54 Chapter 5 Parameters
EV1000 Series General Purpose Variable Speed Drive User Manual
corresponding parameter is set at 33, the drive
will enter traverse mode. If the terminal is
disabled, the drive will exit traverse mode and
stay at preset frequency F6.02.
Ten’s place of F6.01: amplitude control
0: varied amplitude
The traverse amplitude changes with central
frequency. The change rate is defined in F6.04.
1: fixed amplitude
The traverse amplitude is determined by max.
frequency and F6.04.
Hundred’s place of F6.01: start/stop mode
0: start to the state before stop
1: just restart, no other requirement
Thousand’s place of F6.01: save traverse state
upon power failure
This function is valid only when the hundred place
of F6.04 is set at 0.
0: save
1: not save
Note:
You can set any of F7.00~7.04 at 34 to reset the
traverse state.
F6.02 Preset traverse
frequency
Range: 0.00Hz
~
650.0Hz
【
0.00Hz
】
F6.03 Preset traverse
frequency hold time
Range: 0.0
~
3600.0s
【
0.0s
】
F6.02 defines the frequency before entering
traverse state.
When the traverse start mode (F6.01) is set at
“auto”, F6.03 specifies the time period that the
drive run at preset traverse frequency. F6.03 is
invalid if F6.01 set at “manually start”. Please
refer to Fig. 5-36.
F6.04 Traverse
amplitude
Range: 0.0
~
50.0
%【0.0%】
Varied amplitude: AW=central frequency×F6.04
Fixed amplitude: AW=max. frequency
F0.05×F6.04
Note
:
The traverse frequency is limited by upper and lower
limit of frequency. Improper setting of the frequency
limit will result in faults.
F6.05 Step freq.
Range: 0.0
~
50.0
%
(of amplitude)
【
0.0
%】
Refer to Fig. 5-36. If it is set at 0, then there will
be no step frequency.
F6.06 Traverse cycle Range: 0.1
~
999.9s
【
10.0s
】
It defines the period of traverse operation
including rising time and falling time.
Note
:
Under traverse mode, auto Acc/Dec is not allowed,
otherwise, the traverse cycle will become abnormal.
F6.07 Rise time of
triangular wave
Range: 0
~
100.0
%【50.0%】
It defines the rising time of traverse operation that
equals to F6.06×F6.07 (s) and falling time,
F6.06×(1-F6.07) (s).Please refer to Fig. 5-36.
Note
:
You may choose S curve Acc/Dec mode during
traverse operation, which can help the running more
smoothly.
5.8 Multi-function Terminal (F7)
F7.00 Function of multi-function
terminal X1
Range: 0
~
43
【
0
】
F7.01 Function of multi-function
terminal X2
Range: 0
~
43
【
0
】
F7.02 Function of multi-function
terminal X3
Range: 0
~
43
【
0
】
F7.03 Function of multi-function
terminal X4
Range: 0
~
47
【
0
】
F7.04 Function of multi-function
terminal X5
Range: 0
~
48
【
0
】
F7.05~ F7.07
Reserved