Operating instruction 

EXD-HP1/2 Controller with ModBus 

communication capability 

 

 

 

Emerson Climate Technologies GmbH  

www.emersonclimate.eu

 

Am Borsigturm 31 I 13507 Berlin I Germany 

Date: 08.09.2017 

EXD-HP12_OI_ML_R03_865921.docx 

 

Code 

Parameter description and choices 

Min 

Max 

Factory 

setting 

2Pd 

Low pressure alarm cut-in (bar) circuit 2 

0.5 

18 

0.5 

2P4 

Freeze protection alarm function  

0 = disable,   

 

1 = enable auto-reset,  
2 = enable manual reset 

2P2 

Freeze alarm cut-out circuit2 

-20 

2P5 

Freeze protection alarm delay, sec. 

199 

30 

2P- 

Superheat control circuit2  
(Kp factor), fixed PID 

Display 1/10K

 

0.1 

10 

1.0 

2i- 

Superheat control circuit2 (Ti factor),  
fixed PID 

350 

100 

2d- 

Superheat control circuit2 (Td factor),  
fixed PID 

Display 1/10K

 

0.1 

30 

3.0 

2uH 

High superheat alarm mode circuit 2 

2uA 

High superheat alarm setpoint (K) circuit 2 

16 

40 

30 

2ud 

High superheat alarm delay (Min) circuit 2 

15 

 

C o n t r o l   ( v a l v e )   s t a r t - u p   b e h a v i o r :    
(Parameter 1uu/2uu and 1u9/2u9) 

 
 
 

1uu/2uu: 
Min.:      10%  (<1 sec.) 
Default: 20% (< 1.5 sec.) 
Max.:     100% (< 6 sec.) 

 

 

 

U p l o a d / d o w n l o a d   K e y :   F u n c t i o n  

 

For serial production of systems/units, upload/download key allows the 
transmission of configured parameters among range of identical systems. 

U p l o a d i n g   p r o c e d u r e :    
(storing configured parameters in key) 

 

Insert the key while the first (reference) controller is ON and press 

 

button; 

the “

uPL

” message appears followed by “

End

” message for 5 seconds. 

 

Note: If the “

Err

” message is displayed for failed programming, repeat the above 

procedure. 

D o w n l o a d i n g   p r o c e d u r e :  
(configured parameters from key to other controllers) 

 

Turn off power to new controller 

 

Insert a loaded Key (with stored data from reference controller) into new controller 
and turn on the power supply. 

 

The stored parameters of the key will be downloaded automatically into the new 
controller memory; The “

doL

” message appears followed by a “

End

” message for 

5 seconds. 

 

The new controller with new loaded parameters setting will start to operate after 

End

” message disappears. 

 

Remove the key. 

 

Note: If the “

Err

” message is displayed for failed programming, repeat the above 

procedure. 

 

 

 
 
 

 

E r r o r / A l a r m   h a n d l i n g  

Alarm 
code 

Description 

Related 
parameter 

Alarm 
relay 

Valve 

What to do? 

Requires manual reset 
after resolving alarm 

1E0/2E0

 

Pressure sensor 1/2 error 

Triggered  Fully close  Check wiring connection and measure the signal 4 to 20 mA 

No 

1E1/2E0

 

Temperature sensor 1/2 error 

Triggered  Fully close  Check wiring connection and measure the resistance of sensor 

No 

1Ed

 

Discharge hot gas 
temperature sensor 3 error 

Triggered 

Operating  Check wiring connection and measure the resistance of sensor 

No 

1AΠ/2AΠ

 

EXM/EXL electrical 
connection error 

Triggered 

Check wiring connection and measure the resistance of winding 

No 

1Ad 

Discharge hot gas 
temperature above limit 

 

Triggered 

Operating 

Check valve opening/ check liquid flow for flash gas free/check 
discharge hot gas temperature sensor 

No 

AF

 

Freeze protection 

1P4/2P4: 1  Triggered  Fully close  Check the system for cause of low pressure such as insufficient 

load on evaporator 

No 

AF blinking

 

1P4/2P4: 2  Triggered  Fully close 

Yes 

AL

 

Low superheat  
(<0,5K) 

1uL/2uL: 1  Triggered  Fully close 

Check wiring connection and operation of valve 

No 

AL blinking

 

1uL/2uL: 2  Triggered  Fully close 

Yes 

AH 

High superheat 

1uH/2uH: 1  Triggered 

Operating  Check the system 

No 

AP

 

Low pressure 

1P9/2P9: 1  Triggered 

Operating  Check the system for cause of low pressure such as refrigerant 

loss 

No 

AP blinking

 

1P9/2P9: 2  Triggered 

Operating 

Yes 

Err 

Failed 
uploading/downloading 

Repeat again the procedure for uploading/downloading 

No 

Note: When multiple alarms occur, the highest priority alarm is displayed until being cleared, then the next highest alarm is displayed until all alarms are cleared. Only then will 
parameters be shown again. 
 

Summary of Contents for EXD-HP1/2

Page 1: ... waste must NOT be disposed of with other commercial waste Instead it is the user responsibility to pass it to a designated collection point for the safe recycling of Waste Electrical and Electronic Equipment WEEE directive 2012 19 EU For further information contact your local environmental recycling center E l ec tri ca l c o nne c tio n a nd w ir i ng Refer to the electrical wiring diagram for e...

