PACSystems™ RX3i DNP3 Outstation User Manual
Section 4
GFK-3103B
June 2020
HSB Redundancy Configuration
50
Section 4
HSB Redundancy Configuration
This section describes how to configure a CPE400/CPL410 DNP3 Outstation in HSB Redundancy
System.
Note: CPE115 does not support HSB Redundancy.
4.1
CPE400/CPL410 DNP3 Outstation HSB Redundancy
Configuration
Configure CPE400/CPL410 DNP3 Outstation in HSB Redundancy system as mentioned in section 5.1.1
of
PACSystems Hot Standby CPU Redundancy User Manual, GFK
–
2308
. In the Primary Controller under
general setting property page, enable DNP3 Outstation Protocol, and make the required parameter
setting under DNP3 General Settings and DNP3 Object Attributes tabs. Now, mirror the configuration
to secondary controller.
NOTE: Validate Source IP and Validate Source Address are both enabled by default and users cannot
disable these parameters in HSB configuration. It is mandatory to provide unique source LLA addresses
and Source IPs.
Configure the Transfer List with a reference memory address ranges provided as part of DNP3 object
settings tab under individual DI, DO, AI and AO attributes, Refer section 5.4.1.4 of
PACSystems Hot
Standby CPU Redundancy User Manual, GFK
–
2308.
It is recommended to configure the Transfer List in
Redundancy System, if transfer list is not configured with DNP3 references, the static data will not be
synchronized in the very first sweep cycle after the Role Switch.
For additional information on HSB Redundancy Configuration and Download, please refer to
PACSystems Hot Standby CPU Redundancy User Manual, GFK
–
2308
.