-3103B
June 2020
DNP3 Configuration Parameters
42
Parameters
Description
Valid Values
Number of Point
Configurations
Object11
Number of Points that
require other than default
Event Mode & Class Mask
For CPE115,this parameter
is not applicable when
configured using SVC_REQ.
Value: 0 to 512
Default: 0
Object12 Parameters
Number of Points for
Object12
Number of Points
Value: 0 to1024
Default: 0
Memory Address for
Object12
CPU Reference Memory
Type & Address
Value:
Memory Type: %I, %Q, %M, %T, %G
Allocates available reference
Memory ranges
Default: Q%00105
For CPE115 when configured using
SVC_REQ:
Memory Type: 70 - %I, 72 - %Q, 76 -
%M, 74 - %T, 86 - %G
CROB Parameters
Number of Points for
CROB
Number of CROB Points
Value: 0 to 1024 (Should be <= No.
of Obj12 Points)
Default: 0
Memory Address for
CROB
CPU Reference Memory
Type & Address
Value:
Memory Type: %R, %AI, %AQ, %W
Allocates available reference
Memory ranges
Default: %R00001
For CPE115 when configured using
SVC_REQ:
Memory Type: 8 - %R, 10 - %AI, 12 -
%AQ, 196 - %W
Start Point Offset
Start Point offset of
Object12 to be associated
with CROB Control Word
Value: 1 to No. of Obj12 Points
Default: 0