DNP3 Configuration Parameters
48
Parameters
Description
Valid Values
Maximum Events for
Object42
Maximum Number of
Events for this Event object
Value: 0 to 8000
Default: 500
Number of Point
Configurations Object42
Number of Points configured
with other than default Event
Mode & Class Mask that is
set.
For CPE115,this parameter is
not applicable when
configured using SVC_REQ
Value: 0 to Max. Point
configured
Default: 0
Object41 Parameters
Number of Points for
Object41
Maximum Number of Points
Value: 0 to 1000
Default: 0
Memory Address for
Object41
Memory Type & Address
Value:
Memory Type: %R, %AI, %AQ,
%W
Allocates available reference
Memory ranges
Default: %AQ00201
For CPE115 when configured
using SVC_REQ:
Memory Type: 8 - %R, 10 -
%AI, 12 - %AQ, 196 - %W
Command Variation for
Object41
Analog Output Object41
Command Variation
Value:
1
–
“32
-
bit”
2
–
“16
-
bit”
3
–
“Single
-precision, Floating
point”
Default: 1
–
“32
-
bit”
Object43 Parameters
Number of Points for
Object43
Maximum Number of
Points
Value: 0 to (Should be <= No.
of Object 41 Points)
Default: 0