Appendix 1 Parameter Set 127
EV1000 Series General Purpose Variable Speed Drive User Manual
Group FF: Communication Parameters
Para.
Name
Range
Unit Default Modification
FF.00 Communication config
One’s place: baud rate
0: 300BPS
1: 600BPS
2: 1200BPS
3: 2400BPS
4: 4800BPS
5: 9600BPS
6: 19200BPS
7: 38400BPS
Ten’s place: data format
0: 1-8-1 format, no parity
1: 1-8-1 format, even parity check
2: 1-8-1 format, odd parity check
Hundred’s place: virtual input terminal
0: disabled
1: enabled
Thousand’s place: connection mode
0: direct connection (RS485)
1: MODEM (RS485-RS232 adapter
required)
1 0005
×
FF.01 Local address
0
~
126, 127 broadcast address
1 1
×
FF.02
Communcation time out
detect
0.0
~
1000s
0.1
0.0s
×
FF.03 Response delay
0
~
1000ms
1 5ms
×
艾默生变频器、艾默生CT高级授权代理商--广州盟雄 020-85543394 qq:2294731312