PACSystems™ RX3i DNP3 Outstation User Manual
Section 3
GFK-3103B
June 2020
DNP3 Configuration Parameters
46
3.2.6
AO Attributes
This section allows user to configure AO Polled and Events Objects configuration parameters
–
such as
Analog Output Status Object 40, 42, and Analog Outputs Objects
–
41,43.
Table 15: AO Attributes
Parameters
Description
Valid Values
AO Attributes
If Enabled, the AO
parameters gets enabled for
configuration.
If Disabled, the AO
parameters are not allowed
to be configured.
For CPE115,this parameter
is not applicable when
configured using
SVC_REQ.
Value: Enabled/Disabled
Default: Enabled
Object40 Parameters
Number of Points for
Object40
Maximum Number of Points
Value: 1 to 2000
Default: 100
For CPE115 when configured
using SVC_REQ:
Value: 0 to 2000
If set to 0 AO Attributes is not
available
Memory Address for
Object40
Memory Type & Address
Value:
Memory Type: %R, %AI, %AQ,
%W
Allocates available reference
Memory ranges
Default: %AQ00001
For CPE115 when configured
using SVC_REQ:
Memory Type: 8 - %R, 10 -
%AI, 12 - %AQ, 196 - %W
If set to 0 AO Attributes is not
available.