Instruction Manual
D200149X012
3610J and 3620J Positioners
September 2017
9
ATEX
Standards Used for Certification
EN 60079-0: 2012
EN 60079-31: 2009
EN 60079-1: 2007
EN 61241-0: 2006
EN 60079-11: 2012
EN 61241-1: 2004
EN 60079-15: 2010
EN 61241-11: 2006
Special Conditions of Use
Intrinsically Safe
This equipment is intrinsically safe and can be used in potentially explosive atmospheres.
The electrical parameters of certified equipment which can be connected to the device must not exceed the following
values:
U
0
≤
30 VDC
I
0
≤
150 mA
P
0
≤
1.25 W
Ambient temperature:
T6, at Tamb = 47
_
C
T5, at Tamb = 62
_
C
T4, at Tamb = 82
_
C
Flameproof
The flame path is other than required by EN 60079‐1. Contact the manufacturer for information on the dimensions of
the flameproof joints.
Electrical connections are typically made using either cable or conduit.
D
If using a cable connection, the cable entry device shall be certified in type of explosion protection flameproof
enclosure “d”, suitable for the conditions of use and correctly installed.
For ambient temperatures over 70
_
C, cables and cable glands suitable for at least 90
_
C shall be used.
D
If using a rigid conduit connection, an Ex d certified sealing device such as a conduit seal with setting compound
shall be provided immediately to the entrance of the enclosure.
For ambient temperatures over 70
_
C, the wiring and setting compound in the conduit seal shall be suitable for at least
90
_
C.
Type n
No special conditions for safe use.