D100341XUS2
Installation Guide
English – August 2012
Type 1301
www.fisherregulators.com
Introduction
This installation guide provides instructions for
installation, startup, and adjustment. To receive a copy
of the instruction manual, contact your local Sales
Office or view a copy at www.fisherregulators.com. For
further information refer to: Types 1301F and 1301G
Instruction Manual (Form 1111, D100341X012).
P.E.D. Categories
This product may be used as a safety accessory
with pressure equipment in the following Pressure
Equipment Directive 97/23/EC categories. It may
also be used outside of the Pressure Equipment
Directive using sound engineering practice (SEP)
per table below.
Installation
!
WARNING
Only qualified personnel should install
or service a regulator. Regulators
should be installed, operated, and
maintained in accordance with
international and applicable codes and
regulations, and Fisher
®
instructions.
If the regulator vents fluid or a leak
develops in the system, it indicates that
service is required. Failure to take the
regulator out of service immediately may
create a hazardous condition.
Personal injury, equipment damage, or
leakage due to escaping fluid or bursting
of pressure-containing parts may result
if this regulator is overpressured or
is installed where service conditions
could exceed the limits given in the
Specifications section, or where
conditions exceed any ratings of the
adjacent piping or piping connections.
To avoid such injury or damage,
provide pressure-relieving or
pressure-limiting devices (as required
by the appropriate code, regulation,
or standard) to prevent service
conditions from exceeding limits.
Additionally, physical damage to the
regulator could result in personal injury
and property damage due to escaping
fluid. To avoid such injury and damage,
install the regulator in a safe location.
Clean out all pipelines before installation of the
regulator and check to be sure the regulator has
not been damaged or has collected foreign material
during shipping. For NPT bodies, apply pipe
compound to the external pipe threads. For flanged
bodies, use suitable line gaskets and approved
piping and bolting practices. Install the regulator
in any position desired, unless otherwise specified,
but be sure flow through the body is in the direction
indicated by the markings on the body.
PRODUCT SIZE
CATEGORY
FLUID TYPE
1/4 NPT
SEP
1
1.
The pressure/temperature limits in this Installation Guide and any applicable standard or code limitation should not be exceeded.
Specifications
Body Size and End Connection Styles
NPS 1/4, NPT screwed (one inlet and two or
three outlet connections)
Maximum Allowable Inlet Pressure
(1)
414 bar / 6000 psig
Outlet Pressure Ranges
(1)
Type 1301F
: 0.69 to 5.2 bar / 10 to 75 psig,
3.4 to 10.3 bar / 50 to 150 psig, and 6.9 to 15.5
bar / 100 to 225 psig
Type 1301G
: 13.8 to 34.5 bar / 200 to 500 psig
Maximum Emergency Outlet Pressure
(1)
Type 1301F
: 17.2 bar / 250 psig
Type 1301G
: 37.9 bar / 550 psig
Proof Test Pressure
All Pressure Retaining Components have been
proof tested per Directive 97/23/EC - Annex 1,
Section 7.4.
Temperature Capabilities
(1)
Nylon (PA) Valve Disks: -29 to 82°C /
-20 to 180°F
PTFE Valve Disks: -29 to 204°C / -20 to 400°F