background image

 

 

Operating instruction 

EXD-HP1/2 Controller with ModBus 

communication capability 

 

 

 

Emerson Climate Technologies GmbH  

www.emersonclimate.eu

 

Am Borsigturm 31 I 13507 Berlin I Germany 

Date: 08.09.2017 

EXD-HP12_OI_ML_R03_865921.docx 

G e n e r a l   i n f o r m a t i o n :  

EXD-HP1/2 are stand-alone superheat and or economizer controllers. EXD-HP1 is 
intended for operation of one EXM/EXL  valve whereas EXD-HP2 is designed for 
operation of two independent EXM/EXL valves.  

Note: It is possible to use only circuit 1 from EXD-HP2. In this case, the circuit 
2 must be disabled (C2 parameter) and the sensors and the valve for the second 
circuit are not needed.  
ModBus communication is described in a Technical Bulletin and it is not covered 
by this document. 

T e c h n i c a l   D a t a :  

Power supply 

24VAC/DC ±10%; 1A 

Power consumption 

EXD-HP1: 15VA          EXD-HP2: 20VA 

Plug-in connector 

Removable screw terminals wire size 0.14...1.5 mm

2

 

Protection class 

IP20 

Digital Inputs 

Potential free contacts (free from voltage) 

Temperature sensors 

ECP-P30 

Pressure sensors 

PT5 

Operating/surrounding temp. 

0…+55°C 

Output alarm relay 

SPDT contact 24V AC 1 A inductive load; 
24V AC/DC 4 A resistive load 

Activated/energized:  During normal operation (no alarm condition) 

Deactivated/de-energized:  During alarm condition or power supply is OFF 

Stepper motor output 

Coil: EXM-125/EXL-125  
Valves: EXM/EXL-… 

Mounting:  

For standard DIN rail 

Marking 

,  

Dimensions (mm)

 

 

  S a f e t y   i n s t r u c t i o n s :  

 

Read operating instructions thoroughly. Failure to comply can result in device 
failure, system damage or personal injury. 

 

It is intended for use by persons having the appropriate knowledge and skill. 

 

Before installation or service disconnect all voltages from system and device. 

 

Do not operate system before all cable connections are completed. 

 

Do not apply voltage to the controller before completion of wiring. 

 

Entire electrical connections have to comply with local regulations. 

 

Inputs are not isolated, potential free contacts needed to be used. 

 

Disposal: Electrical and electronic waste must NOT be disposed of with other 
commercial waste. Instead, it is the user responsibility to pass it to a designated 
collection point for the safe recycling of Waste Electrical and Electronic 
Equipment (WEEE directive 2012/19/EU).  For further information, contact 
your local environmental recycling center. 

E l e c t r i c a l   c o n n e c t i o n   a n d   w i r i n g :  
•  Refer to the electrical wiring diagram for electrical connections. 
•  Note:  Keep controller and sensor wiring well separated from supply power 

cables. Minimum recommended distance 30 mm. 

• 

EXM-125 / EXL-125 coils are supplied with fix cable and JST terminal block at 
cable end. Cut the wires close to terminal block. Remove the wire insulation 
approximately 7 mm at the end. It is recommended that the wires end to be 
equipped with core cable ends or metallic protective sleeve. 

When connecting the 

wires of EXM/EXL consider the color coding as follows:

 

EXD 

Terminal 

EXM/L-125 wire color 

EXD-HP1 

6  

BR 

7  

BL 

8  

OR 

9  

YE 

10 

WH

 

Brown 

Blue 

Orange 
Yellow 

White 

EXD-HP2 

30 

BR 

31 

BL 

32 

OR 

33 

YE 

34 

WH

 

Brown 

Blue 

Orange 
Yellow 

White 

 

The digital input DI1 (EXD-HP1) and DI1/D12 (EXD-HP1/2) are the 
interfaces between EXD-HP1/2 and upper level system controller if the 
Modbus communication has not been used. The external digital shall be 
operated in function system’s compressor/demand.

  

 

If the output relays are not utilized, the user must ensure appropriate safety 
precautions are in place to protect the system. 

Operating condition 

Digital input status 

Compressor starts/run 

closed (Start)  

Compressor stops 

open (Stop) 

Note:  Connecting any EXD-HP1/2 inputs to the supply voltage will 
permanently damage the EXD-HP1/2. 

 

W i r i n g   b a s e   b o a r d   ( E X D - H P 1 / 2 ) :  

 

 

Note:  

 

Base board is for function of superheat control or Economizer control. 

 

Alarm relay, dry contact. Relay coil is not energized during alarm condition or 
power off. 

 

Hot gas discharge sensor input is mandatory only for economizer control function. 

Warning: Use a class II category transformer for 24VAC power supply. Do 

not ground the 24VAC lines. We recommend using individual transformers for 
EXD-HP1/2 controller and for third party controllers to avoid possible 
interference or grounding problems in the power supply.  
 

 

Summary of Contents for EXD-HP1/2

Page 1: ... waste must NOT be disposed of with other commercial waste Instead it is the user responsibility to pass it to a designated collection point for the safe recycling of Waste Electrical and Electronic Equipment WEEE directive 2012 19 EU For further information contact your local environmental recycling center E l ec tri ca l c o nne c tio n a nd w ir i ng Refer to the electrical wiring diagram for e...

