background image

S201 and S202 Series

4

Before installing the regulator, check for damage 

which might have occurred in shipment.  Also check 

for dirt or foreign matter which may have accumulated 

in the regulator body or in the pipeline.  Apply pipe 

compound to the external threads of the pipeline and 

install the regulator so that flow is in the direction of 

the arrow cast on the body.  The diaphragm casing 

assembly can be rotated to any position relative to the 

body.  Loosen the two cap screws (key 18, Figure 5) in 

order to rotate the diaphragm casing assembly.  
Do not install the regulator in a location where there 

can be excessive water accumulation, such as directly 

beneath a downspout.
If the regulator is used in conjunction with a Type 289H 

relief valve, it should be installed as shown in Figure 4.  

The outside end of the vent line should be protected 

with a rainproof assembly. 
The Type 289H should be set 10-inches w.c. (25 mbar) 

higher than the outlet pressure setting of the regulator, 

up to 30-inches w.c. (75 mbar) outlet pressure.  For 

pressure greater than this, set the Type 289H 0.75 psi 

(0,05 bar) higher than the outlet pressure setting of  

the regulator.
The S201 and S202 Series regulators have 1 NPT 

screened vent openings in the spring case.  If 

necessary to vent escaping gas away from the 

regulator, install a remote vent line in the spring 

case tapping.  Vent piping should be as short and 

direct as possible with a minimum number of bends 

and elbows.  The remote vent line should have the 

largest practical diameter.  Vent piping on regulators 

with internal relief (Types S202 and S202H) must 

be large enough to vent all relief valve discharge to 

atmosphere without excessive backpressure and 

resulting excessive pressure in the regulator.

Periodically check all vent openings to be sure that 

they are not plugged.

Maximum outlet pressure settings are shown in 

Table 2.  Outlet pressure more than 2 psi (0,14 bar) 

(light diaphragm head) or 3 psi (0,21 bar) (heavy 

diaphragm head) above the setpoint may damage 

internal parts such as the diaphragm head and valve 

disk.  

The maximum emergency (casing) outlet 

pressure is 15 psig (1,0 bar).

Startup

CAUTION

Pressure gauges should always be used 

to monitor downstream pressure during 

startup.  Procedures used in putting this 

regulator into operation must be planned 

accordingly if the downstream system is 

pressurized by another regulator or by a 

manual bypass.

If the downstream system is not pressurized by 

another regulator or manual bypass valve, use the 

following procedure to startup the regulator.

Table 1.  Maximum Allowable Inlet Pressures

Table 2.  Maximum Outlet Pressure Setting

ORIFICE SIzE

INLET PRESSURE SETTING

Inches

mm

Optimum

Maximum

Psig

bar

Psig

bar

1/4

6,3

125

8,6

125

8,6

3/8

9,5

100

6,9

125

8,6

1/2

13

60

4,1

100

6,9

3/4

19

25

1,7

60

4,1

1

25

13

0,90

25

1,7

1-3/16

30

5

0,34

13

0,90

TyPE NUMBER

DIAPhRAGM hEAD

MAxIMUM OUTLET*

S201, S202

Light

30-inches w.c.  (75 mbar)

S201H, S202H

Heavy

5 psig  (0,34 bar)

S201K

Heavy

10 psig  (0,69 bar)

  * Maximum emergency outlet (casing) pressure for S200 Series is 15 psig  (1,0 bar).

Table 3.  Outlet Pressure Ranges

TyPE NUMBER

SPRING RANGE

PART NUMBER

SPRING FREE 

LENGTh,

INChES (mm)

SPRING WIRE 

DIAMETER,

INChES (mm)

COLOR CODE

Inches w.c.

mbar

S201 and S202

2.0 to 4.5

3.5 to 6.5

5.0 to 9.0

8.5 to 18.0

14.0 to 30.0

5 to 11

9 to 16

12 to 22

21 to 45

35 to 75

1D892527022

1D892627022

1D892727012

1D893227032

1D893327032

6.12 (155)

7.53 (191)

7.88 (200)

7.50 (191)

7.25 (184)

