Instruction Manual
D200149X012
3610J and 3620J Positioners
September 2017
3
Table 1. Specifications
Unless otherwise specified, the specifications listed
are for all positioner type numbers
Available Configurations
Refer to the type number description
Input Signal
3610J, 3610JP, and 3611JP:
Standard:
J
0.2 to 1.0
bar (3 to 15 psig),
J
0.4 to 2.0 bar (6 to 30 psig), or
J
Adjustable:
Zero is adjustable from 0.07 to 1.5 bar
(1 to 22 psig) for standard valve rotations or valve
travels. Span is adjustable from 0.2 to 2.0 bar (3.2 to
28.8 psi) for standard valve rotations or valve travels.
Adjustment locations are shown in figure 13.
3620J, 3620JP, and 3621JP:
4 to 20 mA DC constant
current with 30 VDC maximum compliance voltage.
Minimum terminal voltage is 2.4 VDC at 20 mA. Split
range is also available, see table 12.
Equivalent Circuit
3620J, 3620JP, and 3621JP:
120 ohms shunted by
three 5.6 V zener diodes
Output Signal
Pneumatic pressure as required by the actuator up to
full supply pressure
Action
:
Field‐reversible between
J
direct and
J
reverse within the pneumatic positioner
Typical Performance for 3610J, 3610JP, 3620J, and
3620JP Positioners with 1051, 1052, and 1061
Actuators
Independent Linearity
Direct‐Acting 3610J and 3620J:
±
1.5% of output span
Reverse‐Acting 3610J and 3620J:
±
0.75% of output span
Direct‐Acting 3610JP and 3620JP:
±
1.25% of output
span
Reverse‐Acting 3610JP and 3620JP:
±
0.5% of output
span
Hysteresis
3610J:
1.0% of output span
3620J:
0.75% of output span
3610JP:
0.5% of output span
3620JP:
0.6% of output span
Deadband:
0.1% of input span
Refer to table 3 for typical performance for 3611JP
and 3621JP positioners
Electromagnetic Compatibility for 3622
electro‐pneumatic converter
Meets EN 61326‐1:2013
Immunity—Industrial locations per Table 2 of the
EN 61326‐1 standard. Performance is shown
in table 2 below.
Emissions—Class A
ISM equipment rating: Group 1, Class A
The electromagnetic compatibility specifications also
apply to 3620J, 3620JP, and 3621JP
electro‐pneumatic positioners.
Maximum Supply Air Demand
3610J and 3620J:
1.4 bar (20 Psig) Supply:
13 normal m
3
/hour (490 scfh)
2.4 bar (35 Psig) Supply:
17 normal m
3
/hour (640 scfh)
3610JP, 3620JP, 3611JP, and 3621JP:
5.2 Bar (75 Psig) Supply:
37 normal m
3
/hour
(1380 scfh)
6.9 Bar (100 Psig) Supply:
46 normal m
3
/hour
(1700 scfh)
Operating Influences for 3610J, 3610JP, 3620J, and
3620JP
Supply Pressure Sensitivity:
A 10% change in supply
pressure changes the valve shaft position less than
the following percentages of valve rotation:
3610J and 3620J:
1.0% at 1.4 bar (20 psig) supply
pressure
3610JP and 3620JP:
1.5% at 4.1 bar (60 psig) supply
pressure
Supply Pressure
Minimum Recommended:
0.3 bar (5 psig) above
actuator requirement [1.4 bar (20 psig) for a 0.2 to
1.0 bar (3 to 15 psig) nominal actuator signal; 2.4 bar
(35 psig) for a 0.4 to 2.0 bar (6 to 30 psig) nominal
actuator signal]
Maximum:
10.3 bar (150 psig) or maximum pressure
rating of the actuator, whichever is lower
- continued -