PACSystems™ RX3i DNP3 Outstation User Manual
Section 5
GFK-3103B
June 2020
System Operation
66
5.8.2
Point Template Configuration
User can
use ‘
Point Template Configuration
’ parameter to set required number of template
configurations, when this parameter is set to non-zero value it populates a new properties page tab
which will allow us to do Template configuration. A maximum of 100 templates is allowed in DNP3
Outstation Configuration. In Template Configuration a range of points for selected object can be
configured to have different Event Class Mask Type and Event Mode other than the defaults configured
at object level.
Users can configure the following parameters on template basis:
1.
Object Type (Obj2, 12, 32, 42)
2.
Range of Points (Start Point Index, End Point Index)
3.
Event Mode
4.
Event Class Mask Type
For e.g. - Point Template Configuration
In this example Point Template Configuration is configured to 1 and Number of Points for Object01 are
configured to 10 with default Event Mode as MOST RECENT and default Event Class Mask Type as CLASS
MASK ONE.