Appendix 1 Parameter Set 91
EV1000 Series General Purpose Variable Speed Drive User Manual
Group 0: Basic Operating Parameters
Para.
Name
Range
Min unit Default Modification
F0.08 Reserved
-
-
-
-
F0.09 Torque boost
0: (auto) 0.1
%~
30.0
%
0.1
%
0.0
%
○
F0.10 Acc time 1
F0.11 Dec time 1
0.1
~
3600
(default unit is second, other options refer to F9.09)
0.1
6.0s
○
F0.12 Upper limit of
freq.
F0.13
~
F0.05
0.01Hz
50.00Hz
×
F0.13 Lower limit of
freq.
0.00
~
F0.12
0.01Hz
0.00Hz
×
F0.14 V/F curve
0: user-defined V/F curve, based on F0.15
~
F0.20
1: curve1, a 2-order curve
2: curve 2, a 1.7-order curve
3: curve 3, a 1.2-order curve
1
0
×
F0.15 V/F freq. F3
F0.17
~
F0.06
0.01Hz
0.00Hz
×
F0.16 V/F voltage V3
F0.18
~
100.0
%
0.1
%
0.0
%
×
F0.17 V/F freq. F2
F0.19
~
F0.15
0.01Hz
0.00Hz
×
F0.18 V/F voltage V2
F0.20
~
F0.16
0.1
%
0.0
%
×
F0.19 V/Ffreq. F1
0.00
~
F0.17
0.01Hz
0.00Hz
×
F0.20 V/F voltage V1
0
~
F0.18
0.1
%
0.0
%
×
F0.21 Manual torque
boost cutoff point
0.0
~
50.0
%
(based on F0.06)
0.1
%
10.0
%
○
艾默生变频器、艾默生CT高级授权代理商--广州盟雄 020-85543394 qq:2294731312