Corrective Maintenance

The most likely malfunction of a loop containing an HF340 filter is reverse polarity installation of one of the wire pairs.
The HF340 filter will work with either polarity, but misconnection could result in the wrong polarity reaching the field
instrument. If the loop is not operating properly, check the polarity of the voltage at the inputs and outputs of the filter
and at the inputs of the instrument.

If the instrument appears to operate properly in the loop, but communication with a non‐isolated multiplexer or PC
modem is not possible, it may help to reverse the wires to the COMM terminals. The HF340 filter inserts a high
impedance in the + side of the loop only. A reversal of the connections to the SYS and FLD terminals of the filter will
result in the control loop operating properly, but inoperative HART communication.

Inadequate control system compliance voltage will not support filter operation. This is an installation problem that
may appear initially to be a filter malfunction. For the filter to operate properly, the control system must have a
compliance voltage that is at least 2 volts higher than the voltage required to drive the loop to maximum current.
Refer to the appropriate instrument instruction manual for information on determining the control system
compliance voltage.

The HF340 filter is protected against accidental over‐current from sources up to 30 volts DC. If an over‐current
condition occurs, the filter may be inoperative for several seconds thereafter.

Summary of Contents for Fisher HF340 HART

Page 1: ...signal to the FIELDVUE instrument Do not install operate or maintain an HF340 filter without being fully trained and qualified in valve actuator and accessory installation operation and maintenance To avoid personal injury or property damage it is important to carefully read understand and follow all of the contents of this manual including all safety cautions and warnings If you have any question...

Page 2: ... I O signal control Burst IEC 61000 4 4 1 kV A Surge IEC 61000 4 5 1 kV line to ground only each A Conducted RF IEC 61000 4 6 150 kHz to 80 MHz at 3 Vrms A A During testing normal performance within the specification limits 1 Not applicable only applicable to magnetically sensitive equipment Description The HF340 filter is used with HART communicating FIELDVUE instruments such as DVC6200 DVC6000 o...

Page 3: ...t cases if an IS barrier is used the filter will not be needed Specifications Typical specifications for the HF340 filter are shown in table 1 Installation Refer to figure 2 for typical installations The HF340 filter mounts on a type 35 DIN rail To install the filter provide a temporary means of process control then take the loop out of service Remove the DIN interconnect blocks from the rail with...

Page 4: ...ides of the filter the shield should connect across the filter If the filter connects directly to the control system output and shielded loop wiring is being used connect the shield to system ground on the instrument side of the filter HART Wiring Connections The COMM terminals on the filter provide a convenient means to tap into the loop wiring for HART communication A HART communicating device s...

Page 5: ...40 filter inserts a high impedance in the side of the loop only A reversal of the connections to the SYS and FLD terminals of the filter will result in the control loop operating properly but inoperative HART communication Inadequate control system compliance voltage will not support filter operation This is an installation problem that may appear initially to be a filter malfunction For the filte...

Page 6: ...te Neither Emerson Emerson Process Management nor any of their affiliated entities assumes responsibility for the selection use or maintenance of any product Responsibility for the selection use and maintenance of any product remains with the purchaser and end user ...

Page 7: ...Instruction Manual D102796X012 HF340 Filter July 2011 7 ...

Page 8: ...e reserve the right to modify or improve the designs or specifications of such products at any time without notice Neither Emerson Emerson Process Management nor any of their affiliated entities assumes responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any product remains solely with the purchaser and end user EFisher Cont...

Reviews: