Chapter 5 Parameters 67
EV1000 Series General Purpose Variable Speed Drive User Manual
【
100.0
%】
It is used to calibrate the error between preset or
feedback parameters and the actual ones. It has
no effect on close-loop PI regulation. the actual
speed.
5.10 Enhanced Function (F9)
F9.00 Operating
command bundled with
freq. setting method
Range: 000
~
777
【
000
】
This function defines the combination of 3
operating command and 7 frequency setting
method, so that they can be switched at the same
time.
Thou.
Hun.
Ten One
Freq. reference in panel control mode
0: No bundling
1: Digital setting1 (
and
▼
)
2: Digital setting 2 ( terminal UP/DN)
3: Digital setting 3 (serial port )
4: VCI analog input
5: CCI analog input
6: Pulse terminal input
Freq. reference in terminal control mode
0~7 : same with above
Freq. reference in serial port control mode
Reserved
▲
0~7 : same with above
7: Potentiometer
Fig. 5-55 Operating command bundled with freq.
Setting method
The reference frequency setting method is
defined by F0.00, see section 5.1 for details.
Different control modes can bundle to one
reference frequency setting method.
You may follow the methods below to change
control command and frequency setting method
simultaneously.
Method 1:Change F0.03;
Method 2: use terminal X1~X5 function No. 28
and 29.
For example:
In order to realize remote and local control, it
requires that:
①
Control modes selection: The control modes
can be selected by terminal remotely or by F0.03
locally;
②
If keypad (panel) control mode is used, press
RUN to run the drive and press STOP to stop the
drive. The preset frequency can be adjusted by
pressing
▲
and
▼
.
③
If terminal control mode is used, close FWD to
run forward and close REV to run reverse. The
preset frequency is adjusted via VCI.
④
Terminal control mode is enabled after the
drive is switched on.
Remote
Multi-function input
Terminal Xi
Local
Panel control mode
Terminal control
mode
Digital setting
mode 1
VCI input
PANEL/REMOTE
ENTER/DATA
Power on
Fig. 5-56 Local and Remote Control
To meet the above requirements,
Set F0.03=1, to select terminal control mode and
remote control is enabled after the drive is
switched on;
Set F7.00=28, and F7.01=29 to select
multi-function input terminal X1 and X2 to input
operating commands;
Set F7.08=1 to select 2-wire control mode 2. The
drive run forward when FWD is enabled, and run
reverse when REV is enabled;
Set F9.00=041, then terminal control mode is
bundled to VCI analog input, and the panel
control mode is bundled to digital setting 1.
艾默生变频器、艾默生CT高级授权代理商--广州盟雄 020-85543394 qq:2294731312