background image

Type HSR regulators provide internal relief that limits the 

total outlet pressure buildup over setpoint. This internal 

relief may be adequate for the application, if not, provide 

additional pressure relief or a pressure-limiting device 

downstream. Regulators should be inspected for damage 

after any overpressure condition.

!

WARnInG

To avoid personal injury or property 

damage due to explosion or damage to 

regulator or downstream components 

during startup, release downstream 

pressure to prevent an overpressure 

condition on the diaphragm of 

the regulator. 
In order to avoid an overpressure 

condition and possible equipment 

damage, pressure gauges should 

always be used to monitor pressures 

during startup.

Startup

With proper installation completed, slowly open the 

shutoff valve. Check all connections for leaks. Check 

the downstream equipment for proper operations.

Adjustment

To increase the outlet pressure setting, turn 

the adjusting screw clockwise. To reduce the 

outlet pressure setting, turn the adjusting screw 

counterclockwise. A pressure gauge should always 

be used to monitor downstream pressure while 

adjustments are being made. Do not adjust the spring 

to produce an outlet pressure setting above the limit 

identified on the information label. If the required 

pressure setting is not within the range of the spring 

being used, substitute with the correct spring. When 

changing the spring, also change the range identified 

on the information label to indicate the actual pressure 

range of the spring in use. After the spring adjustment 

has been completed, replace the closing cap.

Taking Out of Service (Shutdown)

!

WARnInG

To avoid personal injury resulting from 

sudden release of pressure, isolate 

the regulator from all pressure before 

attempting disassembly.  

Before installing the regulator, check for damage 

which might have occurred in shipment. Also check 

for dirt or foreign matter which may have accumulated 

in the regulator body or in the pipeline. Apply pipe 

compound to the male threads of the pipeline 

and install the regulator so that the flow is in the 

direction of the arrow cast on the side of the body. 

The diaphragm actuator assembly can be rotated to 

any position relative to the body, in 90° increments. 

Remove the two cap screws that hold the body 

to the actuator in order to rotate the diaphragm 

actuator assembly.

Do not install the regulator in a location where there 

can be excessive water accumulation, such as directly 

beneath a downspout or in an undrained pit.

To obtain the maximum flow capacities or other 

performance characteristics, the length of pipe from 

the regulator outlet to the meter should have no bends 

and should be the same size as the regulator outlet. 

Replace the regulator if water gets into the spring case 

or the lower casing of the regulator.

CAuTIOn

You are advised to use new vent 

piping because defective threads on 

the relief vent piping may interfere 

with the venting assembly if the 

piping obstructs the movement of the 

vent flapper.

On indoor installations, the vent should be piped 

outside the building. Remove the screen from the 

regulator vent connection and connect vent piping 

from that connection to the outdoors. Install a weather 

and insect resistant vent assembly on the outside 

end of the pipe. Inspect the vent opening regularly. 

On some installations, it may be necessary to install 

the regulator beneath a protective hood. The vent 

should be pointing or sloping down sufficiently to allow 

any condensate to drain. Also check the regulator 

periodically for external or internal corrosion.

Overpressure Protection

!

WARnInG

Some type of overpressure protection 

is needed if actual inlet pressure can 

exceed the outlet pressure rating. 

Overpressuring any portion of this 

equipment may cause damage to 

regulator parts, leaks in the regulator 

or personal injury due to bursting of 

pressure-containing parts or explosion 

of accumulated gas.

Type HSR

2

VCIGD-11698-EN.indd   2

2/22/2019   7:46:25 PM

Summary of Contents for Fisher HSR Series

Page 1: ...pment damage or leakage due to escaping gas or bursting of pressure containing parts might result if these regulators are overpressured or installed where service conditions could exceed the limits for which the regulators were designed or where conditions exceed any ratings of the adjacent piping or piping connections To avoid such injury or damage provide pressure relieving or pressure limiting ...

Page 2: ...foreign matter which may have accumulated in the regulator body or in the pipeline Apply pipe compound to the male threads of the pipeline and install the regulator so that the flow is in the direction of the arrow cast on the side of the body The diaphragm actuator assembly can be rotated to any position relative to the body in 90 increments Remove the two cap screws that hold the body to the act...

Page 3: ...anges outlet pressure range Spring color mbar In w c 10 to 15 4 to 6 Orange 15 to 20 6 to 8 Yellow 20 to 25 8 to 10 Black 25 to 31 10 to 12 5 Silver 31 to 50 12 5 to 20 Gray 50 to 87 20 to 35 Pink 0 09 to 0 15 bar 1 25 to 2 2 psig Light Blue T80573 Key Description 13 Lower Spring Seat 14 Relief Spring Retainer 15 Body 16 O ring 17 Cap Screw 22 Orifice 23 Disk 25 Spring 26 Adjusting Screw 27 Inform...

Page 4: ...ment Regulator Technologies Inc All rights reserved 02 19 The Emerson logo is a trademark and service mark of Emerson Electric Co All other marks are the property of their prospective owners Fisher is a mark owned by Fisher Controls International LLC a business of Emerson Automation Solutions The contents of this publication are presented for information purposes only and while effort has been mad...

Reviews: