Instruction Manual
D101728X012
3710 and 3720 Positioners
September 2017
5
Table 3. Input Signal Range
POSITIONER
INPUT SIGNAL RANGE
Pneumatic
Electronic
3710
w/3 to 15 psig span adj. ass'y
(no color coding)
J
0.2 to 1.0 bar (3 to 15 psig)
J
0.2 to 0.6 bar (3 to 9 psig) and
0.6 to 1.0 bar (9 to 15 psig), split‐ranging
–––
3710
w/6 to 30 psig span adj. ass'y
(red color coding)
J
0.4 to 2.0 bar (6 to 30 psig)
J
0.4 to 1.2 bar (6 to 18 psig) and
1.2 to 2.0 bar (18 to 30 psig), split‐ranging
–––
3720
–––
J
4-20 mA DC
J
4-12 mA DC or 12-20 mA DC, split‐ranging
Positioner to Actuator Mountings List
The positioner mounts directly to the actuator cover plate of Fisher 1051, 1052, and 1061 actuators. See table 4 for
actuator sizes.
Figure 2 shows a positioner ready for mounting on a piston rotary actuator. A mounting plate (key 43) is used to
mount the positioner base plate to Fisher 1051, 1052, 1061, 1066, and 2052 actuators. See table 4 for actuator sizes.
The positioner also mounts on a Fisher 585 and 585R size 25 or 50 sliding‐stem actuator. A mounting plate (key 43) is
used to mount the positioner base plate to the actuator.
W6059‐1
MOUNTING
SCREW
FEEDBACK
SHAFT
MOUNTING SCREWS
TIE BAR
EXTENSION (KEY 44)
POSITIONER
MOUNTING
PLATE (KEY 43)
Figure 2. Mounting the Positioner Base Plate