Page 2: ...meter value Press or to increase or decrease the value Press to temporarily confirm the new value and display its code Repeat the procedure from the beginning press or to show To exit and save the new settings Press to confirm the new values and exit the parameters modification procedure To exit without modifying saving any parameters Do not press any button for at least 60 seconds TIME OUT Reset ...

Page 3: ...30 6 6 1u2 MOP function 0 1 1 0 disable 1 enable 1u3 MOP set point C saturation temperature Factory setting according to selected refrigerant u0 13 C for R22 15 C for R134 R407C R410A R32 R290 Min Max settings dependent on selected type of refrigerant 1P9 Low pressure alarm mode circuit1 0 2 0 0 disabled 1 enabled auto reset 2 enabled manual reset 1PA Low pressure alarm cut out circuit1 0 8 17 7 0...

Page 4: ...ally into the new controller memory The doL message appears followed by a End message for 5 seconds The new controller with new loaded parameters setting will start to operate after End message disappears Remove the key Note If the Err message is displayed for failed programming repeat the above procedure E r ro r Ala r m ha ndl i ng Alarm code Description Related parameter Alarm relay Valve What ...

Page 5: ...hen Anschluss sind die länderspezifischen Vorschriften einzuhalten Digitaleingänge sind spannungsbehaftet nur potentialfreie Schaltkontakte verwenden Entsorgung Elektro und Elektronik Altgeräte dürfen nicht mit anderem Gewerbemüll entsorgt werden Stattdessen ist es in der Verantwortung Benutzer es zu einem Sammelpunkt für die sichere Entsorgung von Elektro und Elektronik Altgeräte WEEE Richtlinie ...

Page 6: ...geschützt Das werksseitig eingestellte Passwort ist 12 Taste länger als 5 Sek gedrückt halten eine blinkende 0 erscheint oder Taste drücken bis Passwort Standardwert 12 angezeigt wird drücken Passwort wird bestätig oder Taste drücken bis der gewünschte Parameter erscheint drücken der aktuell eingestellte Wert wird angezeigt oder Taste drücken der Wert wird vergrößert oder verkleinert drücken der e...

Page 7: ...Start 10 100 20 1u9 Dauer der Ventilöffnung bei Start sec 1 30 5 1uL Alarm bei kleiner Überhitzung 0 2 1 0 aus für überfluteten Verdampfer 1 ein mit automatischer Rückstellung 2 ein mit manueller Rückstellung 1u5 Überhitzung Sollwert K wenn 1uL ein autom or manuell wenn 1uL aus 3 0 5 30 30 6 6 Code Parameter Beschreibung und Auswahl Min Max Werk 1u2 MOP Funktion 0 1 1 0 aus 1 ein 1u3 MOP Sollwert ...

Page 8: ...Am neuen Regler Versorgungsspannung ausschalten Kopierschlüssel mit den Daten des Referenzreglers einstecken dann Versorgungsspannung einschalten Die gespeicherten Daten werden automatisch in den Speicher des neuen Reglers übertragen Auf der Anzeige erscheint die Meldung doL danach 5 Sekunden lang End Nach Erlöschen der End Meldung startet der neue Regler Kopierschlüssel entfernen Hinweis Falls di...

Page 9: ...уживанием отсоедините от системы и всех её устройств напряжение питания Не запускайте систему до полного подключения всех кабелей Не подавать напряжения на контроллер до завершения электроподключения Электрические подключения необходимо производить в соответствии с законодательством Вашей страны Входы не изолированы необходимо использовать сухие контакты Утилизация Электронные и электрические отхо...

Page 10: ...новлены только когда цифровой вход DI1 DI2 выключен открыт в то время как питание включено 24 В Эта особенность нужна для дополнительной безопасности чтобы предовратить случайное повреждение компрессоров и других компонентов системы Как только главные параметры выбраны сохранены EXD HP1 2 готов к пуску Все другие параметры могут быть изменены в любое время в процессе эксплуатации по необходимости ...

Page 11: ...араметров и выборов Мин Макс Уставка завода H5 Пароль 1 1999 12 Adr ModBus адрес 1 127 1 br Modbus скорость в бодах 0 1 1 PAr Modbus четность 0 1 0 C2 Контур 2 EXD HP2 состояние 0 1 0 0 Включен 1 Отключен uC Перевод единиц 0 1 0 0 C K bar 1 F psig HP Режим отображения 0 2 1 EXD HP1 0 не отобр 1 отобр EXD HP2 0 не отобр 1 контур 1 2 контур 2 Параметры контура 1 1uE Функция Когда DI1 выкл 0 1 1 0 Пе...

Page 12: ...ные параметры с ключа на другие контроллеры Выключите питание второго контроллера Вставьте загруженный ключ с сохранёнными данными с первого контроллера во второй контроллер и включите его питание Сохранённые параметры на ключе будут загружены автоматически в память второго контроллера появится сообщение doL за ним через 5 секунд сообщение End Второй контроллер заработает с новыми загруженными пар...

Reviews: