background image

 

 

Operating instruction 

EXD-HP1/2 Controller with ModBus 

communication capability 

 

 

 

Emerson Climate Technologies GmbH  

www.emersonclimate.eu

 

Am Borsigturm 31 I 13507 Berlin I Germany 

Date: 08.09.2017 

EXD-HP12_OI_ML_R03_865921.docx 

W i r i n g :   U p p e r   b o a r d   ( E X D - H P 2 ) :  

 

 

Note: 

 

Upper board is only for function of superheat control. 

 

Upper board does not need to be wired if the circuit 2 is disabled. 
 

P r e p a r a t i o n   f o r   S t a r t - u p :  

 

Vacuum the entire refrigeration circuit. 

 

  Warning:  Electrical Control Valves  EXM/EXL  are delivered partially 

open position. Do not charge system with refrigerant before closure of valve. 

 

Apply supply voltage 24V to EXD-HP1/2 while the digital input (DI1/DI2) is 
OFF(open). The valve will be driven to close position. 

 

After closure of valve, start to charge the system with refrigerant. 

S e t u p   o f   p a r a m e t e r s :  
(need to be checked/modified before start-up) 

 

Make sure that digital input (DI1/DI2) is off (open). Turn the power supply ON. 

 

Four main parameters Password (H5), type of function (1uE), refrigerant type 
(1u0/2u0) and pressure sensor type (1uP/2uP) can be set only when digital input 
DI1/DI2 is off (open) while the power supply is ON (24V). This feature is for added 
safety to prevent accidental damage of compressors and other system components. 

 

Once the main parameters have been selected/saved the EXD-HP1/2 is ready for 
startup. All other parameters can be modified at any time during operation or 
standby if it is necessary. 

D i s p l a y / k e y p a d   u n i t   ( L E D s   a n d   b u t t o n   f u n c t i o n s ) :  
 
 
 

          

 

 
 
 
 
 

P r o c e d u r e   f o r   p a r a m e t e r   m o d i f i c a t i o n :  

The parameters can be accessed via the 4-button keypad. The configuration 
parameters are protected by a numerical password. The default password is “12”. To 
select the parameter configuration: 

 

Press the 

 button for more than 5 seconds, A flashing “0” is displayed 

 

Press 

 until “12” is displayed; (password) 

 

Press 

 to confirm password 

 

Press 

or 

 to show the code of the parameter that has to be changed 

 

Press

 

 to display the selected parameter value 

 

Press 

or 

 to increase or decrease the value 

 

Press 

 to temporarily confirm the new value and display its code 

 

Repeat the procedure from the beginning "press 

or 

 to show..." 

To exit and save the new settings

 

Press 

  to confirm the new values and exit the parameters modification 

procedure. 

To exit without modifying/saving any parameters:  

 

Do not press any button for at least 60 seconds (TIME OUT). 

Reset all parameters to factory setting: 

 

Make sure that digital input (DI1/DI2) is Off (open). 

 

Press 

 and 

 together for more than 5 seconds. 

 

A flashing “0” is displayed. 

 

Press 

or 

 until the password is displayed (Factory setting = 12).  

 

If password was changed, select the new password. 

 

Press 

 to confirm password 

 

Factory setting are applied 

Note: In standard mode the actual superheat is shown at the display. In case of liquid 
injection and economizer function this changes to discharge temperature. 

 

To display other data of circuit 1 of EXD-HP1/2 or 2 of EXD-HP2:  

– 

Press 

 and 

 together for 3 seconds to show data of circuit 1 

– 

Press 

 and 

 together for 3 seconds to show data of circuit 2 

 

To display data of each circuit: Press the 

  button for 1 second until index 

number according to the below table appears. Release the 

 

button and the next 

variable data will appears. By repeating above procedure, variable data can be 

displayed in a sequence as Measured superheat (K) → Measured suction pressure 

(bar)  →  Valve  position  (%)  →  Measured  suction  gas  temperature  (°C)  → 
Calculated saturated temperature (°C) 

→ Measured discharge temperature (°C) (if 

economizer function is selected) 

→ REPEATING…. 

Variable data 

Circuit 1 (EXD-HP1/2) 

Circuit 2 (EXD-HP2) 

Default Superheat K 

1                 0 

2                 0 

Suction pressure bar 

1                 1 

2                 1 

Valve position % 

1                 2 

2                 2 

Suction gas temp C. 

1                 3 

2                 3 

Saturation temp. °C 

1                 4 

2                 4 

Discharge temp. °C 

1                 5 

-

 

Note 1: Discharge temp. is available only if economizer function is selected. 
Note 2: After 30 minutes, display reverts to index 0. 

Blinking:

 valve is closing 

ON:

 valve is fully close 

Blinking:

 valve is opening 

ON:

 valve is fully open 

ON

: alarm 

OFF: no alarm 

Parameters setting/saving 

Selecting/ 

confirming 

Next parameter/ 
value (higher) 

Next parameter/ 
value (lower) 

ON

: Data display 

Circuit 1 

ON

: ModBus 

communication 

ON

: Data display 

Circuit 2 

Summary of Contents for EXD-HP1/2

Page 1: ... waste must NOT be disposed of with other commercial waste Instead it is the user responsibility to pass it to a designated collection point for the safe recycling of Waste Electrical and Electronic Equipment WEEE directive 2012 19 EU For further information contact your local environmental recycling center E l ec tri ca l c o nne c tio n a nd w ir i ng Refer to the electrical wiring diagram for e...