0.109 (2,77)

0.112 (2,84)

0.130 (3,30)

0.156 (3,96)

0.182 (4,62)

Brown

Red

Black

Gray

Dark Green

S201H and S202H

1.0 to 2.0 psig

1.5 to 3.25 psig

2.0 to 5.0 psig

0,07 to 0,14 bar

0,10 to 0,22 bar

0,14 to 0,34 bar

1H975827032

1H975927032

1P615427142

7.09 (180)

6.91 (176)

6.50 (165)

0.225 (5,72)

0.250 (6,35)

0.295 (7,49)

Dark Blue

Orange

Yellow

S201K

2.0 to 5.5 psig

4.0 to 10.0 psig

0,14 to 0,38 bar

0,28 to 0,69 bar

0Y066427022

1H802427032

6.00 (152)

6.00 (152)

0.363 (9,22)

0.406 (10,3)

Green Stripe

Cadmium

Summary of Contents for Fisher S202

Page 1: ...ulator Warning Figure 1 Typical S200 Gas Regulator W1919 Introduction Scope of the Manual This instruction manual provides instructions for installation adjustment maintenance and parts ordering information for Types S201 S201H S201K S202 and S202H gas service regulators Description S201 and S202 Series regulators are typically installed on industrial and commercial applications The Types S202 and...

Page 2: ...Typical start to discharge values are 7 inches w c to 2 psi 17 to 138 mbar above the outlet pressure setting depending on control spring used Available Configurations See Figure 3 Body Size and End Connection Styles 1 1 2 or 2 NPT inlet and outlet and NPS 2 DN 50 CL125 FF flanged Maximum Allowable Inlet Pressures 1 See Table 1 Maximum Emergency Outlet Pressure 1 15 psig 1 0 bar Outlet Pressure Ran...

Page 3: ...utdoor installations point the spring case vent downward to allow condensate to drain see Figure 4 This minimizes the possibility of freezing and of water or other foreign materials from entering the vent and interfering with proper operation Under enclosed conditions or indoors escaping gas may accumulate and be an explosion hazard In these cases the vent should be piped away from the regulator t...

Page 4: ...le 2 Outlet pressure more than 2 psi 0 14 bar light diaphragm head or 3 psi 0 21 bar heavy diaphragm head above the setpoint may damage internal parts such as the diaphragm head and valve disk The maximum emergency casing outlet pressure is 15 psig 1 0 bar Startup caution Pressure gauges should always be used to monitor downstream pressure during startup Procedures used in putting this regulator i...

Page 5: ...pressure and relieving all internal pressure as described in Shutdown Regulators that have been disassembled for repair must be tested for proper operation before returned to service Only parts manufactured by Emerson Process Management Regulator Technologies Inc should be used for repairing Fisher regulators Relight pilot lights according to normal startup procedures Due to normal wear or damage ...

Page 6: ... tear the diaphragm when reassembling 6 Reassemble the spring case unit in the reverse order of the above steps Before tightening the cap screw or stem into the pusher post place the loosely assembled diaphragm and diaphragm head assembly into position in the lower casing being sure that the pusher post is hooked on the lever Rotate the diaphragm so that the diaphragm and lower casing holes are al...

Page 7: ... and S202 Series 7 Figure 5 Type S202 Regulator Assembly 50A9455 parts not shown 46 apply LUB SEA ADH section a a A A VENT 62 61 58 55 60 56 57 59 18 4 5 3 2 6 8 9 7 1 32 14 15 10 25 16 13 21 20 19 12 11 24 ...

Page 8: ... Management Regulator Technologies Inc USA Headquarters McKinney Texas 75069 1872 USA Tel 1 800 558 5853 Outside U S 1 972 548 3574 Asia Pacific Singapore Singapore 128461 Tel 65 6777 8211 Europe Bologna Italy 40013 Tel 39 051 4190611 Gallardon France 28320 Tel 33 0 2 37 33 47 00 TESCOM Emerson Process Management Tescom Corporation USA Headquarters Elk River Minnesota 55330 2445 USA Tel 1 763 241 ...

Reviews: