PACSystems™ RX3i DNP3 Outstation User Manual
Section 3
GFK-3103B
June 2020
DNP3 Configuration Parameters
43
3.2.5
AI Attributes
This section allows user to configure AI Polled and Events Objects configuration parameters
–
such as
Analog Input Object 30, 32, and Analog Dead Band Objects - 34.
Table 14: AI Attributes
Parameters
Description
Valid Values
AI Attributes
If Enabled, the AI
parameters get
enabled for
configuration.
If Disabled, the AI
parameters are not
allowed to be
configured.
For CPE115,this
parameter is not
applicable when
configured using
SVC_REQ.
Value: Enabled/Disabled
Default: Enabled
Object30 Parameters
Number of Points for
Object30
Number of Points
Value: 1 to 2000
Default: 100
For CPE115 when configured
using SVC_REQ:
Value: 0 to 2000
If set to 0 AI Attributes is not
available.
Memory Address for
Object30
CPU Reference
Memory Type &
Address
Value:
Memory Type: %R, %AI, %AQ,
%W
Allocates available reference
Memory ranges
Default: %AI00001
For CPE115 when configured
using SVC_REQ:
Memory Type: 8 - %R, 10 - %AI,
12 - %AQ, 196 - %W,
If set to 0 AI Attributes is not
available.