Instruction Manual
D103292X012
C1 Controllers and Transmitters
March 2017
32
Figure 15. Connecting Link
CONNECTING
LINK (KEY 16)
PROPERLY ALIGNED
CONNECTING LINK
BINDING CONNECTING LINK
(IMPROPERLY ALIGNED)
BEAM
(KEY 39)
WASHER
(KEY 62)
LINK BEARING
(KEY 31)
BOURDON TUBE
(KEY 5)
WASHER
(KEY 62)
LINK BEARING
(KEY 31)
WASHER (QTY 2)
(KEY 62)
BEAM
(KEY 39)
CONNECTING
LINK (KEY 16)
GE37119
BOURDON TUBE
(KEY 5)
11. Check all tubing connections for leaks and the Bourdon tube machine screws, tighten as necessary. Perform the
appropriate calibration procedures.
Replacing Bellows Sensing Element
Refer to figure 25 for key number locations unless otherwise directed.
1. Shut off the supply pressure and process lines to the controller or transmitter.
2. Disconnect the tubing from the mounting base (key 57) and calibration adjuster (key 36). Disconnect the tubing
case.
4. Remove the bellows yoke machine screws and washers (keys 98 and 99), and move the bellows yoke to the right to
permit access to the link screw.
5. Disconnect the link (key 71M) and bearing (key 71L) from the beam. Be careful to avoid losing the bearing.
6. Loosen the nuts that secure the bellows assembly (key 71), and remove this assembly from the bellows yoke
(key 100).
7. For a gauge-pressure sensing element (only one bellows in the assembly), install the proper bellows spring
(key 104) into the bellows assembly if the input signal range is being changed.
8. Install the new bellows assembly into the bellows yoke.
9. Attach the link and bearing to the bellows assembly. Position the bellows yoke (key 100) on the mounting base
(key 57), and attach the link and bearing to the beam. Start but do not tighten the four machine screws (key 98)
with washers (key 99) that attach the yoke to the mounting base. Slide the yoke up or down as necessary to position
the beam horizontally, as shown in figure 25. Tighten the machine screws.
all tubing.
11. If a bellows assembly with a different range is installed, remove the machine screw and washer (keys 61 and 60) and
dial (key 6), and install a new dial having an adjustment range corresponding to the range of the bellows. If an
optional process pressure gauge (key 4, figure 22) is being used, install a new gauge with the appropriate
measurement capability.