Instruction Manual
D200149X012
3610J and 3620J Positioners
September 2017
8
WARNING
Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion,
and area re‐classification.
CSA
Intrinsically Safe, Explosion-proof, Type n, Dust‐Ignition proof, DIV 2
No special conditions for safe use.
Refer to table 4 for approval information.
Table 4. Hazardous Area Classifications for Fisher 3622 Converter
—CSA (Canada)
Certification Body
Certification Obtained
Entity Rating
Temperature Code
CSA
Intrinsically Safe
Ex ia IIC T4/T5/T6 per drawing GE28591 (see figure 31)
Ex ia Intrinsically Safety
Class I, II Division 1 GP A,B,C,D,E,F,G
T4/T5/T6 per drawing GE28591 (see figure 31)
Vmax = 30 VDC
Imax = 150 mA
Pi = 1.25 W
Ci = 0 nF
Li = 0 mH
T4 (Tamb
≤
82
°
C)
T5 (Tamb
≤
62
°
C)
T6 (Tamb
≤
47
°
C
Explosion-proof
Ex d IIC T5
Class I, Division I, GP A,B,C,D T5
- - -
T5 (Tamb
≤
82
°
C)
Type n
Ex nA IIC T6
- - -
T6 (Tamb
≤
82
°
C)
Class I, Division 2, GP A,B,C,D T6
- - -
T6 (Tamb
≤
82
°
C)
Class II, Division 1, GP E,F,G T5
T5 (Tamb
≤
82
°
C)
Class II, Division 2, GP F,G T6
T6 (Tamb
≤
82
°
C)
1. These hazardous area classification also apply to 3620J positioners.
FM
Intrinsically Safe, Explosion-proof, Type n, Dust‐Ignition proof, Non‐incendive
No special conditions for safe use.
Refer to table 5 for approval information.
Table 5. Hazardous Area Classifications for Fisher 3622 Converter
—FM (United States)
Certification Body
Certification Obtained
Entity Rating
Temperature Code
FM
Intrinsically Safe
Class 1 Zone 0 AEx ia IIC T4/T5/T6 per drawing GE28590 (see figure 32)
Class I, II, III Division 1 GP A,B,C,D,E,F,G T4/T5/T6
per drawing GE28590 (see figure 32)
Vmax = 30 VDC
Imax = 150 mA
Pi = 1.25 W
Ci = 0 nF
Li = 0 mH
T4 (Tamb
≤
82
°
C)
T5 (Tamb
≤
62
°
C)
T6 (Tamb
≤
47
°
C)
Explosion-proof
Class 1 Zone 1 AEx d IIC T5
Class I, Division I, GP A,B,C,D T5
- - -
T5 (Tamb
≤
82
°
C)
Type n
CL 1 Zone 2 AEx nA IIC T5
- - -
T5 (Tamb
≤
82
°
C)
Class I, Division 2, GP A,B,C,D T5
Class II, Division 1, GP E,F,G T5
Class II, Division 2, GP F,G T5
- - -
T5 (Tamb
≤
82
°
C)
1. These hazardous area classification also apply to 3620J positioners.