Page 2: ...meter value Press or to increase or decrease the value Press to temporarily confirm the new value and display its code Repeat the procedure from the beginning press or to show To exit and save the new settings Press to confirm the new values and exit the parameters modification procedure To exit without modifying saving any parameters Do not press any button for at least 60 seconds TIME OUT Reset ...

Page 3: ...30 6 6 1u2 MOP function 0 1 1 0 disable 1 enable 1u3 MOP set point C saturation temperature Factory setting according to selected refrigerant u0 13 C for R22 15 C for R134 R407C R410A R32 R290 Min Max settings dependent on selected type of refrigerant 1P9 Low pressure alarm mode circuit1 0 2 0 0 disabled 1 enabled auto reset 2 enabled manual reset 1PA Low pressure alarm cut out circuit1 0 8 17 7 0...

Page 4: ...ally into the new controller memory The doL message appears followed by a End message for 5 seconds The new controller with new loaded parameters setting will start to operate after End message disappears Remove the key Note If the Err message is displayed for failed programming repeat the above procedure E r ro r Ala r m ha ndl i ng Alarm code Description Related parameter Alarm relay Valve What ...

Page 5: ...hen Anschluss sind die länderspezifischen Vorschriften einzuhalten Digitaleingänge sind spannungsbehaftet nur potentialfreie Schaltkontakte verwenden Entsorgung Elektro und Elektronik Altgeräte dürfen nicht mit anderem Gewerbemüll entsorgt werden Stattdessen ist es in der Verantwortung Benutzer es zu einem Sammelpunkt für die sichere Entsorgung von Elektro und Elektronik Altgeräte WEEE Richtlinie ...

Page 6: ...geschützt Das werksseitig eingestellte Passwort ist 12 Taste länger als 5 Sek gedrückt halten eine blinkende 0 erscheint oder Taste drücken bis Passwort Standardwert 12 angezeigt wird drücken Passwort wird bestätig oder Taste drücken bis der gewünschte Parameter erscheint drücken der aktuell eingestellte Wert wird angezeigt oder Taste drücken der Wert wird vergrößert oder verkleinert drücken der e...

Page 7: ...Start 10 100 20 1u9 Dauer der Ventilöffnung bei Start sec 1 30 5 1uL Alarm bei kleiner Überhitzung 0 2 1 0 aus für überfluteten Verdampfer 1 ein mit automatischer Rückstellung 2 ein mit manueller Rückstellung 1u5 Überhitzung Sollwert K wenn 1uL ein autom or manuell wenn 1uL aus 3 0 5 30 30 6 6 Code Parameter Beschreibung und Auswahl Min Max Werk 1u2 MOP Funktion 0 1 1 0 aus 1 ein 1u3 MOP Sollwert ...

Page 8: ...Am neuen Regler Versorgungsspannung ausschalten Kopierschlüssel mit den Daten des Referenzreglers einstecken dann Versorgungsspannung einschalten Die gespeicherten Daten werden automatisch in den Speicher des neuen Reglers übertragen Auf der Anzeige erscheint die Meldung doL danach 5 Sekunden lang End Nach Erlöschen der End Meldung startet der neue Regler Kopierschlüssel entfernen Hinweis Falls di...

Page 9: ...уживанием отсоедините от системы и всех её устройств напряжение питания Не запускайте систему до полного подключения всех кабелей Не подавать напряжения на контроллер до завершения электроподключения Электрические подключения необходимо производить в соответствии с законодательством Вашей страны Входы не изолированы необходимо использовать сухие контакты Утилизация Электронные и электрические отхо...

Page 10: ...новлены только когда цифровой вход DI1 DI2 выключен открыт в то время как питание включено 24 В Эта особенность нужна для дополнительной безопасности чтобы предовратить случайное повреждение компрессоров и других компонентов системы Как только главные параметры выбраны сохранены EXD HP1 2 готов к пуску Все другие параметры могут быть изменены в любое время в процессе эксплуатации по необходимости ...

Page 11: ...араметров и выборов Мин Макс Уставка завода H5 Пароль 1 1999 12 Adr ModBus адрес 1 127 1 br Modbus скорость в бодах 0 1 1 PAr Modbus четность 0 1 0 C2 Контур 2 EXD HP2 состояние 0 1 0 0 Включен 1 Отключен uC Перевод единиц 0 1 0 0 C K bar 1 F psig HP Режим отображения 0 2 1 EXD HP1 0 не отобр 1 отобр EXD HP2 0 не отобр 1 контур 1 2 контур 2 Параметры контура 1 1uE Функция Когда DI1 выкл 0 1 1 0 Пе...

Page 12: ...ные параметры с ключа на другие контроллеры Выключите питание второго контроллера Вставьте загруженный ключ с сохранёнными данными с первого контроллера во второй контроллер и включите его питание Сохранённые параметры на ключе будут загружены автоматически в память второго контроллера появится сообщение doL за ним через 5 секунд сообщение End Второй контроллер заработает с новыми загруженными пар...

Reviews: