PACSystems™ RX3i DNP3 Outstation User Manual
Section 3
GFK-3103B
June 2020
DNP3 Configuration Parameters
49
Parameters
Description
Valid Values
Start Point Offset
Start Point offset of
Object41 to be associated
with Analog Output
Command Event Object43
Value: 1 to No. of Obj41
Points
Default: 0
Default Event Variation for
Object43
Analog Output Command
Event Object43 Default
Event Variation
Value:
1
–
“32
-
bit without Time”
2
–
“16
-
bit without Time”
3
–
“32
-
bit with Time”
4
–
“16
-
bit with Time”
5
–
“Single
-precision, Floating
point without Time”
7
–
“Single
-precision, Floating
point with Time”
Default: 3
–
“32
-bit with
Time”
Default Event Mode for
Object43
Object43 Default Event
Mode
Value:
1
–
SOE
2 - MOST RECENT
Default: 2 - MOST RECENT
Default Class Mask for
Object43
Object43 Default Event
Class Mask
Value:
0
–
CLASS MASK NONE
1
–
CLASS MASK ONE
2
–
CLASS MASK TWO
3
–
CLASS MASK THREE
Default: 3
–
CLASS MASK
THREE
Maximum Events for
Object43
Maximum Number of
Events for this Event
Object
Value: 0 to 8000
Default: 500