PACSystems™ RX3i DNP3 Outstation User Manual
Section 3
GFK-3103B
June 2020
DNP3 Configuration Parameters
32
3.1.5
Event Scan Parameters
Table 9: Event Scan Parameters
Parameters
Description
Valid Values
Delete Oldest Event
for Session 1 to 8
Specifies if event with the earliest
Time Stamp will be deleted in Session
[x] when a new event is added to an
event queue that is full.
If set to True, event with the earliest
timestamp will be deleted in
Session[x] when a new event is added
to an event queue that is full.
If set to False, event with the latest
timestamp will be discarded in
Session[x] when a new event is added
to an event queue that is full.
Value: True/False
Default: False
Note: For CPE115
when configured
using SVC_REQ,
there is only single
parameter for this
feature, and it is
applicable for all the
configured sessions.
Data Change Scan
Period
Specifies Time interval for all Polled
DNP3 Objects to identify the change
in data to generate Events.
The internal database screens fast-
changing events with data change
Scan period.
Value: 10 to 32000
mSec
Default: 250 mSec