PACSystems™ RX3i DNP3 Outstation User Manual
Section 5
GFK-3103B
June 2020
System Operation
84
5.15
I/O Scans
The CPE400/CPL410 and CPE115 module for DNP3 data exchange does not use a specific I/O Scan Set
as defined in the PME processor Settings tab, and in the Ethernet tab for the CPE400/CPL410 and
CPE115 Module.
STOP Mode
In STOP Mode, the DNP3 Outstation will respond to Class 0, 1, 2, or 3 poll requests. The requests will be
serviced with current state data; however, the data will be marked as offline to the DNP3 Master. In
STOP Mode, CROB and Analog Output Values will return a failure to the Master Station.
RUN IO Disable
In RUN IO Disable Mode, the DNP3 Outstation will respond as documented for STOP Mode.
5.16
Alarms
DNP3 Outstation will internally log messages to the CPU log, most of these faults are not fatal, a given
fault may relate to the Ethernet interface, or may be specific to the DNP3 Outstation functionality. Fatal
and recurrent other faults should be reported to technical support.
For more information on Log Messages captured by the Station Manager, Refer to GFK-2225,
PACSystems TCP/IP Ethernet Communications Station Manager User Manual
.
Figure 28: LOG Command Display for Event Type 37