Page 2: ...meter value Press or to increase or decrease the value Press to temporarily confirm the new value and display its code Repeat the procedure from the beginning press or to show To exit and save the new settings Press to confirm the new values and exit the parameters modification procedure To exit without modifying saving any parameters Do not press any button for at least 60 seconds TIME OUT Reset ...

Page 3: ...30 6 6 1u2 MOP function 0 1 1 0 disable 1 enable 1u3 MOP set point C saturation temperature Factory setting according to selected refrigerant u0 13 C for R22 15 C for R134 R407C R410A R32 R290 Min Max settings dependent on selected type of refrigerant 1P9 Low pressure alarm mode circuit1 0 2 0 0 disabled 1 enabled auto reset 2 enabled manual reset 1PA Low pressure alarm cut out circuit1 0 8 17 7 0...

Page 4: ...ally into the new controller memory The doL message appears followed by a End message for 5 seconds The new controller with new loaded parameters setting will start to operate after End message disappears Remove the key Note If the Err message is displayed for failed programming repeat the above procedure E r ro r Ala r m ha ndl i ng Alarm code Description Related parameter Alarm relay Valve What ...

Page 5: ...hen Anschluss sind die länderspezifischen Vorschriften einzuhalten Digitaleingänge sind spannungsbehaftet nur potentialfreie Schaltkontakte verwenden Entsorgung Elektro und Elektronik Altgeräte dürfen nicht mit anderem Gewerbemüll entsorgt werden Stattdessen ist es in der Verantwortung Benutzer es zu einem Sammelpunkt für die sichere Entsorgung von Elektro und Elektronik Altgeräte WEEE Richtlinie ...

Page 6: ...geschützt Das werksseitig eingestellte Passwort ist 12 Taste länger als 5 Sek gedrückt halten eine blinkende 0 erscheint oder Taste drücken bis Passwort Standardwert 12 angezeigt wird drücken Passwort wird bestätig oder Taste drücken bis der gewünschte Parameter erscheint drücken der aktuell eingestellte Wert wird angezeigt oder Taste drücken der Wert wird vergrößert oder verkleinert drücken der e...

Page 7: ...Start 10 100 20 1u9 Dauer der Ventilöffnung bei Start sec 1 30 5 1uL Alarm bei kleiner Überhitzung 0 2 1 0 aus für überfluteten Verdampfer 1 ein mit automatischer Rückstellung 2 ein mit manueller Rückstellung 1u5 Überhitzung Sollwert K wenn 1uL ein autom or manuell wenn 1uL aus 3 0 5 30 30 6 6 Code Parameter Beschreibung und Auswahl Min Max Werk 1u2 MOP Funktion 0 1 1 0 aus 1 ein 1u3 MOP Sollwert ...

Page 8: ...Am neuen Regler Versorgungsspannung ausschalten Kopierschlüssel mit den Daten des Referenzreglers einstecken dann Versorgungsspannung einschalten Die gespeicherten Daten werden automatisch in den Speicher des neuen Reglers übertragen Auf der Anzeige erscheint die Meldung doL danach 5 Sekunden lang End Nach Erlöschen der End Meldung startet der neue Regler Kopierschlüssel entfernen Hinweis Falls di...

Page 9: ...уживанием отсоедините от системы и всех её устройств напряжение питания Не запускайте систему до полного подключения всех кабелей Не подавать напряжения на контроллер до завершения электроподключения Электрические подключения необходимо производить в соответствии с законодательством Вашей страны Входы не изолированы необходимо использовать сухие контакты Утилизация Электронные и электрические отхо...

Page 10: ...новлены только когда цифровой вход DI1 DI2 выключен открыт в то время как питание включено 24 В Эта особенность нужна для дополнительной безопасности чтобы предовратить случайное повреждение компрессоров и других компонентов системы Как только главные параметры выбраны сохранены EXD HP1 2 готов к пуску Все другие параметры могут быть изменены в любое время в процессе эксплуатации по необходимости ...

Page 11: ...араметров и выборов Мин Макс Уставка завода H5 Пароль 1 1999 12 Adr ModBus адрес 1 127 1 br Modbus скорость в бодах 0 1 1 PAr Modbus четность 0 1 0 C2 Контур 2 EXD HP2 состояние 0 1 0 0 Включен 1 Отключен uC Перевод единиц 0 1 0 0 C K bar 1 F psig HP Режим отображения 0 2 1 EXD HP1 0 не отобр 1 отобр EXD HP2 0 не отобр 1 контур 1 2 контур 2 Параметры контура 1 1uE Функция Когда DI1 выкл 0 1 1 0 Пе...

Page 12: ...ные параметры с ключа на другие контроллеры Выключите питание второго контроллера Вставьте загруженный ключ с сохранёнными данными с первого контроллера во второй контроллер и включите его питание Сохранённые параметры на ключе будут загружены автоматически в память второго контроллера появится сообщение doL за ним через 5 секунд сообщение End Второй контроллер заработает с новыми загруженными пар...

Reviews: